BP 15-xx

Ring type instrument transformers

Insulation voltage
Rated primary current

kV

17,5

2000 10000

Highest internal diameter

mm

210 350

Minimum internal diameter of bushing

mm

592 720

0,2; 0,5; 5P

Accracy class

Description
The BP 15-60.3, BP 15-60.2, BP 15-60, BP 15-100 transformers are used for measurement and
protections as a built-in, encapsulated devices in the outlets of alternatots. The rated voltages of up to
17,5 kV and rated currents of up to 10 000 A and the transformer design meets the most exigent
parameters for operation in severe climatic conditions.
The transformer has a three-core, two-core,one-core, ring type, through-going conductor and cylindrical
shape design with special outlets for mounting into the alternator enclosure.
The feed through hole is provided with a metalic screening electrode which is embedded into epoxi
material. The outlet of screening electrode has to be connected with a high voltage potential conductor,
to prevent the ionization of air.
Other technical parameters as per this specification should be agreed separately with manufacturer.

Technical parameters
Type

BP 15-60

BP 15-100

BP 15-60.3

BP 15-60.2

Highest external wire diameter

mm

210

350

264

264

Minimum internal diametr of bushing

mm

592

720

632

632

Insulation voltage

kV

17,5

17,5

17,5

17,5

Testing AC voltage

kV

45

45

45

45

Rated primary current

2000 - 6000

6000 10 000

2000 - 6000

2000 - 6000

Rated power

VA

Accuracy class

30, 45, 60, 90, 120

Weight

0,2; 0,5; 5P

kg

78

102

102

60

Dimensions

Type

BP 15-60.3

264

610

287

170

85

220

BP 15-60.2

264

610

215

98

49

148

BP 15-60

210

582

231

120

60

180

BP 15-100

350

710

233

124

62

180

1VLC000514 Rev -, en 2004.02.10

ABB s.r.o.
Videnska 117
619 00 Brno, Czech Republic
E-mail: info.ejf@cz.abb.com
http://www.abb.com

Tel.: +420 547 152 602


+420 547 152 604
Fax: +420 547 152 626

The data and ilustrations in this catalogue are not binding.