6.2 The Circuit Breaker Shall Be Capable of

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Duty same as under (i) above.

The first, third and fourth closures are to be on deenergised line while second closing is to be made with lines against trapped charge of
1.2 p.u. (Based on 1 pu = 653kV) of opposite polarity.
iii) OUT OF PHASE CLOSING
One closing operation under phase opposition that is with twice the voltage across the
terminals.
iv) No allowance shall be made for heat dissipation of resistor during time interval
between successive closing operations. The resistors and resistor supports shall
perform all these duties without deterioration. Calculations and test reports of resistors
proving thermal rating for duties specified above shall be furnished along with the bid.
The calculations shall take care of adverse tolerances on resistance values and time
settings.
6.2

The circuit breaker shall be capable of:


i)

Interrupting the steady and transient magnetizing current corresponding to 400 kV/220 kV
class transformers of 250 MVA to 630 MVA ratings on both 400 kV & 220 kV side.

ii)

Interrupting line/cable charging current as per IEC without re-strikes and without use of
opening resistors.

iii) Clearing short line fault (Kilometric faults) with source impedance behind the bus
equivalent to symmetrical fault current specified.
iv)

Breaking 25% the rated fault current at twice the rated voltage under phase opposition
condition.

v)

The breaker shall satisfactorily withstand the high stresses imposed on them during fault
clearing, load rejection and re-energisation of lines with trapped charges.

vi) 400 kV breakers shall be able to switch in and out the 400 kV shunt reactor for any value
from 50 MVAR up to 80 MVAR without giving rise to overvoltage more than 2.3 p.u.
Laboratory test and or field test reports in support of the same shall be furnished along
with the bid.
6.3

Total Break Time


The total break time shall not be exceeded under any of the following duties :
i)

Test duties T10,T30,T60,T100 (with TRV as per IEC- 62271-100 )

ii)

Short line fault L90, L75 (with TRV as per IEC-62271-100 )

ii)

The Contractor may please note that total break time of the breaker shall not be exceeded
under any duty conditions specified such as with the combined variation of the trip coil
voltage (70-110%), pneumatic/hydraulic pressure and SF6 gas pressure etc. While
14

VOL-II/SEC-1 (A): Technical Details of GIS Substation