TransferDiaphragm Wood
TransferDiaphragm Wood
TransferDiaphragm Wood
CLIENT :
JOB NO. :
PAGE :
DESIGN BY :
REVIEW BY :
DATE :
B=
L=
12
32
ft
ft
PANEL GRADE ( 0 or 1)
=
1
<= Sheathing and Single-Floor
MINIMUM NOMINAL FRAMING WITH ( 2 or 3) =
3
in
15/32 in
MINIMUM NOMINAL PANEL THICKNESS =
COMMON NAIL SIZE ( 0=6d, 1=8d, 2=10d )
1
8d
SPECIFIC GRAVITY OF FRAMING MEMBERS
0.43
FRAMING OF Douglas-Fir-Larch OR Southern Pine ?
Yes
`
ALLOWABLE SHEAR FORCE ON TRANSFER DIAPHRAGM SIDE
MAX. ALLOWABLE COLLECTOR (DRAG) FORCE
MAX. ALLOWABLE CHORD FORCE
V =
10
kips
T drag =
11
kips
T chord =
kips
ANALYSIS
CHECK MAX DIAPHRAGM DIMENSION RATIO (SDPWS-08, 4.2.4 & IBC 09, 2308.12.6)
L/B=
2.67
>
<
2.00
4.00
[Satisfactory]
CHECK DIAPHRAGM SHEAR CAPACITY (ACI 318-08, 21.11.9)
v = 1.25 V / L =
508
plf, ASD, (ASCE 7-05, 12.3.3.4 & Table 12.3-2.4)
=
where
1.3
(ASCE 7-05, 12.10.1.1 & 12.3.4.2)
[Satisfactory]
THE SHEAR CAPACITIES PER IBC Table 2306.2.1 / SDPWS-08 Table 4.2A with ASD reduction factor 2.0 :
Min.
Min.
Member
Blocked Nail Spacing
Panel Grade
Sheathing and Single-Floor
Common Penetration
Thickness
Width
Unblocked
Nail
(in)
(in)
(in)
6/6
4/6
2.5 / 4
2/3
Case 1
Others
8d
1 1/2
15/32
300
400
600
675
265
200
Note: The indicated shear numbers have reduced by specific gravity factor per SDPWS-08 Table 4.2A note
16.3
kips