Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

Sprinklers system design

Type of sprinklers
-Wet pipe systems
They are simple, with the only operating components being the automatic sprinklers.
An automatic water supply provides water under pressure to the system piping. All of
the piping is filled with water. Until sufficient heat is applied, causing one or more
sprinklers to fuse (open), the automatic sprinklers prevent the water from being
discharged.
Operation - When an automatic sprinkler is exposed to sufficient heat, the heat
sensitive element (glass bulb or fusible link) releases, allowing water to flow from that
sprinkler. Sprinklers are manufactured to react to a specific range of temperatures.

-Dry pipe systems


Water is not present in the piping until the system operates.
When one or more of the automatic sprinklers is exposed to sufficient heat, it opens, allowing
the maintenance air to vent from that sprinkler.
Each sprinkler operates individually. As the air pressure in the piping drops, the pressure
differential across the dry pipe valve changes, allowing water to enter the piping system. Water
flow from sprinklers needed to control the fire is delayed until the air is vented from the
sprinklers. For this reason, dry pipe systems are usually not as effective as wet pipe systems in
fire control during the initial stages of the fire.

-Deluge systems
"Deluge" systems are systems that have open sprinklers, the heat sensing operating element is
removed or specifically designed open sprinklers, so that all sprinklers connected to the water
piping system are open. These systems are used for special hazards where rapid fire spread is a
concern, as they provide a simultaneous application of water over the entire hazard. They are
commonly seen as preventive measures to prevent egress of fire from an external source.
Water is not present in the piping until the system operates. Because the sprinkler orifices are
open, the piping is at atmospheric pressure. To prevent the water supply pressure from forcing
water into the piping, a deluge valve is used in the water supply connection, which is a
mechanically latched valve. It is a non-resetting valve, and stays open once tripped.

-Hybrid system Preaction-system


A combination of previous types
2 subcategories of Hybrid system do exist
-single interlock that act like dry system except these systems require
that a preceding fire detection event, typically the activation of a heat
or smoke detector, takes place prior to the action of water
introduction into the systems piping by opening the pre-action valve.

-double interlock similar to deluge systems except that automatic


sprinklers are used.
Activation of either the fire detectors alone, or sprinklers alone, without
the concurrent operation of the other, will not allow water to enter the
piping

-Classification of Occupancies
sprinkler design and installation are directly related to the classification
of occupancy .
We Have :
*Light Hazard Occupancies
-Low combustibility , Low rate of heat release.
*Ordinary Hazard Occupancies
-Ordinary Hazard (Group 1) Low combustibility
-Ordinary Hazard (Group 2) Moderate to high combustibility
*Extra Hazard Occupancies
-Extra Hazard (Group 1) High combustibility with great probability of
rapidly developing fire .
-Extra Hazard (Group 2) Moderate amount of flammable liquids exist
*Commodity Classification.
4 classes exist according to the type of materials which are in their turn
classified into 3 groups .

System Hardwares
sprinklers shall be permanently marked with a one- or two-character manufacturer symbol,
followed by three or four numbers, in order to determine the characteristic of each one .
Sprinklers have standardized discharge characteristics where The K-factor Is one of them
which describe the size and shape of the sprinklers orifice .

Governing equation for sprinklers dicharge

P:pressure in PSI
Q:Flow rate IN GPM

-Another characteristic that must be taken in consideration is :Temperature


Automatic sprinklers shall have their frame arms, deflector, coating material, or liquid bulb
colored in accordance with the requirements of Table 6.2.5.1NFPA13.
Pipe and tubes above ground are also standardized

Please check NFPA 13 , 6.3.1.2 , 6.3.2, 6.3.3, 6.3.4. , and Table 6.3.6.1 , Table 6.3.1.1 for steel , copper and Chlorinated polyvinyl
chloride pipes and tubes specifications.
ASTM: International develops international standards for materials, products, systems and services used in construction, manufacturing and
transportation.
AWS: American Welding Society .

FOAM WATER SPRINKLER


The Foam-Water Sprinklers are used to protect the risk where foam is required to be
applied from overhead sprinklers and is to be followed with plain water in a standard
sprinkler pattern.
Foam Water Sprinklers protect the loading and unloading area in the event of a spill fire
with low
expansion foam systems. These are useful in otherwide applications including Air Craft
Hangers.

SPECIFICATION
Foam Water Sprinklers are open and air aspirating type. The pattern of coverage is
similar to the
conventional sprinkler head. The Foam Water Sprinkler has standard orifice with Kfactor of 42.
Foam Water Sprinklers are designed to operate at a minimum of 2 bar pressure and
maximum of 4.1 bar.The Foam Water Sprinkler with K-42 will deliver about 61 LPM at 2
bar pressure. The standard coverage per Foam Water Sprinkler is 9.3sq.m. (100 sq.ft.)

Pre-action and Deluge system Requirements


-Pressure gauges must be installed above and below preaction valve and below deluge valve
-Spacing of detection devices, including automatic sprinklers used as detectors, shall be in accordance with
their listing and manufacturer's specifications.
-Not more than 1000 automatic sprinklers shall be controlled by any one preaction valve.

The following types of sprinklers and arrangements shall be permitted for preaction systems:
(1) Upright sprinklers
(2) Pendent sprinklers and sidewall sprinklers installed on return bends, where the sprinklers, return bend,
and branch line piping are in an area maintained at or above 40F (4C)
(4) Horizontal sidewall sprinklers, installed so that water is not trapped
The difference between an upright head and a pendent head is, an upright sprinkler is designed to be
installed upright in the branchline piping of a sprinkler system. The pendent is designed to be in the pendent
or 6 o clock position, with the deflector facing downward.
We may use Anti-freeze agents according to the type of water supplied in the pipes Potable or non-potable
water check NFPA 13 Table 7.5.2.2 & Table 7.5.2.3

Hangers sprinkler specifications Group I


-In group I hangers we use Deluge Foam-Water Sprinklers
-The maximum distance between sprinklers either on branch lines or between branch
lines shall be 3.7 m (12 ft).
-System piping shall be hydraulically designed using the Hazen and Williams
formula where the coefficient C shall be taken as 120 in the calculations.
-The discharge devices shall have a minimum nominal 6.4-mm (-in.) orifice and shall be
listed for use with the particular type of foam concentrate to be used in the system.
- The discharge density from air-aspirating discharge devices using protein-type,
fluoroprotein-type, or AFFF-type foam solutions shall be a minimum of 8.1 L/min/m2
(0.20 gal of foam solution per min per ft2) of floor area and a minimum of 6.5 L/min/m2
(0.16 gal of foam solution per min per ft2) of floor area for non non air-aspirating
discharge devices.

Hangers sprinkler specifications Group IV


-In Group IV hangers we use Preaction system
- Sprinkler spacing shall be similar to group I
- The design density from sprinkler systems shall be a minimum of 6.9 L/min/m2.

Hydraulic Calculation
-Pipe sizes shall be no less than 1 in. (25.4 mm) nominal for ferrous piping and in. (19 mm)
nominal for copper tubing or nonmetallic piping listed for fire sprinkler service.
- The number of sprinklers per branch line, and number of branch lines per cross main shall
otherwise be limited only by the available water supply.
- Pipe friction losses shall be determined on the basis of the Hazen-Williams formula.
The Hazen-Williams equation for calculating the pressure drop due to friction for a given pipe
diameter and flow rate is as follow

The equation in metric units


*P = frictional pressire drop, kPa/m
*Q = flow rate, m^3/h
*D = pipe inside diameter, mm
*C = Hazen-Williams C factor, dimensionaless.

Hydraulic Calculation example :Tree system

We begin with the furthest sprinkle


-Assuming the density of discharge of the sprinkler is equal to :0.15
:0.15 gpm
gpm/ft
/ft sqr.
sqr.
-The area of application <<surface
surface area > is equal to 1500 ft sqr .
- Coverage / sprinkler = 130 ft sqr <calculated from sprinkler spacing >
-Number of sprinklers on branch line = 1.2 x radical(design area)/distance between sprinklers
1.2 x radical(1500)/13 = 3.58 >>> 4 sprinklers on each branch.
-We chose the type of sprinkler we want to use , we chose The nominal factor K <5.6>
We calculate the flow rate of the furthest sprinkle Q= Coverage per sprinkler X density of discharge
Q= 130 X 0.15 = 19.5 GPM
-we calculate the length of the pipe between the last sprinkler on that branch and the previous one + the
Hazen--Williams formula to calculate the fiction pressure /ft of
equivalent length of fittings , then we use the Hazen
pipe , using factor C , Diameter of the pipe , and the flow rate inside that pipe
Then we multiply Pf by the total equivalent length of that pipe .
We calculate the pressure at the furthest discharging sprinkler using Pt= (Q/K) square
We add Pt + Pf and we get the total pressure on the second sprinkler on the same branch

Steps continued in this table taken from NFPA 13 ,ANNEX A EXPLANATORY MATERIAL .

You might also like