MVSWGR Secc 2 MV Part MVSWGR Secc 2 LV Part: T Coil C Coil

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

13.

8KV Bus Bar

52MV1

1200A
MAIN
50KVA

PT to Secc4

T Coil
C Coil
PT from
Secc1

TC
Core 1:
600/5
xxVA
C100

PT Bus Bar

Core 2:
600/5
xxVA
C100

Trip to
52GCB1

Trip to H110

Square D SEPAM Relay S82-MCS025

Close
52
Trip to
52MV3
Trip to
52MV4

MVSWGR Secc 2 LV Part

Open/Trip
52

MVSWGR Secc 2 MV Part

Phase overcurrent (1) 50/51


Earth fault / Sensitive earth fault (1)
50N/51NG 50G/51
Breaker failure 50BF
Negative sequence / unbalance 46
Thermal overload for cables 49RMS
Directional phase overcurrent (1) 67
Directional earth fault (1) 67N/67NC
Directional active overpower 32P
Undervoltage (L-L or L-N) 27
Positive sequence undercurrent 27D
Remanent undervoltage 27R
Overvoltage (L-L or L-N) 59
Neutral voltage displacement 59N
Negative sequence overvoltage 47
Overfrequency 81H
Underfrequency 81L
Trip Circuit Sup 74
CT/VT sup 60
Synchro-check (4) 25
Latching / acknowledgement 86

PT to 115KV
27/25

Local, Remote,
Auto transf. Close

Interlocking permisive

Local, Remote,
Auto Transf. Open

13.8KV:120V

Modbus

Local/Remoto
Automatic/Manual
Ext. 87U, 50BF
MV3, MV4, P.TX-1

Communication Port to DCS.


Alarms.
Indications
Commands
Mesurement I,V, P,Q,S,F

To Tx-1
Proyecto: PIGAP II. Ingeniera Bsica Metal CLAD. 13.8KV. Elaborado por: Ing. Diego Quirs Ramos. Fecha Rev1:24-03-2012