Modern Petrofils

DTY Area
Basis of Design:
Temperature Condition:

Outside
Inside

Area
Height
Electrical Load
Lighting Load
Occupancy

:
:
:
:
:

DB
110
82.4

%
RH
28
60

WB
80
71.7

2250 sq.m ( 50x45)


6m
600 kW
1 w/sq.ft
60 People

New Air Quantity


:
115000 Cfm
New Requirement of Cooling Capacity for this ROOM Area: 280 TR.

TFO Area Humidification only with Air Washer


Basis of Design:
Temperature Condition:

Outside
Inside

Area
Height
Electrical Load
Lighting Load
Occupancy
New Air Quantity

:
:
:
:
:
:

DB
110
82.4

2250 sq.m ( 50x45)


5m
610 kW
1 w/sq.ft
60 People
260000 Cfm

%
RH
28
60

WB
80
71.7

PACKING AREA Humidification only with Air Washer


Basis of Design:
Temperature Condition:

Outside
Inside

Area
:
Height
:
Electrical Load
:
Lighting Load
:
Occupancy
:
Requirement of Air Quantity

DB
110
82.4

484 sq.m ( 22X22)


5m
37 kW
2 w/sq.ft
60 People
:
33000 Cfm

%
RH
28
60

WB
80
71.7

You might also like