Proposed solution
We chose to redesign the duct work as this is the most likely cause of
the problem.
Information Collected
Testing: Checked the cubic feet / minute (cfm) of the duct, it was about 2000
cfm to low.
Testing: The thermal expansion valve checked good, it responded to the
warming of the sensing bulb
Testing: One of the check valves tested badly. It had a 10 degree delta temp
across it. Indication a restriction.