How To Megger A Motor

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

How to Megger a Motor

Troubleshooting any electric motor can be accomplished with a simple volt ohm meter.
Sometimes, though, the motor has more problems than a simple meter can detect. This is
where the high-voltage Megger comes into play.

Instructions
1.
o

1
Put on safety glasses. Disconnect and remove all power sources to the motor
before attempting any type of repair. Double-check by using your volt ohm
meter to ensure that all power is shut off.

2
Remove the four screws that hold the motor's wire connection cover in place,
and set them aside. De-terminate, or unwire, the power wires from the motor
wires. You may have to identify the pairs with labels or numbers so proper
rotation can be maintained, especially in three-phase motors.

3
Attach one side of the Megger meter to one of the motor wires and the other to
the motor ground or metal case. Turn on the meter or crank the handle. The
meter's manufacturer should have reference readings for each meter.
Generally, a reading above 20 to 30 megohms should be sufficient to run most
motors. All new motors should read greater than 999 megohms; any reading
less than this indicates winding deterioration to the insulation.

4
Test each motor winding in turn, and record each set of windings, per the
megohm reading. If one of the legs has a very low reading, the motor should
be replaced. This will also result in a high amperage draw or frequent blown
fuses.