1. All Switches are in closed Position.

Phase A

Phase B

Phase C

Remarks

Way 1 Way 2
Way 2 Way 3
Way 3 Way 4

2. All Switches are in Ground Position.


Phase Ground ()

3. In case if there are parallel bushings:


A-A

B-B

C-C

Remarks

Criteria of Rejection:
1.
2.
3.
4.

Any way resistance (Including ground and Parallel) Value > 0.5 m.
Ground resistance for switches with GPLP modules > 0.6 m.
Variation between phases on same way > 0.1 m.
Any way resistance for MR & PI switches with parallel fuse > 0.7 m.
(Note: for Round Style So. Cal. Edision RP Switches (BURDS) Criteria # 1 applies.)