Professional Documents
Culture Documents
The Maintenance Managers' Guide To PFC Capacitor Banks
The Maintenance Managers' Guide To PFC Capacitor Banks
Power Quality
Main circuit-breaker
Capacitors banks
circuit-breaker
Three phase
load
PQ analyser
at point 1
Capacitors
Power Quality
Power Quality
http://www.leonardo-energy.org
Leonardo Energy wish to thank Eduwatt and the Copper Development Association UK for their valuable
technical contribution to this guide.
While this Guide has been prepared with care, ECI and other contributors provide no warranty with regard
to the content and shall not be liable for any direct, incidental or consequential damages that may result
from the use of the information or the data contained.
1.
The primary function of a capacitor bank is to control the displacement power factor (DPF), because in an ideal system
the voltage and current should be in phase. This is only true of a purely resistive load and most industrial loads have
an inductive component that causes the current waveform to lag the voltage waveform, which is where capacitors
play their primary role.
DPF is expressed as the cosine of the angle between the system voltage and the load current; ideally it should be unity
[the cosine of zero] but it is not that straightforward as a leading DPF, where the current is ahead of the voltage, must
be avoided; consequently the DPF correction systems are designed to keep the DPF close to unity, but always lagging
typically, the target is around 0.95 lagging.
The following text box describes the difference between Power Factor and Displacement Power Factor.
What is the difference between Power factor and Displacement power factor?
Power factor is the ratio of useful power delivered to the load to the apparent power consumed from the supply. Useful
power, measured in kW, is the product of the supply voltage and the real current (i.e the component that is in phase with
the voltage) consumed by the load, while apparent power, measured in kVA, is simply the product of supply voltage and
current magnitude.
Displacement power factor is the same, but only the fundamental frequency is considered in calculating the current
magnitude.
PQ analysers differentiate between DPF (or Cos 0) and PF and, before there were so many non-linear loads producing
harmonic currents, the two were effectively the same so it was unnecessary to differentiate between them unlike today,
when harmonic currents are universally present.
Capacitors can correct the DPF the fundamental component compensating the reactive component. Harmonic filters
can reduce the non-fundamental components.
DPF is important because the reactive component of the current the part that is responsible for the lag although
it does no useful work, still has to be transported through the electricity network. The reactive current does not
contribute to delivered energy, but it does contribute to losses, thus reducing the capacity of the increasingly
expensive electricity supply network resource. If nothing is done then the end customer has to pay for the cost of this
additional use of capacity in the form of a reactive power additional charge. Consequently, installing DPF correction
measures often makes economic sense.
Usually, DPF correction takes the form of a central bank of capacitors and a controller that monitors the load power
factor, adjusting the total capacitance as the load changes.
The effect is illustrated in these two diagrams. On the left there is no DPF correction and the green current curve
clearly lags the red voltage curve; on the right a degree of DPF correction has been added, reducing the displacement.
The DPF has been improved from 0.59 to 0.81 and the magnitude of the load current has been reduced by 40%.
The user will see a reduction in reactive demand charge. Since reactive current does not provide energy, there is no
change in the charge for energy.
So capacitor banks are worthwhile in simple terms by saving the end-user unnecessary additional costs.
2.
Capacitors are vulnerable to high voltages and currents in an electrical power system.
As electronic equipment presence increases most modern loads are non-linear (i.e. they contain some sort of switching
control in their power supplies) and produce harmonic currents. Usually, most odd harmonics are present up to at least
the 15th harmonic. Problems arise when the frequency of the stray inductance in the installation forms a resonant circuit
with the DPF capacitance at or near one of the harmonic frequencies. If this happens, the capacitor will experience high
voltages and currents that will inevitably destroy it unless it is disconnected by a protective circuit breaker leaving the
DPF uncorrected. [LPQI Application Note 3.1.2 http://www.leonardo-energy.org/drupal/apguide.]
3.
If resonance is occurring, the harmonic current at some frequencies will be much higher when the capacitors are
connected than when they are not. By taking measurements of the harmonic spectrum with the capacitors in and out
of circuit, together with a measurement of the capacitor current when connected, the presence of resonance will be
clearly seen.
Taking the measurements is not difficult, however, as it requires working in an area of the installation where the short
circuit current capacity is very high, it can be very dangerous. Staff working in areas such as this must be adequately
trained, take proper precautions and ensure that the work is carried out in accordance with a procedure determined
by a specific risk assessment.
3a.
Power quality analysers easily measure harmonic currents and voltages and typically display the spectrum of the
voltage and current waveforms up to the 50th harmonic. Many different models of harmonic analyser are available,
ranging from small handheld instruments (ideal for quick diagnostic tests) through portable loggers (ideal for
collecting data over a period of a few days or weeks) to permanently installed monitoring systems which are ideal for
implementing preventative maintenance programmes. Some handheld instruments measure only a single phase but
most allow measurement of voltage and current on three phases together with neutral current. Current measurement
is made using current clamps.
Power Quality
http://www.leonardo-energy.org
Where to measure
3b.
PQ analyser
at point 1
Main circuit-breaker
HV-LV Transformer
Three phase
load
Capacitors banks
circuit-breaker
PQ analyser
at point 1
Capacitors
Where the installation has a fixed DPF correction, this is a simple procedure. Using a switched bank is more complicated
as it is necessary to take measurements at every possible capacitance step because in each case the resonant
frequency will be different. Here, one approach would be to carry out the measurements under typical operating
conditions e.g. during working and non-working hours and then use a logging PQ analyser to carry out long-term
measurements at Point 2 over a period of one week or one month.
4.
This measurement at Point 1, with the capacitor bank circuit breaker closed ie the normal operational configuration,
is shown below. The total harmonic distortion (THD) of both voltage and current, seen in the top right, is extremely
high and clearly wrong at ~6% and ~22% respectively. The voltage and current histograms reveal that the 5th and
11th harmonics are responsible. The high level of harmonics and the fact that the 11th harmonic current is higher than
the 5th suggest there is a resonance problem.
In this configuration the DPF correction should be active, so a DPF measurement of above 0.92 lagging would
be expected. A lower value, or a leading value, would indicate that the DPF control system is not working correctly.
ThD Phase to Neutral Voltage (%)
1000
I1
500
U2
0
-500
0,005
0,01
0,015
0,02
I2
6,20
6,00
22,00
21,00
20,00
19,00
5,40
5,20
I3
-1500
23,00
5,80
5,60
U3
-1000
18,00
5,00
17,00
time (s)
Phase 1
Phase 2
Phase 3
200
U2
100
U3
50
0
300
400
500
600
Phase 3
700
600
500
400
300
200
100
0
U1
150
200
Phase 2
100
Phase 1
250
6,40
700
I1
I2
I3
800
50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850
The measurements taken with the capacitor bank circuit breaker open are shown below. They reflect the natural
behaviour of the load. The THD of both voltage and current, seen in the top right, is now much lower and more
reasonable ~2.5% and ~7% respectively. Since the level of distortion is significantly higher when the capacitors are
present, it is likely that resonance is present.
1000
I1
500
U2
0
0
-500
0,005
0,01
0,015
1500
I2
0,02
U3
-1000
I3
2,70
7,15
2,65
7,10
2,60
7,05
2,55
7,00
2,50
6,95
2,45
6,90
6,85
2,40
-1500
Phase 1
time (s)
Phase 2
Phase 1
Phase 3
Phase 2
Phase 3
250
200
600
I1
U1
150
100
50
U2
400
I2
U3
200
I3
0
0
100
200
300
400
500
600
700
800
50
100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850
600
400
I1
200
U2
0
-200
0,005
0,01
0,015
0,02
-400
I2
U3
I3
-600
6,30
6,20
6,10
6,00
5,90
5,80
5,70
5,60
5,50
U1
Phase 1
time (s)
Phase 2
Phase 3
Phase 1
Phase 2
Phase 3
250
200
U1
150
U2
100
U3
200
I1
150
I2
100
I3
50
50
0
0
0
100
200
300
400
500
600
700
800
100
200
300
400
500
600
700
800
The combination of DPF capacitance and circuit inductance, shown in the figure below, results in a resonant frequency
near to the 11th harmonics, causing its amplification up to a similar magnitude to the fundamental, for which the
capacitors and their protection devices were designed.
Power Quality
http://www.leonardo-energy.org
Line impedance
Transformer
Capacitors banks
Load
Line impedance
Transformer
impedance
Capacitors banks
11th
harmonic
current
source
Single phase diagram of the electrical distribution and the equivalent circuit
This publication is subject to copyright and a disclaimer. Please refer to the Leonardo ENERGY website.