Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Test report

Location

Tested by

BAB#2
SUBSTATION::
220KV GIS
VOLTAGE::
B105-6
CB TYPE::
CONTROL VOLTAGE::Unom 110V

Date

Page

14/09/2014

Signature

Approved by

Test ID:
Type of test:
Date/Time:
Operator:

ASPS-01
D03
14/09/2014 13:41
TM1760

t A 01M

t B 01M

t C 01M

t AAUXa1

t BAUXa1

t CAUXa1

t AAUXb1

t BAUXb1

t CAUXb1

M C: 50 mm/div

M B: 50 mm/div

M A: 50 mm/div

Scale = 20.0 ms/divs

-40.0

0.0

40.0

80.0

120.0

160.0

200.0

240.0

280.0

320.0

Operation: CLOSE 1
Parameters

Value

Unit

Pass / Fail

Minimum

Maximum

Close time A 01M

66.875

ms

Pass

64.0

69.0

Close time B 01M

67.425

ms

Pass

64.0

69.0

Close time C 01M

66.750

ms

Pass

64.0

69.0

Diff A-B-C

0.675

ms

Pass

0.0

5.0

Cls time a AAUXa1

70.450

ms

Pass

68.0

82.0

Cls time a BAUXa1

71.425

ms

Pass

68.0

82.0

Nominal

360.0

Test report

Date

Page

14/09/2014

Parameters

Value

Unit

Pass / Fail

Minimum

Maximum

Cls time a CAUXa1

71.000

ms

Pass

68.0

82.0

Opn time b AAUXb1

57.850

ms

Pass

49.0

66.0

Opn time b BAUXb1

57.550

ms

Pass

49.0

66.0

Opn time b CAUXb1

58.100

ms

Pass

49.0

66.0

Cls speed A

5.53

m/s

Pass

5.00

6.00

Cls speed B

5.49

m/s

Pass

5.00

6.00

Cls speed C

5.49

m/s

Pass

5.00

6.00

Nominal