Test report

Location

Tested by

BAB#2
SUBSTATION::
220KV GIS
VOLTAGE::
B105-6
CB TYPE::
CONTROL VOLTAGE::Unom 110V

Date

Page

14/09/2014

Signature

Approved by

Test ID:
Type of test:
Date/Time:
Operator:

ASPS-01
D03
14/09/2014 13:41
TM1760

t A 01M

t B 01M

t C 01M

t AAUXa1

t BAUXa1

t CAUXa1

t AAUXb1

t BAUXb1

t CAUXb1

M C: 50 mm/div

M B: 50 mm/div

M A: 50 mm/div

Scale = 20.0 ms/divs

-40.0

0.0

40.0

80.0

120.0

160.0

200.0

240.0

280.0

320.0

Operation: OPEN 2
Parameters

Value

Unit

Pass / Fail

Minimum

Maximum

Open time A 01M

19.225

ms

Pass

17.5

20.5

Open time B 01M

19.050

ms

Pass

17.5

20.5

Open time C 01M

19.250

ms

Pass

17.5

20.5

Diff A-B-C

0.200

ms

Pass

0.0

3.3

Opn time a AAUXa1

15.225

ms

Pass

7.5

16.8

Opn time a BAUXa1

14.725

ms

Pass

7.5

16.8

Nominal

360.0

Test report

Date

Page

14/09/2014

Parameters

Value

Unit

Pass / Fail

Minimum

Maximum

Opn time a CAUXa1

14.250

ms

Pass

7.5

16.8

Cls time b AAUXb1

24.050

ms

Pass

21.5

35.8

Cls time b BAUXb1

24.600

ms

Pass

21.5

35.8

Cls time b CAUXb1

24.150

ms

Pass

21.5

35.8

Opn speed A

8.32

m/s

Pass

8.20

8.80

Opn speed B

8.55

m/s

Pass

8.20

8.80

Opn speed C

8.23

m/s

Pass

8.20

8.80

Nominal