Area Calculation

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

AREA CALCULATION

Area
m2

No.

Description

1.

North West Area


Area of Glass Window
68.03
Floor Area
33.43
North East Area
Area of Glass Window
36.41
Floor Area
32.01
South East Area (Without Server Room)
Area of Glass Window
60.9
Floor Area
28.81
Central Area
Area of Glass Window
0
Floor Area
266.3
Total Area
525.89

2.

3.

4.

5.

COOLING LOAD CALCULATION


STEP

HEAT SOURCE

"A"
m2

Quantity

"B" Multiplying Factor

"C"
Cooling Load =
"A" x "B"

North West Area


1.

2.

3.
4.

North West Area

68.03

No Awnings
Yes Curtains and Blinds
260

Floor Area
Carpeted

33.43

201

Area of Glass Window

17688

People
Sitting

22

120

2640

Lights and Appliances


Lamps
PC
Dispenser
Refrigerator
Xerox

22
22
1
1
1

36
135
170
100
130

792
2970
170
100
130

5.

Sensible Cooling Load (Watts)

24690

6.
7.

Sensible Cooling Load (Btu/hr)


Cooling Load per square metre (Btu/hr_m2)

84247
830

STEP

HEAT SOURCE

"A"
m2

Quantity

"B" Multiplying Factor

"C"
Cooling Load =
"A" x "B"

North East Area

North East

36.41

No Awnings
Yes Curtains and Blinds
260

2.

Floor Area
Carpeted

32.01

192

3.

People
Sitting

12

120

1440

Lights and Appliances


Lamps
PC
Dispenser
Xerox

8
12
1
1

36
135
170
130

288
1620
170
130

1.

4.

Area of Glass Window

9467

5.

Sensible Cooling Load (Watts)

13307

6.
7.

Sensible Cooling Load (Btu/hr)


Cooling Load per square metre (Btu/hr_m2)

45404
664

STEP

1.

"A"
m2

HEAT SOURCE

Area of Glass Window


North East

2.

Floor Area
Carpeted

3.

People
Sitting

4.

Lights and Appliances


Lamps
PC

Quantity

"B" Multiplying Factor

South East Area (Without Server Room)


No Awnings
Yes Curtains and Blinds
60.9
260
28.81

"C"
Cooling Load =
"A" x "B"

15834

173

11

120

1320

16
11

36
135

576
1485

5.

Sensible Cooling Load (Watts)

19388

6.
7.

Sensible Cooling Load (Btu/hr)


Cooling Load per square metre (Btu/hr_m2)

66154
737

STEP

HEAT SOURCE

"A"
m2

Quantity

"B" Multiplying Factor

"C"
Cooling Load =
"A" x "B"

Central Area
1.

Central
2.

No Awnings
Yes Curtains and Blinds
260

Area of Glass Window

Floor Area
Carpeted

0
266.3

1598

3.

People
Sitting

63

120

7560

4.

Lights and Appliances


Lamps
PC
Xerox

96
63
1

36
135
130

3456
8505
130

5.

Sensible Cooling Load (Watts)

21249

6.
7.

Sensible Cooling Load (Btu/hr)


Cooling Load per square metre (Btu/hr_m2)

72504
272

AVERAGE COOLING LOAD ALL AREA (WITHOUT SERVER ROOM)

510