Test report

Date

Page

21-05-14

Circuit Breaker

Circuit Breaker Data

Breaker ID1
Breaker ID2
Breaker ID3
Breaker ID4
Serial no.
Commission date
Interruping medium
Rated frequency
Rated voltage
Rated curre nt
Rated short-circuit breaking current
Rated motor voltage
Rated supply voltage

Test Data

Test ID
Test date
Type
Reference
Counter
Operator
Plan ID
Plan description

LSTA
BC 1
Bay 04

100.0

Hz
kV
A
kA
V
V

Trip 1
21-May-14
Overhaul test
TM1760
Created in TM1800
Created in TM1800

Y-of fset = -19 divs

t A 01M

t B 01M

t C 01 M

t AAUXa1

t BAUXa1

t CAUXa1

-48 7.0

Scale = 100.0 ms/divs

-38 7.0

-28 7.0

Parameters

-18 7.0

Open time A 01M


Open time B 01M
Open time C 01M
Opn time a AAUXa1
Diff M-a AAUXa1
Cls time b AAUXb1
Diff M-b AAUXb1
Opn time a BAUXa1
Diff M-a BAUXa1
Cls time b BAUXb1
Diff M-b BAUXb1
Opn time a CAUXa1
Diff M-a CAUXa1
Cls time b CAUXb1
Diff M-b CAUXb1
Open time A
Open time B
Open time C
Open time
Temp.
Temp.

-87 .0

Value

16.325
16.500
16.500
8.850
-7.475
20.375
4.050
8.725
-7.775
19.925
3.425
8.575
-7.925
20.050
3.550
16.325
16.500
16.500
16.500
-- -- --- -- --

13.0

113. 0

Unit

ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
C
F

213. 0

313. 0

413. 0

513. 0

613. 0

713. 0

813. 0

913. 0

1013 .0

1113 .0

1213 .0