Calculation FM-200 HFC-227ea

Clean Agent Fire Suppression System

NFPA 2001

FrankAppication

PichairatPunta

FM-200 HFC-227ea
Its chemical formula is CF3-CHF-CF3, or C3HF7. With a boiling point of -16.4 C, it
is a gas at room temperature. It is slightly soluble in water (260 mg/L).
HFC-227ea finds use in fire suppression systems in data processing and
telecommunication facilities, and in protection of many flammable liquids and gases. HFC227ea falls in the category of Clean Agents and is governed by NFPA 2001 - Standard for
Clean Agent Fire Extinguishing Systems. Effective fire suppression requires introducing a
concentration of the HFC-227ea agent between 6.25% and 9% depending on the hazard being
protected. Its NOAEL level for cardiac sensitization is 9%. The United States Environmental
Protection Agency allows concentration of 9% volume in occupied spaces without mandated
egress time, or up to 10.5% for a limited time. Most fire suppression systems are designed to
provide concentration of 6.25-9%.The HFC-227ea fire suppression agent was the first nonozone depleting replacement for Halon 1301 In addition, HFC-227ea leaves no residue on
valuable equipment after discharge. HFC-227ea contains no chlorine or bromine atoms,
presenting no ozone depletion effect. Its atmospheric lifetime is approximated between 31 and
42 years. It leaves no residue or oily deposits and can be removed by ventilation of the
affected space.As an aerosol propellant, HFC-227ea is used in pharmaceutical metered dose
inhalers such as those used for dispensing asthma medication.
At high temperatures, heptafluoropropane will decompose and produce hydrogen
fluoride. This is observable as presence of sharp, pungent odour, which can be perceived in
concentrations far below a dangerous level. Other decomposition products include carbon
monoxide and carbon dioxide. Prior to re-entry of a room where HFC-227ea system has been
activated to suppress a fire, the atmosphere should be tested.Contact with liquid HFC-227ea
may cause frostbite

FrankAppication

PichairatPunta

Develop Application By Frank


You can consult fire suppression systems
consultdesignFM200SystemandInstallationFM200System
CONTACT US

Job

Frank.engineer11@gmail.com

https://www.facebook.com/pichairat.punta?ref=tn_tnmn
https://www.facebook.com/#!/FrankApplication?fref=ts

Thailand
FM-200 About

FrankAppication

PichairatPunta

Frank Application
Calculation FM-200 HFC-227ea
Clean Agent Fire Suppression System

1
2
3
4
5

1.

Volume (m^3) = Istheresult of thecalculation ofthe volume ofspacethatis used to


figure outtheamountofFM-200for example.

W = Width (m.)
L = Long (m.)
H = High (m.)

Volume=W x L x H
Volume = cubic meter
Volume=

FrankAppication

PichairatPunta

For example1. Room Width = 5 m. , Long =10 m. , High = 5 m.

Volume= Width (W) x Long ( L) x High (H)

W= 10 m. , L=10 m. , H= 5m.

1.1

Volume = 10 x 10 x5
Volume=500

1.1

FrankAppication

For example2. Room Area =50

PichairatPunta

, High (H) = 5 m.

Volume= Area x High(H)


1.2

Volume= 100 x 5
Volume=500

1.2

FrankAppication

PichairatPunta

Design Concentrate (%) For FM-200


2

2. Concentrate (%) = The system design is to calculate the weight of the fire
extinguishing song you want to achieve the desired concentration within a protected
area under consideration by the NFPA 2001 standard.
Class A Fire. Fire in ordinary combustible materials, such as wood, cloth,
paper,rubber, and many plastics. For system design Class A in calculate Concentrate

For FM200 By Concentrate (%) = 6.7% or Very > 6.7% henceforth


Class B Fire. Fire in flammable liquids, oils, greases, tars, oil-base paints, lacquers,
and flammable gases.
HFC-227ea (HFC-227ea) Design Concentration Class B Fuels
Fuel of Product
%C
Fuel of Product
Acetone
t-Amyl Alcohol
Aviation Gas
n-Butane
n-Butanol
2-Butoxyethalnol
2-Butoxyethyl Acetate
n-Butyl Acetate
Carbon Disulfide
Cholroethane
Crude Oil
Cyclohexane
Cyclopentanone
Diesel No2.
N,N-Diethylethanolamina
Diethyl Ether
Ethane
Ethanol
Ethyl Acetate
Ethyl Benzene
Ethylene
Ethylene Glycol
Gasoline
n-Heptane
n-Hexane
1-Hexane
Hydraulic Fluid

9.0
9.5
8.5
8.6
9.9
9.6
9.0
9.1
15.3
8.2
8.5
9.4
9.6
8.7
10.1
9.8
8.7
10.8
8.8
8.2
10.9
9.9
9.0
8.7
9.0
7.5
8.5

Hydraulic Oil
Hydrogen
Isobuty Alcohol
Iso-Octane
Isopropanol
i-Propanol
JP-4
JP-5
Kerosene
Methanol
2-Methoxyethanol
Methyl Ehtyl Ketone (MEK)
Methyl Isobuty Ketone(MIK)
Mineral Spirits
Moropholine
Nitromethane
n-Pentane
Propane
1-Propanol
Propylene
Propylene Glycol
Pyrrolidine
Tetrahydrofuran
Tolulene
Tetrahydrothiophene
Transformer oil
Xylene

%C
7.7
17.2
9.9
9.2
9.8
9.5
9.0
9.0
9.6
13.5
12.2
9.6
9.1
8.6
10.3
12.9
8.8
8.7
10.0
8.1
11.2
9.5
8.6
7.3
8.6
9.5
7.8

FrankAppication

PichairatPunta

Class C Fire. Fire that involves energized electrical equipment where the electrical
resistivity of the extinguishing media is of importance. Design Class C about
electrical equipment for example Room

Electrical and Electronic Hazards


DATA Processing Facilities
Telecommunication Facilies
Storage Rooms-Flammable Liquids and gases
High value assets,where the associated down time would be costly

By Class C Fire For system design Class C in calculate Concentrate For FM200

By

Concentrate (%) = 7% or Very >7% henceforth

For example1. DATA Processing Room by Area =50

, High (H) = 5 m.

Concentrate = 7%

Concentrate = 7%

FrankAppication

PichairatPunta

Temperature For FM-200


3

Defining the design temperature is Celsius . By

3.TemperatureforsystemFM200desing.

use temperature Room at design and Environment

3
4
5

Calculate the amount of extinguishing agents use design Room FM-200 . Metric name
of Unit Kilogram(kg) Unit
5
Calculate the amount of extinguishing agents use design Room FM-200 . name of
Unit Pound(Ib) Unit
4

FrankAppication

PichairatPunta

Fill Capacity
Cylinder

Minimum
Ibs
6
12
21
28
48
82
138
211
282
304
455
620

Alpha 10
Alpha 20
Beta 40
Beta 55
Beta 95
Gamma 150
Gamma 250
Gamma 400
Gamma 550
Sigma 600
Sigma 750
Sigma 1000

For example1

Maximum
kg
2.7
5.4
9.5
12.7
21.8
37.2
62.2
95.7
127.9
137.9
206.4
281.2

Ibs
12
23
41
55
96
163
274
421
500
607
910
1000

Quantity Substance = 273.804 Kg

Quantity Substance = 603.623 Ibs

kg
5.4
10.4
18.1
24.9
43.5
73.9
124.3
191
226.8
275.3
412.8
453.6

CHEMETRON Fire Systems Cylinder


Ibs

Sigma 1000

620

kg

281.2

CHEMETRON Fire Systems Cylinder = Sigma 1000

Ibs

1000

kg

453.6

FrankAppication

PichairatPunta

Fill Capacity
Cylinder

Minimum
Ibs
22
41
66
138
211
304
455
619

Sv 40
Sv 80
Sv 130
Mv 250
Mv 420
Lv 600
Lv 900
Lv 1000

For example2

Maximum
kg
10
18.6
29.9
62.6
95.7
137.9
206.4
280.8

Ibs
49
81
131
274
422
607
910
1000

Quantity Substance = 273.804 Kg

Quantity Substance = 603.623 Ibs

kg
19.5
36.7
59.4
124.3
191.4
275.3
412.8
453.6

JANUS Fire Systems Cylinder

Lv 1000

Ibs

kg

619

280.8

JANUS Fire Systems Cylinder = Lv 1000

Ibs

1000

kg

453.6

FrankAppication

PichairatPunta

Fill Capacity
Cylinder

Minimum
Ibs
12
22
37
58
73
128
123
215
372
573

20
35
60
100
125
215i
215
375
650
1000

For example3

Maximum
kg
54
10
16.8
26.3
33.1
58.1
55.8
97.5
168.7
260

Ibs
21
38
64
100
127
223
215
375
650
1002

Quantity Substance = 273.804 Kg

Quantity Substance = 603.623 Ibs

Kidde Fire Systems Cylinder = Cylinder 1000

kg
9.5
17.2
29
45.4
57.6
101.2
97.5
170
296
454

FrankAppication

OPERATING DIAGRAM OF FIRE SUPPRESSION SYSTEM

Typical Clean Agent System Layout

PichairatPunta

FrankAppication

PichairatPunta

FM-200 HFC-227ea

CF3-CHF-CF3 C3HF7 -16.4 C


(260 . / )
HFC-227ea
HFC-227ea
NFPA 2001 -

HFC-227ea 6.25% 9%
NOAEL 9%
9%
10.5%
6.25-9% HFC-227ea depleting
1301. HFC-227ea
31 42

heptafluoropropane

re-entry
HFC-227ea
, HFC-227ea

FrankAppication

PichairatPunta

Develop Application By Frank


You can consult fire suppression systems
CONTACT US
Frank.engineer11@gmail.com

https://www.facebook.com/pichairat.punta?ref=tn_tnmn
https://www.facebook.com/#!/FrankApplication?fref=ts
Thailand
FM-200

FrankAppication

PichairatPunta

Frank Application
Calculation FM-200 HFC-227ea
Clean Agent Fire Suppression System

1
2
3
4
5

1.

Volume (m^3)
FM-200

W = ()
L = ()
H = ()

=W
xLxH
=
=

FrankAppication

PichairatPunta

1. = 5 m. , =10 m. , = 5 m.

= (W) x ( L) x (H)

W= 10 , L=10 , H= 5

1.1

= 10 x 10 x5
=500

1.1

FrankAppication

2. =50

PichairatPunta

, (H) = 5 m.

= x (H)
= 100 x 5
=500
Design Concentrate (%) For FM-200

1.2

2.(%) =
NFPA 2001
Class A Fire. ,,,
FM-200 (%)
= 6.7% > 6.7%
Class B Fire., , , Tars, ,

HFC-227ea (HFC-227ea) Design Concentration Class B Fuels
Fuel of Product
%C
Fuel of Product

Acetone
t-Amyl Alcohol
Aviation Gas
n-Butane
n-Butanol
2-Butoxyethalnol
2-Butoxyethyl Acetate

9.0
9.5
8.5
8.6
9.9
9.6
9.0

Hydraulic Oil
Hydrogen
Isobuty Alcohol
Iso-Octane
Isopropanol
i-Propanol
JP-4

%C
7.7
17.2
9.9
9.2
9.8
9.5
9.0

FrankAppication

n-Butyl Acetate
Carbon Disulfide
Cholroethane
Crude Oil
Cyclohexane
Cyclopentanone
Diesel No2.
N,N-Diethylethanolamina
Diethyl Ether
Ethane
Ethanol
Ethyl Acetate
Ethyl Benzene
Ethylene
Ethylene Glycol
Gasoline
n-Heptane
n-Hexane
1-Hexane
Hydraulic Fluid

9.1
15.3
8.2
8.5
9.4
9.6
8.7
10.1
9.8
8.7
10.8
8.8
8.2
10.9
9.9
9.0
8.7
9.0
7.5
8.5

PichairatPunta

JP-5
Kerosene
Methanol
2-Methoxyethanol
Methyl Ehtyl Ketone (MEK)
Methyl Isobuty Ketone(MIK)
Mineral Spirits
Moropholine
Nitromethane
n-Pentane
Propane
1-Propanol
Propylene
Propylene Glycol
Pyrrolidine
Tetrahydrofuran
Tolulene
Tetrahydrothiophene
Transformer oil
Xylene

9.0
9.6
13.5
12.2
9.6
9.1
8.6
10.3
12.9
8.8
8.7
10.0
8.1
11.2
9.5
8.6
7.3
8.6
9.5
7.8

Class C Fire.

Class C

Electrical and Electronic Hazards


DATA Processing Facilities
Telecommunication Facilies
Storage Rooms-Flammable Liquids and gases
High value assets,where the associated down time would be costly

Class C Class C FM200


(%) = 7% > 7%

1. DATA Processing =50


= 7%

, (H) = 5 m.

FrankAppication

PichairatPunta

Concentrate = 7%

FrankAppication

PichairatPunta

1.2

2.

FM-200

FrankAppication

PichairatPunta

3
4
5

FM-200
(.)
5
FM-200
4

FrankAppication

PichairatPunta

Fill Capacity
Cylinder

Minimum
Ibs
6
12
21
28
48
82
138
211
282
304
455
620

Alpha 10
Alpha 20
Beta 40
Beta 55
Beta 95
Gamma 150
Gamma 250
Gamma 400
Gamma 550
Sigma 600
Sigma 750
Sigma 1000

Maximum
kg
2.7
5.4
9.5
12.7
21.8
37.2
62.2
95.7
127.9
137.9
206.4
281.2

Ibs
12
23
41
55
96
163
274
421
500
607
910
1000

kg
5.4
10.4
18.1
24.9
43.5
73.9
124.3
191
226.8
275.3
412.8
453.6

= 273.804 Kg
= 603.623 Ibs

CHEMETRON Fire Systems Cylinder


Ibs

Sigma 1000

620

kg

281.2

CHEMETRON Fire Systems Cylinder = Sigma 1000

Ibs

1000

kg

453.6

FrankAppication

PichairatPunta

Fill Capacity
Cylinder

Minimum
Ibs
22
41
66
138
211
304
455
619

Sv 40
Sv 80
Sv 130
Mv 250
Mv 420
Lv 600
Lv 900
Lv 1000

Maximum
kg
10
18.6
29.9
62.6
95.7
137.9
206.4
280.8

Ibs
49
81
131
274
422
607
910
1000

kg
19.5
36.7
59.4
124.3
191.4
275.3
412.8
453.6

= 273.804 Kg
= 603.623 Ibs

JANUS Fire Systems Cylinder

Lv 1000

Ibs

kg

619

280.8

JANUS Fire Systems Cylinder = Lv 1000

Ibs

1000

kg

453.6

FrankAppication

PichairatPunta

Fill Capacity
Cylinder

Minimum
Ibs
12
22
37
58
73
128
123
215
372
573

20
35
60
100
125
215i
215
375
650
1000

Maximum
kg
54
10
16.8
26.3
33.1
58.1
55.8
97.5
168.7
260

= 273.804 Kg
= 603.623 Ibs

Kidde Fire Systems Cylinder = Cylinder 1000

Ibs
21
38
64
100
127
223
215
375
650
1002

kg
9.5
17.2
29
45.4
57.6
101.2
97.5
170
296
454

FrankAppication

OPERATING DIAGRAM OF FIRE SUPPRESSION SYSTEM

Typical Clean Agent System Layout

PichairatPunta

You might also like