Calculation FM-200 HFC-227ea
NFPA 2001
FrankAppication
PichairatPunta
FM-200 HFC-227ea
Its chemical formula is CF3-CHF-CF3, or C3HF7. With a boiling point of -16.4 C, it
is a gas at room temperature. It is slightly soluble in water (260 mg/L).
HFC-227ea finds use in fire suppression systems in data processing and
telecommunication facilities, and in protection of many flammable liquids and gases. HFC227ea falls in the category of Clean Agents and is governed by NFPA 2001 - Standard for
Clean Agent Fire Extinguishing Systems. Effective fire suppression requires introducing a
concentration of the HFC-227ea agent between 6.25% and 9% depending on the hazard being
protected. Its NOAEL level for cardiac sensitization is 9%. The United States Environmental
Protection Agency allows concentration of 9% volume in occupied spaces without mandated
egress time, or up to 10.5% for a limited time. Most fire suppression systems are designed to
provide concentration of 6.25-9%.The HFC-227ea fire suppression agent was the first nonozone depleting replacement for Halon 1301 In addition, HFC-227ea leaves no residue on
valuable equipment after discharge. HFC-227ea contains no chlorine or bromine atoms,
presenting no ozone depletion effect. Its atmospheric lifetime is approximated between 31 and
42 years. It leaves no residue or oily deposits and can be removed by ventilation of the
affected space.As an aerosol propellant, HFC-227ea is used in pharmaceutical metered dose
inhalers such as those used for dispensing asthma medication.
At high temperatures, heptafluoropropane will decompose and produce hydrogen
fluoride. This is observable as presence of sharp, pungent odour, which can be perceived in
concentrations far below a dangerous level. Other decomposition products include carbon
monoxide and carbon dioxide. Prior to re-entry of a room where HFC-227ea system has been
activated to suppress a fire, the atmosphere should be tested.Contact with liquid HFC-227ea
may cause frostbite
FrankAppication
PichairatPunta
Job
Frank.engineer11@gmail.com
https://www.facebook.com/pichairat.punta?ref=tn_tnmn
https://www.facebook.com/#!/FrankApplication?fref=ts
Thailand
FM-200 About
FrankAppication
PichairatPunta
Frank Application
Calculation FM-200 HFC-227ea
Clean Agent Fire Suppression System
1
2
3
4
5
1.
W = Width (m.)
L = Long (m.)
H = High (m.)
Volume=W x L x H
Volume = cubic meter
Volume=
FrankAppication
PichairatPunta
W= 10 m. , L=10 m. , H= 5m.
1.1
Volume = 10 x 10 x5
Volume=500
1.1
FrankAppication
PichairatPunta
, High (H) = 5 m.
Volume= 100 x 5
Volume=500
1.2
FrankAppication
PichairatPunta
2. Concentrate (%) = The system design is to calculate the weight of the fire
extinguishing song you want to achieve the desired concentration within a protected
area under consideration by the NFPA 2001 standard.
Class A Fire. Fire in ordinary combustible materials, such as wood, cloth,
paper,rubber, and many plastics. For system design Class A in calculate Concentrate
9.0
9.5
8.5
8.6
9.9
9.6
9.0
9.1
15.3
8.2
8.5
9.4
9.6
8.7
10.1
9.8
8.7
10.8
8.8
8.2
10.9
9.9
9.0
8.7
9.0
7.5
8.5
Hydraulic Oil
Hydrogen
Isobuty Alcohol
Iso-Octane
Isopropanol
i-Propanol
JP-4
JP-5
Kerosene
Methanol
2-Methoxyethanol
Methyl Ehtyl Ketone (MEK)
Methyl Isobuty Ketone(MIK)
Mineral Spirits
Moropholine
Nitromethane
n-Pentane
Propane
1-Propanol
Propylene
Propylene Glycol
Pyrrolidine
Tetrahydrofuran
Tolulene
Tetrahydrothiophene
Transformer oil
Xylene
%C
7.7
17.2
9.9
9.2
9.8
9.5
9.0
9.0
9.6
13.5
12.2
9.6
9.1
8.6
10.3
12.9
8.8
8.7
10.0
8.1
11.2
9.5
8.6
7.3
8.6
9.5
7.8
FrankAppication
PichairatPunta
Class C Fire. Fire that involves energized electrical equipment where the electrical
resistivity of the extinguishing media is of importance. Design Class C about
electrical equipment for example Room
By Class C Fire For system design Class C in calculate Concentrate For FM200
By
, High (H) = 5 m.
Concentrate = 7%
Concentrate = 7%
FrankAppication
PichairatPunta
3.TemperatureforsystemFM200desing.
3
4
5
Calculate the amount of extinguishing agents use design Room FM-200 . Metric name
of Unit Kilogram(kg) Unit
5
Calculate the amount of extinguishing agents use design Room FM-200 . name of
Unit Pound(Ib) Unit
4
FrankAppication
PichairatPunta
Fill Capacity
Cylinder
Minimum
Ibs
6
12
21
28
48
82
138
211
282
304
455
620
Alpha 10
Alpha 20
Beta 40
Beta 55
Beta 95
Gamma 150
Gamma 250
Gamma 400
Gamma 550
Sigma 600
Sigma 750
Sigma 1000
For example1
Maximum
kg
2.7
5.4
9.5
12.7
21.8
37.2
62.2
95.7
127.9
137.9
206.4
281.2
Ibs
12
23
41
55
96
163
274
421
500
607
910
1000
kg
5.4
10.4
18.1
24.9
43.5
73.9
124.3
191
226.8
275.3
412.8
453.6
Sigma 1000
620
kg
281.2
Ibs
1000
kg
453.6
FrankAppication
PichairatPunta
Fill Capacity
Cylinder
Minimum
Ibs
22
41
66
138
211
304
455
619
Sv 40
Sv 80
Sv 130
Mv 250
Mv 420
Lv 600
Lv 900
Lv 1000
For example2
Maximum
kg
10
18.6
29.9
62.6
95.7
137.9
206.4
280.8
Ibs
49
81
131
274
422
607
910
1000
kg
19.5
36.7
59.4
124.3
191.4
275.3
412.8
453.6
Lv 1000
Ibs
kg
619
280.8
Ibs
1000
kg
453.6
FrankAppication
PichairatPunta
Fill Capacity
Cylinder
Minimum
Ibs
12
22
37
58
73
128
123
215
372
573
20
35
60
100
125
215i
215
375
650
1000
For example3
Maximum
kg
54
10
16.8
26.3
33.1
58.1
55.8
97.5
168.7
260
Ibs
21
38
64
100
127
223
215
375
650
1002
kg
9.5
17.2
29
45.4
57.6
101.2
97.5
170
296
454
FrankAppication
PichairatPunta
FrankAppication
PichairatPunta
FM-200 HFC-227ea
heptafluoropropane
re-entry
HFC-227ea
, HFC-227ea
FrankAppication
PichairatPunta
https://www.facebook.com/pichairat.punta?ref=tn_tnmn
https://www.facebook.com/#!/FrankApplication?fref=ts
Thailand
FM-200
FrankAppication
PichairatPunta
Frank Application
Calculation FM-200 HFC-227ea
Clean Agent Fire Suppression System
1
2
3
4
5
1.
Volume (m^3)
FM-200
W = ()
L = ()
H = ()
=W
xLxH
=
=
FrankAppication
PichairatPunta
1. = 5 m. , =10 m. , = 5 m.
= (W) x ( L) x (H)
W= 10 , L=10 , H= 5
1.1
= 10 x 10 x5
=500
1.1
FrankAppication
2. =50
PichairatPunta
, (H) = 5 m.
= x (H)
= 100 x 5
=500
Design Concentrate (%) For FM-200
1.2
2.(%) =
NFPA 2001
Class A Fire. ,,,
FM-200 (%)
= 6.7% > 6.7%
Class B Fire., , , Tars, ,
HFC-227ea (HFC-227ea) Design Concentration Class B Fuels
Fuel of Product
%C
Fuel of Product
Acetone
t-Amyl Alcohol
Aviation Gas
n-Butane
n-Butanol
2-Butoxyethalnol
2-Butoxyethyl Acetate
9.0
9.5
8.5
8.6
9.9
9.6
9.0
Hydraulic Oil
Hydrogen
Isobuty Alcohol
Iso-Octane
Isopropanol
i-Propanol
JP-4
%C
7.7
17.2
9.9
9.2
9.8
9.5
9.0
FrankAppication
n-Butyl Acetate
Carbon Disulfide
Cholroethane
Crude Oil
Cyclohexane
Cyclopentanone
Diesel No2.
N,N-Diethylethanolamina
Diethyl Ether
Ethane
Ethanol
Ethyl Acetate
Ethyl Benzene
Ethylene
Ethylene Glycol
Gasoline
n-Heptane
n-Hexane
1-Hexane
Hydraulic Fluid
9.1
15.3
8.2
8.5
9.4
9.6
8.7
10.1
9.8
8.7
10.8
8.8
8.2
10.9
9.9
9.0
8.7
9.0
7.5
8.5
PichairatPunta
JP-5
Kerosene
Methanol
2-Methoxyethanol
Methyl Ehtyl Ketone (MEK)
Methyl Isobuty Ketone(MIK)
Mineral Spirits
Moropholine
Nitromethane
n-Pentane
Propane
1-Propanol
Propylene
Propylene Glycol
Pyrrolidine
Tetrahydrofuran
Tolulene
Tetrahydrothiophene
Transformer oil
Xylene
9.0
9.6
13.5
12.2
9.6
9.1
8.6
10.3
12.9
8.8
8.7
10.0
8.1
11.2
9.5
8.6
7.3
8.6
9.5
7.8
Class C Fire.
Class C
, (H) = 5 m.
FrankAppication
PichairatPunta
Concentrate = 7%
FrankAppication
PichairatPunta
1.2
2.
FM-200
FrankAppication
PichairatPunta
3
4
5
FM-200
(.)
5
FM-200
4
FrankAppication
PichairatPunta
Fill Capacity
Cylinder
Minimum
Ibs
6
12
21
28
48
82
138
211
282
304
455
620
Alpha 10
Alpha 20
Beta 40
Beta 55
Beta 95
Gamma 150
Gamma 250
Gamma 400
Gamma 550
Sigma 600
Sigma 750
Sigma 1000
Maximum
kg
2.7
5.4
9.5
12.7
21.8
37.2
62.2
95.7
127.9
137.9
206.4
281.2
Ibs
12
23
41
55
96
163
274
421
500
607
910
1000
kg
5.4
10.4
18.1
24.9
43.5
73.9
124.3
191
226.8
275.3
412.8
453.6
= 273.804 Kg
= 603.623 Ibs
Sigma 1000
620
kg
281.2
Ibs
1000
kg
453.6
FrankAppication
PichairatPunta
Fill Capacity
Cylinder
Minimum
Ibs
22
41
66
138
211
304
455
619
Sv 40
Sv 80
Sv 130
Mv 250
Mv 420
Lv 600
Lv 900
Lv 1000
Maximum
kg
10
18.6
29.9
62.6
95.7
137.9
206.4
280.8
Ibs
49
81
131
274
422
607
910
1000
kg
19.5
36.7
59.4
124.3
191.4
275.3
412.8
453.6
= 273.804 Kg
= 603.623 Ibs
Lv 1000
Ibs
kg
619
280.8
Ibs
1000
kg
453.6
FrankAppication
PichairatPunta
Fill Capacity
Cylinder
Minimum
Ibs
12
22
37
58
73
128
123
215
372
573
20
35
60
100
125
215i
215
375
650
1000
Maximum
kg
54
10
16.8
26.3
33.1
58.1
55.8
97.5
168.7
260
= 273.804 Kg
= 603.623 Ibs
Ibs
21
38
64
100
127
223
215
375
650
1002
kg
9.5
17.2
29
45.4
57.6
101.2
97.5
170
296
454
FrankAppication
PichairatPunta