Proofex Torchseal
Specification
The waterproofing membrane shall be a high performance
torch applied 3mm / 4mm thick membrane, manufactured
from high quality polymer - modified bituminous compounds
and reinforced with non woven polyster fabric, weighing
180g/m.
Properties
Membrane thickness (+/- 5%) :
(ASTM D 751)
:
Nominal weight
:
Reinforcement base
:
Softening point
(ASTM D36)
:
Penetration
(ASTM D5)
:
Flexibility at low temperature
(Din 52123)
:
Tensile strength
Longitudinal (UEAtc)
:
Transverse (UEAtc)
:
Elongation of membrane
Longitudinal (UEAtc)
:
Transverse (UEAtc)
:
Tear resistance
Longitudinal (ASTM D4073) :
Transverse (ASTM D4073)
:
Lap joint strength
Longitudinal (UEAtc)
:
Transverse (CGSB37-GP56m) :
Load Strain
Longitudinal (CGSB-37-GP56M):
Transverse
:
Puncture Resistance
Static (UEAtc)
:
Dynamic
:
Water absorption
(ASTM D5147)
:
Water vapour transmission
(ASTM E96)
:
Resistance to ageing due to :
UV radiation(ASTM G53)
Proofex 3P - 3mm
Proofex 4P - 4mm
3mm - 3.5kg/m
4mm - 4.5kg/m
180g/m
150C
17 - 25 dmm
-5C
750 N/5cm
550 N/5cm
40%
50%
180 N
190 N
750 N/5cm
550 N/5cm
41,000
36,000
L4
I3
<0.15%
<0.50g/m/24h
No signs of deterioration
after the test
Proofex Torchseal
3P* & 4P*
Instructions for use
Storage
Surface preparation
Precautions
Application
The membrane is unrolled and placed in the correct position where
it is to be torched on later. During each stage, each roll must overlap
the next layer by atleast 10cm. The membrane is rolled back without
changing the orientation. The rolled membrane is slowly unrolled
again, while its surface is lightly heated, transversally, by means of
a propane gas torch, thus causing surface melting and subsequent
adhesion to the surface. End joints should be made with a minimum
of 15cm overlap.
Coverage
Proofex Torchseal Primer :
Important note
Fosroc products are guaranteed against defective materials and manufacture and are sold subject to its standard
Conditions for the Supply of Goods and Service. All Fosroc datasheets are updated on a regular basis. It is the users
responsibility to obtain the recent version. Refer to www.fosroc.com.
Al Gurg Fosroc
LLC
Post Box 657, Dubai
United Arab Emirates
www.fosroc.com
Head Office
telephone: (+9714) 2039699
email: agf@fosroc.com
Regional offices
Abu Dhabi, Al Gurg Fosroc
Bahrain, YBA Kanoo
email: abudhabi@fosroc.com
email: bahrain@fosroc.com
Kuwait, Boodai
Oman, Al Amana
Qatar, Tadmur
telephone: 4817618
telephone: 24815080
telephone: 4500607
fax: 4832124
fax: 24817554
fax: 4500543
email: kuwait@fosroc.com
email: oman@fosroc.com
email: qatar@fosroc.com
UAE/0511/04/C