INDUCEDOVERVOLTAGEWITHSTANDTEST

PURPOSEOFTHETEST
Theobjectofthetestistosecurethattheinsulationbetweenthephasewindings,turn,coils,
tappingleadsandterminals,withstandthetemporaryovervoltagestowhichthetransformermay
besubjectedduringitslifetime.

PERFORMANCE
Theexcitationvoltageisappliedtotheterminalsofthelowvoltagewinding.Theotherwindings
areleftopencircuited.
Thedurationofthetestis:

ratedfrequency.120seconds
testfrequency
Thetestissuccessfulifnocollapseofthetestvoltageoccurs.
Thetestvoltageconnectionisessentiallythesameasinservice.Athreephasewindingistested
withsymmetricalthreephasevoltageinducedinthephasewindings.Ifthewindinghasaneutral
terminal,maybeitisearthedduringthetest.

Thetestvoltageistwicetheratedvoltage.However,thevoltagedevelopedbetweenline
terminalsofanywindingshallnotexceedtheratedshortdurationpowerfrequencywithstand
voltage.

Thevoltageismeasuredbetweenterminalsofthelowvoltagewindingusingavoltmeterat
r.s.m.value.Thevoltageissoadjusted,thattheaveragetothevoltagevaluemeasuredbetween
terminalsisequaltotherequiredtestvoltagevalue.

Fig.5.1

Testcircuitforinducedovervoltagewithstandtestonthreephase
transformer.
G 1supplygenerator, T1transformerundertest, T2currenttransformer,

P 1ammeter, P 2voltmeter(r.s.m.value).

TESTREPORT
Thetestvoltage,frequencyandtestdurationarestatedinthereport.