Technical Specification of Primary Current Injection Kit.

Model: PCIK-4000
Sr. No.

Equipment Parameter

Offered Specification

Primary Current injection Kit

4000 A, 20 KVA

Construction

Unit in 2 Parts1) Control Unit


2) Loading Unit

Current Range

0 2000 4000 Amps (20KVA)

Output voltage

2000A 10 Volt &


4000A 5Volt

Input Supply Voltage

Three Phase 415 Volts10% AC, 50 Hz

Output Current Resolution

2.5 Amps

Display

LED Type

Burden Capacity

20 KVA

Timer Range

0.0001 sec to 9999 sec

10

Display Accuracy

1.5 % of rdg. 2 digit

11

Duty Cycle

7 Min ON & 15 Min OFF at full range current.

12

Operation

Motorized Operation

13

Additional Features

1) CT Polarity Tester
2) Voltmeter for voltage drop measurement
3) Timer for current injection time

14

Timer

With trip circuit


(NC C NO)

Protection

The equipment is well protected by circuit breakers, fuses to prevent


overheating and damage. We use MCB & HRC Fuse.

Transportation

The test set is wheel mounted (heavy duty iron wheel) for easy
transportation.

Accessories

1) Set of 4000A current cable with lugs (both side). With extra price per
meter quoted separately. Cable size shall be (240 sq. mm X 4)=960
sq. mm cotton braded multi strand copper cable.
2) Power supply cord of 4 mtr length.
3) One set of spare fuse.
4) Operational Manual.
5) Test & calibration report.