GEOE11055- Owners Engineering Services for 9 MWp Grid-Interactive Solar PV Power Project in Gujarat.

Comments on " Supply Items, Work Items & Fencing Layout"


SL
NO

DRAWING / DOCUMENT
NUMBER

REV
NO

DESCRIPTION

ICML/SOLAR/GUJ/CIVIL/DWG/002

Fencing Layout

LAHMEYER COMMENTS
DATED: 12/05/2011

i) The weight and type of barbed wire shall be specified.


Ii) The grade of the concrete shall be specified.
iii) At angle points /sharp corners, the stay concrete posts are to be provided. One stay post for every 20m in
straight runs has to be provided.
v) The bottom row of barbed wire may be replaced with 300mm or 250mm high pre-cast PCC or brick masonry
kerb wall. This will also prevent entry of rain water from surrounding Area.
vi) The pre-cast pole concrete grade and reinforcement arrangement should also be specified.
vii) There should be a parity observed in size of dimensioning , texts, sections etc used in the drawing.

Approval
Status

A2

REPLY DATED
: _____

LAHMEYER COMMENTS
DATED: 23/05/2011

Approval
Status

i) Noted
Ii) Noted
iii) At angle points /sharp corners, the stay concrete posts are to be provided. One stay post for every 20m in
straight runs has to be provided.
v) The bottom row of barbed wire may be replaced with 300mm or 250mm high pre-cast PCC or brick masonry
kerb wall. This will also prevent entry of rain water from surrounding Area.
vi) Noted but please show the section of pole.
vii) There should be a parity observed in size of dimensioning , texts, sections etc used in the drawing.

Approval Status (This approval status shall not relieve the Contractor from his contractual obligations):
A1: Approved
A2: Approved subject to incorporation of Comments/modifications as noted. Resubmit revised drgs./docs after Incorporating the comments
A3: Not approved. Resubmit revised drgs/ Docs. Incorporating comments/Modifications, as noted, for approval.
I: Information

Page 1 of 1

A2

REPLY
DATED :
_____

LAHMEYER COMMENTS
DATED: 26/05/2011

1) The detail showing the typical arrangement of Stay


concrete post at corners and at every 20m in straight run is to
be added and accordingly modify the number of footings, if
necessary.
2) Please revise the comment resolution sheet as brick
masonry kerb wall is adopted by replacing the bottom row of
barbed wire .
3)Please modify the section A of Drg No : KML/SOLAR/
GUJ/CIVIL/DWG/002 REV02 sheet 2/2 in line with the view
FENCING DETAILS( i.e no of rows barbed wire, kerb wall, ).

Approval
Status

A2

REPLY
DATED :
_____

LAHMEYER COMMENTS
DATED: 27/05/2011

1) approved with minor comment as to write one note under


"stay post detail" . Note:-" At every 20m in straight run and at
corner post"
2) Noted and no further comment
3) Noted that seven barbed wire is reduced to six as per
comment and no further comment.

Approval
Status

REPLY DATED :
_____

LAHMEYER COMMENTS
DATED: 06/06/2011

Approval
Status

i) Revised Document was


found generally in order.

A1

A1