Professional Documents
Culture Documents
Electrical Protection PDF
Electrical Protection PDF
Electrical Protection PDF
Electrical Faults
Phase to phase
Phase to ground
Phase to phase to phase
Phase to phase to phase to ground
Minimize damage
Leave unaffected equipment in-service
Maintain equipment operating limits
Maintain electrical system stability
Requirements of a Protection
System
Speed
Reliability
Security
Sensitivity
Some terms
Over-current
Overload
Inverse time
Protection Zones
Simple Zone
Double Protection
Bus Zone
Circuit
Breaker
Y
Circuit
Breaker
X
CT CT CT CT
1 2 3 4
Bus
CT CT CT CT
2 1
4 3
Bus Zone H2
Bus Zone H3
Bus Zone H1
Bus
H2
Bus H1
Zone
T1
Bus
H3
Transformer
T1
Zone
SST1
SST1
LV Bus
Bus L1
Bus Zone L1
Transformer
SST1
G1
Zone
G1
Protection
Zones
Breaker Failure
Minimizes the amount of equipment
removed from service in event of a failure
Failure Determination
Not started opening in a certain time
Not open in a certain time
Current not broken in a certain time
CT
1
Electrical bus
Electrical
System
PT
System
Input
A Protection
Initiate
Trip
Action Q
Protection
Logic
B Protection
Close
Breaker X
Initiate
Breaker Y
Trip
Close
Device Z
Protection
Output
Electrical
Devices
Bus Protection
Bus Protection
Over-current
Differential
Back-up
Under voltage
Over-current Relay
CT 2000/5 A
I 1P
I 1S
Differential Protection
I = 1P
I = 2P
I
CT1 2000/5 A
Bus
H1
CT2 2000/5 A
I 1P
I 2P
I = 1S
I = 2S
I
I 1S
I 2S
I 1S
I = 1S
I = 2S
I
I 2S
Fault Conditions
Fault
CT1 2000/5 A
Bus
H1
CT2 2000/5 A
I1P
I2P
I1S
I2S
I1S
I2S
CT 2000/5 A
Bus
H1
I 1P
CT 2000/5 A
I 2P
I 3P
I 1S
I 3S
CT 2000/5 A
T1
I3S
I 1S
I 2S
I 2S
X
T1
S
Backup
Zone L1
Load
L1
Bus
Y
Zone L2
Load
L2
Back-up relay
Over Current
Backup Relay
Differential
Relay
X
T1
S
Load
L1
Bus
Y
Load
L2
To Potential
Transformer
Bus Protection
Over-current
Differential
Back-up
Under voltage
Transformer Protection
Transformer Protection
Instantaneous
Differential
Gas
Thermal Overload
Ground
Transformer Characteristics
High magnetizing inrush currents
Ratio mismatch with CTs aggravated by
tap-changers
Phase shifts
Transformers are affected by over-fluxing
Affected by over-temperature
Transformer Zone
T1 Zone
T1
CT
1
CT
2
CT
3
CT
4
CT
4
CT
3
CT
2
CT
1
Differential
T1
CT1
CT2
I 1P
I 2P
I 1S
Restraint
Coil
I 1S
Operate
Coil
I = 1S
I = 2S
I
I 2S
Restraint
Coil
I 2S
Gas Relay
Winding Temperature
CT2
CT1
IN
CT3
Differential
Relay
Transformer
Star Point
Ground
CT
Ground
Backup
IN
IF
Transformer Protection
Instantaneous
Differential
Gas
Thermal Overload
Ground
Motor Protection
Service Factor
Continuous allowable overload
Many motors some with a power rating and a
service factor
A 10 HP motor with a service factor of 1.15
has a maximum continuous output of 11.5 HP
Instantaneous Over-current
Stall
Thermal Overload
Phase Unbalance
Ground
Inverse
Time
Relay
Overload
Stalls
Heater
(electrical
connectio ns no t
s ho wn)
Overload
Setting
Po inter
Actuating Bimetal
Instantaneous Over-current
Stall
Thermal Overload
Phase Unbalance
Ground
Generator Protection
Classes of TG trips
Class A
Trip generator breaker, field breaker and
turbine
Electrical trips before the output breakers
Class B
Trip generator output but leave it supplying
station service
Electrical faults in the switchyard
Classes of TG trips
Class C
Over excitation high V/Hz
Only used when generator is isolated from grid
Class D
Trip turbine
Trip Generator after motoring is detected
Mechanical type turbine trips high condenser pressure
Generator Protection
Over-current
Overload
Differential
Split phase differential
Ground
Rotor ground
Phase Unbalance
Low field
Under frequency
Out of Step
Reverse power
Ge ne rator Terminals
R
B
Diffe re ntial
Relay
Prote ction
Zo ne s
b) Faulted Phas e
Differential
Generator
Star Point
IP = I1P = I2P
I 1P
G1
CT1
To Main
Transformer
CT2
I 2P
I 1S
Restraint
Coil
I 1S
Operate
Coil
Is = I1S = I2S
Restraint
Coil
I 2S
I 2S
GT1
Stator Ground
Relay
IF
Other Protections
Phase Unbalance
Loss of field
Under frequency
Out of Step
Reverse Power
G
Re ve rse
Powe r
Re aly
V.T.
Generator Protection
Over-current
Overload
Differential
Split phase differential
Ground
Rotor ground
Phase Unbalance
Low field
Under frequency
Out of Step
Reverse power
For You To Do