Fire Fighting Equipment Requirement For A Liquid Terminal Kandla As Per OISD 117:2012

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

Fire Fighting Equipment Requirement for a Liquid terminal Kandla as per OISD 117:2012

S. no.
1.
2.

Particulars
Fire water storage in KL
Fixed foam pourer system

i)

4.

Foam compound (AFFF)in


ltrs
Foam compound(AGFFF)
Portable foam compound
trolley
Fixed water spray
system(MVCS)
Fire water pumps

5.
6.
7.
i)

Jockey pump
Hydrants
Monitors
Portable fire Extinguisher
50 Kg DCP

ii)
iii)

10Kg DCP
05Kg DCP

122

iv)

4.5Kg CO2

ii)
iii)
3.

Qty Required

Available
1800*2=3600

Shortage

2 no(18 to 20 dia
tank),
4 no(25 to 30 dia
tank)
600

2 no.

200/210 liters

nil

Required for all


tanks & TLFs

Available

nil

Main pump(313 BHP,615


KL/H)
1no.
12 no.
24 no.
03

Additional
extinguisher
s available

122
10

Additional
extinguisher
s available
01

05

Other Accessories:
Accessories
Hose boxes
Fire hoses
Jet nozzle
Fog nozzle
Universal nozzle
Foam branch pipe
Water curtain nozzle
Sand buckets
Stretcher with blanket
First aid box
Explosimeter
Fire proximity suit
SCBA suit(30 mint
capacity)
Water jel blanket

Qty Required
Between two hydrant
point
2 no per hose box
1 no in each hose box
At least two no.
At least two no.
At least two no.
At least two no.
4 no
02
01
01
01
01

Available
28

Shortage
nil

56
06
02
00
01
00
04
01
02
01
02
02

nil
22
nil
02
01
02
nil
01
nil
nil
nil
nil

01

00

01

Siren-electrical
Siren-hand operated
Red& green flags
PA system

01 for 3 km range
1 no.
2 no. in each colour
01

01
01
00
00

nil
nil
02
01

You might also like