Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Calculations on MAG5100W DN 65 / 2" sensor

Transmitter choice: MAG5000


Low flow range
Flowrate: Flow velocity: Max. error *):
[m3/h]
[m/s]
[% of Flowrate]
1.19

0.10

1.40

1.99

0.17

1.00

11.95

1.00

0.50

Selected flow range


Flowrate: Flow velocity: Max. error *):
[m3/h]
[m/s]
[% of Flowrate]
18.00

1.51

0.47

19.17

1.60

0.46

20.33

1.70

0.46

21.50

1.80

0.46

22.67

1.90

0.45

23.83

2.00

0.45

25.00

2.09

0.45

Maximum flow rate


Flowrate: Flow velocity: Max. error *):
[m3/h]
[m/s]
[% of Flowrate]
100.10

8.38

0.41

The following data are used for the calculation:


Transmitter choice:

MAG5000

Sensor choice:

MAG5100W

Liquid Name:

Conductive Liquid

Minimum flow rate:

18 m3/h

Maximum flow rate:

25 m3/h

Select flowrate function:

Focus on the whole flow range (Linear)

Details

Accuracy: 0.4% 1.0 mm/s


Customer:

Project:

Tag ID:

DN65 MAG5100_MAG5000

ASME B 16.5 150lb

POS.:2.136...2.139

v. 3.1.105

You might also like