Annexure: Particulars required for 132kV overhead Crossing

S. No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

Attributes
Code of Conductor
Size of conductor
Size of Earth Wire
Overall Dia
Area
Unit wt of Conductor
Ultimate tensile strenghth
Coeff of Linear Expansion
Young's modulus
Normal Span
Max. Temp.
Min. Temp.
Max Sag at 75 deg c at normal span
Crossing Span
Min. sag at -2.5degC at normal span
FOS
FOS at 32.2 degC
Wind Presssure
Wind Load per metre (Wh)
Type of Tower Crossing

Unit
ACSR panther
30/3 mm Al./ steel 7/3.00mm dia
7/ 3.15 mm dia
mm
21
mm2
261.5
kg/m
0.974
kg
9144
per deg C
0.0000193
kg/mm2
7870
m
335
degC
75
degC
-2.5
m
7.592
m
256
m
4.75
2
4
kg/m2
45
kg/m
0.630
440 kV D/C, B+3 type tower Loc. No. -31