COMPAA MINERA ANTAMINA S.A.

ESTUDIO DE COORDINACIN DE PROTECCIONES

- MLB 001, 002 Y 003


ACTUALES

DLF SAC

Pgina 257 de 551

Revisin: 0

Per Unit X 10
.005
1K

.01

.03

.05

.1

.3

.5

10

30

50

Normalized (shifted) TCC


3-Phase (Sym) fault: 25.666kA @ 22.556kV
Faulted Bus:
Bus23
Configuration:
2+3 / A+B

500

100
1K

500

740-CBH-004
Relay293

300

CT480
500/5

300

OCR
-2.5% TapP

740-XFR-002
220/23 kV

75 MVA
Relay295

CT482
200/5

Relay292

CT479
4000/5

OCR

100

100

740-BSM-006
740-SGM-001B

740-CBM-006

50

50
SECC 30
o

CT207
800/5

30

Relay119

30

OCR

Bus23

Cable1243
9-1/C 250

CT208
50/5

Relay302
o

10

CT490
200/5
310-XFC-031
6.29 MVA
DY

23/0.963 kV

310-XFC-032
6.29 MVA
DY

10

310-XFC-033
6.29 MVA

23/0.963 kV

23/0.963 kV
DY

Relay293 - P
OC1

.5

.3

Cable1408

Cable1407

SW323
VFD13

12-1/C 500

0.725 s

Cable1410

GE Multilin
F60
CT Ratio 500:5
IAC - Very Inverse
Pickup = 0.86 (0.01 - 30 xCT Sec)
Time Dial = 1.5
3x = 0.806 s, 5x = 0.399 s, 8x = 0.279 s
1.413 kA @ 220 kV
t1: 0.688 s

12-1/C 500

Bus26

12-1/C 500

12-1/C 500

Cable1406

.5

310-MLB-002A
11190 kW

.3

Relay119 - P
OC1
.1

GE Multilin
750/760
CT Ratio 800:5
ANSI - Extremely Inverse
Pickup = 0.56 (0.05 - 20 xCT Sec)
Time Dial = 5
3x = 3.3 s, 5x = 1.24 s, 8x = 0.628 s
Inst = 7.5 (0.05 - 20 xCT Sec)
25.666 kA @ 22.556 kV
t1: 0 s

.05

.03

.01
.005

.01

.03

.05

GE Multilin
F60
CT Ratio 4000:5
IAC - Very Inverse
Pickup = 0.93 (0.01 - 30 xCT Sec)
Time Dial = 0.9
3x = 0.484 s, 5x = 0.24 s, 8x = 0.168 s
13.783 kA @ 22.556 kV
t1: 0.343 s
.1

.3

.5

10

Per Unit X 10

Project: ECP PLANTA CONCENTRADORA

Fault: Phase(Normalized)
Circuit: TR2 + TR3 / A + B
Cortocircuito Trifasico

30

50

.05

.03

.01
100

ETAP Star 11.0.0

MLB - 001, 002, 003

Configuracin Actual

.1

Relay292 - P
OC1

Seconds

Seconds

Per Unit
.005
1K

.01

.03

.05

.1

.3

.5

10

30

50

Normalized (shifted) TCC


Line-to-Ground (Sym) fault: 0.126kA @ 22.556kV
Faulted Bus:
Bus23
Configuration:
2+3 / A+B

500
740-CBH-004

100
1K

500

CT480
500/5

300

300

-2.5% TapP

740-XFR-002
220/23 kV

75 MVA
Relay295
o

CT482
200/5

Relay292
o

CT479
4000/5

OCR

740-BSM-006

100

740-SGM-001B

100

740-CBM-006

SECC 30

50

50
o

CT207
800/5

Relay119
OCR

30

30

Cable1243
9-1/C 250

CT208
50/5

Bus23

Relay295 - G
GE Multilin
T60
CT Ratio 200:5
Definite Time
Pickup = 0.25 (0.01 - 30 xCT Sec)
Time Dial = 1.5
3x = 1.5 s, 5x = 1.5 s, 8x = 1.5 s
0.126 kA @ 22.556 kV
t1: 1.5 s

Relay302
o

CT490
200/5

10
310-XFC-031
6.29 MVA
DY

23/0.963 kV

310-XFC-032
6.29 MVA
DY

310-XFC-033
6.29 MVA

23/0.963 kV

23/0.963 kV

Cable1408

12-1/C 500

Cable1407

12-1/C 500

12-1/C 500

Bus26

10

SW323

12-1/C 500

Cable1410

VFD13

1.2 s
310-MLB-002A
11190 kW

.5

.5

.3

.3

Relay119 - G
OC1
GE Multilin
750/760
CT Ratio 50:5
Definite Time
Pickup = 0.9 (0.05 - 20 xCT Sec)
Time Dial = 3
3x = 0.3 s, 5x = 0.3 s, 8x = 0.3 s
0.126 kA @ 22.556 kV
t1: 0.3 s

.1

.05

.03

.01
.005

.01

.03

.05

.1

.1

.05

.03

.3

.5

10

30

Per Unit

Configuracin Actual

Fault: Ground(Normalized)
Circuit: TR2 + TR3 / A + B
Cortocircuito Monofsico, R=50ohm

.01
100

ETAP Star 11.0.0

MLB - 001, 002, 003


Project: ECP PLANTA CONCENTRADORA

50

Seconds

Seconds

Cable1406

DY

Per Unit X 10
.005
1K

.01

.03

.05

.1

.3

.5

740-CBH-004
Relay293
o

CT480
500/5

OCR
-2.5% TapP

740-XFR-002

500

10

30

50

Normalized (shifted) TCC


3-Phase (Sym) fault: 76.347kA @ 0.944kV
Faulted Bus:
Bus26
Configuration:
2+3 / A+B

220/23 kV

75 MVA
Relay295

100
1K

500

CT482
200/5

Relay292
o

300

CT479
4000/5

300

OCR

740-BSM-006
740-SGM-001B

740-CBM-006

SECC 30
o

100

CT207
800/5

100

Relay119
OCR

Cable1243
9-1/C 250

CT208
50/5

50
Bus23

50
Relay302
o

CT490
200/5

30
310-XFC-031
6.29 MVA
DY

23/0.963 kV

310-XFC-032
6.29 MVA
DY

30
310-XFC-033
6.29 MVA

23/0.963 kV

23/0.963 kV
DY

Cable1408

12-1/C 500

Cable1407

12-1/C 500

12-1/C 500

Bus26

10

Cable1406

Relay302 - P
GE Multilin
T60
CT Ratio 200:5
IEC - Curve A
Pickup = 0.87 (0.01 - 30 xCT Sec)
Time Dial = 1
3x = 6.3 s, 5x = 4.28 s, 8x = 3.3 s
1.071 kA @ 22.556 kV
t1: 3.78 s

SW323

12-1/C 500

Cable1410

310-MLB-002A
11190 kW

2.03 s

.5

.5

.3

.3

Relay119 - P
OC1

.1

.1

GE Multilin
750/760
CT Ratio 800:5
ANSI - Extremely Inverse
Pickup = 0.56 (0.05 - 20 xCT Sec)
Time Dial = 4
3x = 2.64 s, 5x = 0.99 s, 8x = 0.503 s
3.197 kA @ 22.556 kV
t1: 0.581 s

.05

.03

.01
.005

.01

.03

.05

.1

.3

.5

10

Per Unit X 10

Configuracin Actual

Fault: Phase(Normalized)
Circuit: TR2 + TR3 / A+B
Cortocircuito Trifasico

.03

50

.01
100

ETAP Star 11.0.0

MLB - 001, 002, 003


Project: ECP PLANTA CONCENTRADORA

30

.05

Seconds

Seconds

VFD13

10

COMPAA MINERA ANTAMINA S.A.


ESTUDIO DE COORDINACIN DE PROTECCIONES

- MLB 001, 002 Y 003


PROPUESTOS

DLF SAC

Pgina 261 de 551

Revisin: 0

Per Unit
.005
1K

.01

.03

500

.05

.1

.3

.5

10

30

50

100
1K

Normalized (shifted) TCC


Line-to-Line (Sym) fault: 18.353kA @ 23.737kV
Faulted Bus:
Bus23
Configuration:
1+2+3

740-CBH-004
Relay293
o

CT480
500/5

OCR
-2.5% TapP

300

500

300

740-XFR-002
220/23 kV

75 MVA
Relay295

Relay119 - P
OC1

CT482
200/5

Relay292
o

CT479
4000/5

OCR

100

GE Multilin
750/760
CT Ratio 800:5
ANSI - Extremely Inverse
Pickup = 0.56 (0.05 - 20 xCT Sec)
Time Dial = 1.8
3x = 1.19 s, 5x = 0.445 s, 8x = 0.226 s
18.353 kA @ 23.737 kV
t1: 0.107 s

740-BSM-006
740-SGM-001B

740-CBM-006

50

SECC 30
o

CT207
800/5

30

Relay119
OCR
o

50

30

Cable1243
9-1/C 250

CT208
50/5

100

Relay293 - P
OC1

Bus23

10

Relay302
o

310-XFC-031
6.29 MVA

DY

23/0.963 kV

310-XFC-032
6.29 MVA
DY

GE Multilin
F60
CT Ratio 500:5
IAC - Very Inverse
Pickup = 0.86 (0.01 - 30 xCT Sec)
Time Dial = 1.5
3x = 0.806 s, 5x = 0.399 s, 8x = 0.279 s
1.458 kA @ 220 kV
t1: 0.654 s

310-XFC-033
6.29 MVA

23/0.963 kV

23/0.963 kV

Cable1408

12-1/C 500

Cable1407

12-1/C 500

12-1/C 500

Cable1406

DY

10

Bus26

SW323

.5

0.215 s

Cable1410

12-1/C 500

VFD13

.5

.3

.3

0.349 s

310-MLB-002A
11190 kW

Relay292 - P
OC1

.1

.1

GE Multilin
F60
CT Ratio 4000:5
IAC - Very Inverse
Pickup = 0.93 (0.01 - 30 xCT Sec)
Time Dial = 0.9
3x = 0.484 s, 5x = 0.24 s, 8x = 0.168 s
11.705 kA @ 23.737 kV
t1: 0.444 s

.05

.03

.01
.005

.01

.03

.05

.1

.3

.5

.05

.03

10

30

Per Unit

Configuracin Corto Mnimo

Fault: Phase(Normalized)
Cortocircuito Bifsico

.01
100

ETAP Star 11.0.0

MLB - 001, 002, 003


Project: ECP PLANTA CONCENTRADORA

50

Seconds

Seconds

CT490
200/5

Per Unit X 10
.005
1K

.01

.03

.05

.1

.3

.5

740-CBH-004
Relay293
o

CT480
500/5

OCR

500

10

30

50

Normalized (shifted) TCC


3-Phase (Sym) fault: 33.778kA @ 23kV
Faulted Bus:
Bus23
Configuration:
1+2+3/ A+B+C

-2.5% TapP

740-XFR-002
220/23 kV

75 MVA

100
1K

500

Relay295
o

CT482
200/5

Relay292

300

300

CT479
4000/5

OCR

740-BSM-006
740-SGM-001B

740-CBM-006

SECC 30

100

100

CT207
800/5

Relay119
OCR
o

CT208
50/5

50

Cable1243
9-1/C 250

50
Bus23

Relay302
o

CT490
200/5

Bus26

23/0.963 kV

Cable1407

DY

12-1/C 500

12-1/C 500

10

23/0.963 kV

Cable1406

DY

310-XFC-032
6.29 MVA

30

310-XFC-033
6.29 MVA
23/0.963 kV

DY

12-1/C 500

310-XFC-031
6.29 MVA

Cable1408

30

10

SW323

Relay293 - P
OC1

12-1/C 500

Cable1410

GE Multilin
F60
CT Ratio 500:5
IAC - Very Inverse
Pickup = 0.86 (0.01 - 30 xCT Sec)
Time Dial = 1.5
3x = 0.806 s, 5x = 0.399 s, 8x = 0.279 s
1.039 kA @ 220 kV
t1: 1.25 s

310-MLB-002A
11190 kW

1.55 s

.5

.5

1.2 s
.3

.3

Relay119 - P
OC1
.1

GE Multilin
750/760
CT Ratio 800:5
ANSI - Extremely Inverse
Pickup = 0.56 (0.05 - 20 xCT Sec)
Time Dial = 1.8
3x = 1.19 s, 5x = 0.445 s, 8x = 0.226 s
33.778 kA @ 23 kV
t1: 0.107 s

.05

.03

.01
.005

.01

.03

.05

.1

.1

Relay292 - P
OC1
GE Multilin
F60
CT Ratio 4000:5
IAC - Very Inverse
Pickup = 0.93 (0.01 - 30 xCT Sec)
Time Dial = 0.9
3x = 0.484 s, 5x = 0.24 s, 8x = 0.168 s
9.939 kA @ 23 kV
t1: 0.605 s
.3

.5

Per Unit X 10

10

30

50

Configuracin Corto Mximo

Fault: Phase(Normalized)
Circuit: TR1 + TR2 + TR3 / A+B+C
Cortocircuito Trifasico

.03

.01
100

ETAP Star 11.0.0

MLB - 001, 002, 003


Project: ECP PLANTA CONCENTRADORA

.05

Seconds

Seconds

VFD13

Per Unit
.005
1K

.01

.03

.05

.1

.3

.5

740-CBH-004
o

CT480
500/5

500

10

30

50

Normalized (shifted) TCC


Line-to-Ground (Sym) fault: 0.126kA @ 22.556kV
Faulted Bus:
Bus23
Configuration:
2+3 +CLIP

-2.5% TapP

740-XFR-002
220/23 kV

75 MVA

100
1K

500

Relay295
o

CT482
200/5

300

300

Relay292
o

CT479
4000/5

OCR

740-BSM-006
740-SGM-001B

740-CBM-006

SECC 30

100

100

CT207
800/5

Relay119
OCR

CT208
50/5

50

Cable1243
9-1/C 250

50
Bus23

Relay302

30

30

CT490
200/5
310-XFC-031
6.29 MVA
DY

23/0.963 kV

310-XFC-032
6.29 MVA
DY

310-XFC-033
6.29 MVA

23/0.963 kV

23/0.963 kV
DY

Cable1408

Cable1407

12-1/C 500

Bus26

12-1/C 500

12-1/C 500

10

Cable1406

Relay295 - G
GE Multilin
T60
CT Ratio 200:5
Definite Time
Pickup = 0.25 (0.01 - 30 xCT Sec)
Time Dial = 1.5
3x = 1.5 s, 5x = 1.5 s, 8x = 1.5 s
0.126 kA @ 22.556 kV
t1: 1.5 s

SW323

12-1/C 500

Cable1410

310-MLB-002A
11190 kW

0.5 s
1

Relay119 - G
OC1

.5

.5

GE Multilin
750/760
CT Ratio 50:5
Definite Time
Pickup = 0.4 (0.05 - 20 xCT Sec)
Time Dial = 10
3x = 1 s, 5x = 1 s, 8x = 1 s
0.126 kA @ 22.556 kV
t1: 1 s

.3

.1

.3

.1

.05

.05

.03

.03

.01
.005

.01

.03

.05

.1

.3

.5

10

30

Per Unit

Configuracin Propuesta

Fault: Ground(Normalized)
Circuit: TR2 + TR3 / CLIP
Cortocircuito Monofsico, R=50ohm

.01
100

ETAP Star 11.0.0

MLB - 001, 002, 003


Project: ECP PLANTA CONCENTRADORA

50

Seconds

Seconds

VFD13

10

Per Unit X 10
.005
1K

.01

.03

.05

.1

.3

.5

740-CBH-004
Relay293
o

CT480
500/5

OCR
-2.5% TapP

740-XFR-002

500

10

30

50

Normalized (shifted) TCC


3-Phase (Sym) fault: 78.704kA @ 0.963kV
Faulted Bus:
Bus26
Configuration:
1+2+3/ A+B+C

220/23 kV

75 MVA
Relay295

100
1K

500

CT482
200/5

Relay292
o

300

CT479
4000/5

300

OCR

740-BSM-006
740-SGM-001B

740-CBM-006

SECC 30
o

100

CT207
800/5

100

Relay119
OCR

Cable1243
9-1/C 250

CT208
50/5

50
Bus23

50
Relay302
o

CT490
200/5

30
310-XFC-031
6.29 MVA
DY

23/0.963 kV

310-XFC-032
6.29 MVA
DY

30
310-XFC-033
6.29 MVA

23/0.963 kV

23/0.963 kV

Cable1408

12-1/C 500

Cable1407

12-1/C 500

12-1/C 500

Bus26

10

Cable1406

DY

10

SW323

12-1/C 500

5
Cable1410

3
310-MLB-002A
11190 kW

Relay119 - P
OC1
1

GE Multilin
750/760
CT Ratio 800:5
ANSI - Extremely Inverse
Pickup = 0.56 (0.05 - 20 xCT Sec)
Time Dial = 2.5
3x = 1.65 s, 5x = 0.619 s, 8x = 0.314 s
3.295 kA @ 23 kV
t1: 0.349 s

.5

.3

.5

.3

.1

.1

Relay302 - P
.05

.03

.01
.005

0.127 s

GE Multilin
T60
CT Ratio 200:5
IEC - Curve A
Pickup = 0.87 (0.01 - 30 xCT Sec)
Time Dial = 0.01
3x = 0.063 s, 5x = 0.0428 s, 8x = 0.033 s
1.104 kA @ 23 kV
t1: 0.0372 s
.01

.03

.05

.1

.05

.03

.3

.5

Per Unit X 10

10

30

50

ETAP Star 11.0.0

MLB - 001, 002, 003


Project: ECP PLANTA CONCENTRADORA
Configuracin Corto Mximo

Fault: Phase(Normalized)
Circuit: TR1 + TR2 + TR3 / A+B+C
Cortocircuito Trifasico

.01
100

Seconds

Seconds

VFD13

COMPAA MINERA ANTAMINA S.A.


ESTUDIO DE COORDINACIN DE PROTECCIONES

- MLB 004
ACTUALES

DLF SAC

Pgina 266 de 551

Revisin: 0

Per Unit
.005
1K

.01

.03

.05

.1

.3

.5

500

300

30

50

100
1K

500

300

Relay229 - P
OC1
GE Multilin
F60
CT Ratio 800:5
IEEE - Extremely Inverse
Pickup = 0.612 (0.01 - 30 xCT Sec)
Time Dial = 0.65
3x = 2.37 s, 5x = 0.843 s, 8x = 0.37 s
17.471 kA @ 23 kV
t1: 0.125 s

100

50

100

50

30

30

10

10

5
740-CBH-007

Relay226

OCR

CT347
500/5

-2.5% TapP

740-XFR-003
220/23 kV
75 MVA
Relay227

Relay226 - P
OC1

200/5

CT348

Relay195
4000/5
CT311

OCR

1.402 kA @ 220 kV
t1: 0.697 s

740-BSM-007

740-CBM-008

740-SGM-002

.5

0.34 s

SECC 48

.5

CT359
800/5

Relay229
OCR

.3

.3

CT358
50/5

Bus58

Cable48

9-1/C 350

0.232 s

Relay308
o

CT496
250/5
310-XFC-604
6.5 MVA
DY

23/1.15 kV

Relay195 - P
OC1

23/1.15 kV
DY
-5% TapP

Cable1460

12-1/C 500

-5% TapP

12-1/C 500

Cable1459

12-1/C 500

.1

310-XFC-606
6.5 MVA

23/1.15 kV
DY

-5% TapP

.05

OCR

310-XFC-605
6.5 MVA

GE Multilin
F60
CT Ratio 4000:5
IAC - Very Inverse
Pickup = 0.93 (0.01 - 30 xCT Sec)
Time Dial = 0.9
3x = 0.484 s, 5x = 0.24 s, 8x = 0.168 s
13.414 kA @ 23 kV
t1: 0.357 s

Cable1461

.1

.03
Bus59
SW22

310-CYC-101

.01
.005

11190 kW
310-MLB-004A

.01

.03

.05

.1

.3

.5

10

Per Unit

Configuracin Actual

Fault: Phase(Normalized)
Circuit: TR2 + TR3 + CLIP
Cortocircuito Trifasico

50

.03

.01
100

ETAP Star 11.0.0

MLB - 004
Project: ECP PLANTA CONCENTRADORA

30

.05

Seconds

Seconds

10

Normalized (shifted) TCC


3-Phase (Sym) fault: 17.471kA @ 23kV
Faulted Bus:
Bus58
Configuration:
2+3 +CLIP

Per Unit
.005
1K

.01

.03

.05

.1

.3

.5

10

30

50

Normalized (shifted) TCC


Line-to-Ground (Sym) fault: 0.418kA @ 23kV
Faulted Bus:
Bus58
Configuration:
2+3 +CLIP

500

100
1K

500

300

300
740-CBH-007
o

CT347
500/5
-2.5% TapP

740-XFR-003
220/23 kV
75 MVA
Relay227
o

100

CT348

200/5

100

Relay195
o

OCR

740-BSM-007

4000/5
CT311

50

740-CBM-008

GE Multilin
T60
CT Ratio 200:5
Definite Time
Pickup = 0.25 (0.01 - 30 xCT Sec)
Time Dial = 1.5
3x = 1.5 s, 5x = 1.5 s, 8x = 1.5 s
0.0836 kA @ 23 kV
t1: 1.5 s

SECC 48

30

CT359
800/5

Relay229
OCR

Bus58

Cable48

9-1/C 350

CT358
50/5

10

Relay308
o

CT496
250/5
310-XFC-604
6.5 MVA

310-XFC-605
6.5 MVA

23/1.15 kV

23/1.15 kV
DY

12-1/C 500

-5% TapP

Cable1460

12-1/C 500

Cable1459

12-1/C 500

-5% TapP

Bus59
SW22

310-CYC-101

1
11190 kW
310-MLB-004A

1.1 s

.5

.5

.3

.3

Relay229 - G
OC1

.1

.1

GE Multilin
F60
CT Ratio 50:5
Definite Time
Pickup = 0.4 (0.01 - 30 xCT Sec)
Time Dial = 0.4
3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s
0.167 kA @ 23 kV
t1: 0.4 s

.05

.03

.01
.005

.01

.03

.05

.1

.3

.5

.05

.03

10

Per Unit

Configuracin Actual

Fault: Ground(Normalized)
Circuit: TR2 + TR3 + CLIP
Cortocircuito Monofsico

50

.01
100

ETAP Star 11.0.0

MLB - 004
Project: ECP PLANTA CONCENTRADORA

30

Seconds

Seconds

10

310-XFC-606
6.5 MVA

23/1.15 kV
DY

-5% TapP

OCR

30

Cable1461

DY

50

Relay227 - G

740-SGM-002

Per Unit
.005
1K

.01

.03

.05

.1

.3

.5

10

30

50

Normalized (shifted) TCC


3-Phase (Sym) fault: 64.505kA @ 1.15kV
Faulted Bus:
Bus59
Configuration:
2+3 +CLIP

500

100
1K

500

300

300
740-CBH-007

Relay226
o

OCR

CT347
500/5

-2.5% TapP

740-XFR-003
220/23 kV
75 MVA
Relay227
o

100

200/5

CT348

100

Relay195
o

OCR

740-BSM-007

4000/5
CT311

50

50

740-CBM-008
740-SGM-002

SECC 48

30

30
o

CT359
800/5

Relay229
OCR
o

Bus58

Cable48

10

9-1/C 350

CT358
50/5

10
Relay308
o

CT496
250/5

DY

23/1.15 kV

Cable1460

-5% TapP

12-1/C 500

-5% TapP

12-1/C 500

Cable1459

310-XFC-606
6.5 MVA
DY

-5% TapP

12-1/C 500

Seconds

23/1.15 kV

Bus59
SW22

310-CYC-101

1
11190 kW
310-MLB-004A

.5

.5

.3

.3

Relay229 - P
OC1

.1

.1

GE Multilin
F60
CT Ratio 800:5
IEEE - Extremely Inverse
Pickup = 0.612 (0.01 - 30 xCT Sec)
Time Dial = 0.65
3x = 2.37 s, 5x = 0.843 s, 8x = 0.37 s
3.225 kA @ 23 kV
t1: 0.512 s

.05

.03

.01
.005

.01

.03

.05

.1

.05

.03

.3

.5

10

Per Unit

Configuracin Actual

Fault: Phase(Normalized)
Circuit: TR2 + TR3 + CLIP
Cortocircuito Trifasico

50

.01
100

ETAP Star 11.0.0

MLB - 004
Project: ECP PLANTA CONCENTRADORA

30

Seconds

310-XFC-605
6.5 MVA

23/1.15 kV
DY

GE Multilin
T60
CT Ratio 250:5
IEC - Curve A
Pickup = 1.1 (0.01 - 30 xCT Sec)
Time Dial = 1.5
3x = 9.45 s, 5x = 6.42 s, 8x = 4.95 s
Inst = 3.9 (0.01 - 30 xCT Sec)
Time Delay = 0.35 s
1.085 kA @ 23 kV
t1: 0.35 s

310-XFC-604
6.5 MVA

Cable1461

Relay308 - P

COMPAA MINERA ANTAMINA S.A.


ESTUDIO DE COORDINACIN DE PROTECCIONES

- MLB 004
PROPUESTOS

DLF SAC

Pgina 270 de 551

Revisin: 0

Per Unit
.005
1K

.01

.03

.05

.1

.3

.5

10

30

50

Normalized (shifted) TCC


3-Phase (Sym) fault: 23.373kA @ 22.999kV
Faulted Bus:
Bus58
Configuration:
1+3 / B+C

500

100
1K

500

300

300
740-CBH-007
Relay226
o

CT347
500/5

OCR
-2.5% TapP

740-XFR-003
220/23 kV

75 MVA

100

100

Relay227
o

200/5

CT348

Relay195
o

OCR

740-BSM-007

4000/5
CT311

50

50

740-CBM-008

740-SGM-002

SECC 48

30

30
o

CT359
800/5

Relay229
OCR

Bus58

Cable48

10

9-1/C 350

CT358
50/5

10
Relay308
o

12-1/C 500

310-XFC-604
6.5 MVA

310-XFC-605
6.5 MVA

23/1.15 kV

23/1.15 kV
DY

.5

.3

23/1.15 kV

-5% TapP

12-1/C 500

Cable1460

12-1/C 500

-5% TapP

Bus59
SW22

GE Multilin
F60
CT Ratio 4000:5
IAC - Very Inverse
Pickup = 0.93 (0.01 - 30 xCT Sec)
Time Dial = 0.9
3x = 0.484 s, 5x = 0.24 s, 8x = 0.168 s
13.56 kA @ 22.999 kV
t1: 0.351 s

Cable1459

-5% TapP

Relay195 - P
OC1

310-XFC-606
6.5 MVA
DY

Cable1461

DY

310-CYC-101

1
11190 kW
310-MLB-004A

.5

0.332 s

.3

0.232 s

Relay229 - P
OC1

.1

.1

Relay226 - P
OC1

GE Multilin
F60
CT Ratio 800:5
IEEE - Extremely Inverse
Pickup = 0.612 (0.01 - 30 xCT Sec)
Time Dial = 0.58
3x = 2.12 s, 5x = 0.752 s, 8x = 0.33 s
23.373 kA @ 22.999 kV
t1: 0.112 s

.05

.03

.01
.005

.01

.03

.05

.1

GE Multilin
F60
CT Ratio 500:5
IAC - Very Inverse
Pickup = 0.86 (0.01 - 30 xCT Sec)
Time Dial = 1.5
3x = 0.806 s, 5x = 0.399 s, 8x = 0.279 s
1.418 kA @ 220 kV
t1: 0.685 s
.3

.5

10

Per Unit

Configuracin Corto Mximo

Fault: Phase(Normalized)
Circuit: TR1 + TR3 y B+C
Cortocircuito Trifasico

50

.03

.01
100

ETAP Star 11.0.0

MLB - 004
Project: ECP PLANTA CONCENTRADORA

30

.05

Seconds

Seconds

CT496
250/5

740-CBH-007
o

CT347
500/5
-2.5% TapP

740-XFR-003
220/23 kV
75 MVA
Relay227
o

CT348

R
200/5

Relay195
o

OCR

740-BSM-007

4000/5
CT311

740-SGM-002

740-CBM-008

SECC 48
o

CT359
800/5

Relay229
OCR
o

Bus58

Cable48

9-1/C 350

CT358
50/5

Relay308
o

CT496
250/5

310-XFC-606
6.5 MVA

23/1.15 kV

23/1.15 kV

23/1.15 kV

DY

DY
-5% TapP

Cable1460

12-1/C 500

-5% TapP

12-1/C 500

Cable1459

-5% TapP

12-1/C 500

310-XFC-605
6.5 MVA

Bus59
SW22

310-CYC-101

11190 kW
310-MLB-004A

Cable1461

DY

310-XFC-604
6.5 MVA