Professional Documents
Culture Documents
Ctu2601 24V 01
Ctu2601 24V 01
V1
Input
Not in use
0-10Vdc
Analog output 1
Digital output 8
Digital output 7
Digital output 6
Digital output 5
Digital output 4
24VAC
Digital output 3
Digital output 2
Digital output 1
Analog output 2
Important !
Disconnect power to the main board
before making any changes to DIP
switches/Jumpers and while wiring
the unit .
AO1
AO2
Fuse 8A
CTU2601-24V-01
MAC Address
DIP switch (S1)
Configuration
DIP switch (S2)
ON
T3
AI1
0-10Vdc
AI2 5VDC A
6 7
RS485
Original with BT
DIN
Off
Off
Off
On
Off
Off
Off
On
Off
On
On
Off
Off
Off
On
On
Off
On
Off
On
On
DIN=
MAC+1200
DIN=
MAC+1000
DIN=
MAC+800
DIN=
MAC+600
DIN=
MAC+400
DIN=
MAC+200
On
On
On
DIN=MAC
DIP Switch S1
MAC Address
EEPROM
ON
1
2
4
8
16
32
64
128
1 2 3 4 5 6 7 8
CTU2601-24V-01
1
Bacnet Protocol
Title:
Date: 09.03.10
RS485
Communication cable
2x22AWG
Twisted, Shielded
(120 @ 1MHz )
Tel: +972-3-9626462
Fax: +972-3-9626620
e-mail: support@meitavtec.com
Bacnet Protocol
meitav tec
LED Power
Device Instance
Number DIN
Analog input 2
T2
Analog input 1
Normally open
T1
DI8 12V
Digital input 8
DI6 DI7
Digital input 7
Digital input 6
DI4 DI5
Digital input 5
Digital input 4
DI2 DI3
Digital input 3
Digital input 2
Digital input 1
DI1
LED TX/RX
ON
09.03.10
Drawn: M.Ruchansky
Checked:S.Lukin
Approved: A.Samocha
File: CTU2601-24V-01-BELIMO.vsd