Analisis Karakteristik Oli Trafo Pakai

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

Analisis Karakteristik Oli Trafo Pakai (Parameter Oil Transformer Lab.

Test)
No.

Parameter Uji
1
1 Interfacial Tension /
Tegangan Antar Muka
2 Neutralization Number /
Angka Kenetralan /
Kadar Asam
3 Break Down Voltage /
Tegangan Tembus

STD
2

Hasil Uji
3

Dyne / cm

Batasan

5
24' -30'

Mg KOH/gram

1
Maximum

kV/2,5 mm

4 Colour / Warna

ASTM Std. oC

5 Flash Point / Titik Nyala

6 Water Content / Kadar


Air

ppm

7 Sedimen and Sludge /


Sedimen

30kV/2,5mm
3.5
146 oC
minimum
20
Maximum
0.1

Tujuan dari Test. Analisis Karakteristi Oli Trafo Pakai adalah menunjukkan adanya kandun
trafo, atau pengujian kelayakan minyak trafo
Sumber : IEC 156, IEC 296

tan delta, DFR, Insulation Resistance, Polarity Index, Winding Resistance, Turn Ratio, DG
estimasi lifetime dari trafo melalui pengujian metode Weibull analysis

Langkah yang diambil bila


NO.5 Tidak tercapai

Metode

Ket/
Saran

6
Filtering

ISO 6295

0,4 - 1 (filtering)
> 1 (changing)

IEC296-1969 Normal

Filtering

IEC
156-1995

Normal

Reclamation

ASTM
D.1524

Normal

Oil Changing

ASTM D.92

Normal

Filtering

ASTM
D.1533
IEC 733
ASTM
D.1698

Normal

Filtering

Normal

Normal

nunjukkan adanya kandungan-kandungan yang terdapat di dalam minyak

Resistance, Turn Ratio, DGA, Furan Test, Degree Polymarization, SFRA

You might also like