Total Connected Load On Diesel Generator Set: Linear Load: Non-Linear Load

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 1

System Voltage ( P-P )

415

Volt

Linear Load:

General Equipments, Heater

System Voltage ( P-N )

230

Volt

Non-Linear Load:

UPS,Invertor,Ballast,VFD

Future Load Expansion

0%

Average Intermittent Use of Equipment

0.8

Sr.No

Equipment
Tower Crain-E
Tower Crain-C
Tower Crain-C

(0.7 To 1.0)
0.8
Total Connected Load on Diesel Generator Set
Load
Load Type
Supply
Qty
Load
Kw/Hp
Motor
Motor
Motor

3Ph
3Ph
3Ph

1
1
1

43
43
43

Kw
Kw
Kw

Starting Condition
Starting P.F Running P.F
0.8
0.8
0.8

0.8
0.8
0.8

Diversity
Factor

Motor Starter

0.5
0.5
0.5

Auto.Tra.
Y-D
Auto.Tra.

Starting
Amp

Running Condition

Full Load
Starting Kva Starting Kw
Kva

Full
Load
Kw

Full Load
Amp

RESULTS

112
150
112
0
0
0
0

81
108
81
0
0
0
0

65
86
65
0
0
0
0

27
27
27
0
0
0
0

22
22
22
0
0
0
0

37
37
37
0
0
0
0

Starting Kva
Starting Kw
Starting Amp
Running Kva
Running Kw
Running Amp

269
215
374
81
65
112

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

Voltage (P-N)
Efficiency
Engine Overload Capacity

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

Generator KVA
Engine KW

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

Alternator Details
230
80%
130%

(Appro 130% To 150%)

Required Generator Rating

215
67

Calculate D.G Set Efficiency & Unit Rate of


Power
D.G Size ( Kva )
D.G P.F
D.G Running Hours
Diesel Consumption (Liter)
KWH Reading of Meter
M.F of KWH Meter
Diesel Rate /Liter (Rs)

1000
1
20
1000
10000
1
40

Efficiency of D.G
KWH/Liter (Unit Per Liter)
Unit Rate of Power (Rs)

63%
10
4.0

(Select D.G near This Value)

Calculate Approximate Fuel


Consumption
D.G Size (Kva)
D.G P.F
D.G Operation

115
0.8
1/2 Load

Required Diesel
Liter/Hour
12.88