Professional Documents
Culture Documents
LESSER 6.4.4 Back Pressure
LESSER 6.4.4 Back Pressure
6.4.4
Back Pressure
6.4.4.1 Definitions
Back pressure is the pressure that exists at the outlet of a pressure relief device as a result of the
pressure in the discharge system. It is the sum of the superimposed and built-up back pressures and
has an influence on the function of the safety valve.17)
Back Pressure = Built-up + Superimposed
The type of back pressure that occurs depends on the type of installation. The simplest version of
installation is a vessel with a safety valve but no connected outlet line (see Figure 6.4.4.1-1). This
configuration is used for uncritical mediums like water or air and small safety valve sizes. With this
configuration no additional back pressure arises.
Safety valve
Safety valve
Safety valve
Blowdown System
Outlet line
Outlet line
Vessel
Vessel
Figure 6.4.4.1-1:
Without Back Pressure
Figure 6.4.4.1-2:
Built-up Back Pressure
Vessel
Figure 6.4.4.1-3:
Superimposed Back pressure
17)
LWN 753.00
edition: 10.05.2010
6.4-3
Distinction
Built-up
Back Pressure
Action
< 15%
No action required
15%
Balanced Bellows
Back Pressure
Constant
Superimposed
Back Pressure
Variable
Balanced Bellows
CDTP-correction
Balanced Bellows
Depending on the type of back pressure, LESER defines different actions to avoid reductions of
capacity (Figure 6.4.4.2-1).
Built-up Back Pressure
< 15%: LESER conventional Safety Valves are able to compensate for <15% built-up back pressure
without further devices.
15%: To compensate for 15% built-up back pressure a balanced bellows has to be installed. This
compensation reaches up to 50 % for safety valves of the API product group and up to 35% for all
other LESER safety valves with balanced bellows
Note: API 520 defines the built- up back pressure limit for conventional safety valves to 10%.
Constant Superimposed Back Pressure
The constant superimposed back pressure can be compensated for either by a balanced bellows or
by Cold Differential Test Pressure correction (CDTP). A combination of both alternatives is not
possible.
Compensation by balanced bellows
Balanced bellows are designed in such a way that the effective area AB of the bellows is equivalent
to that of the seat area AS (Figure 6.4.4.2-2). Balanced bellows are typically made from metallic
materials like stainless steel. Elastomer bellows are not suitable for compensation of back pressure.
FS
AB
p
AS
Used Symbols
Fpa Bellows
Fpa Disc
Fp
Fs
Spring force
Fp
Fpa Bellows
Fpa Disc
AS
Seat area
AB
Bellows area
AS = AB
Figure 6.4.4.2-2: Function of balanced bellows
The compensation by balanced bellows reaches up to 50 % for safety valves of the API product
group and up to 35% for all other LESER safety valves with balanced bellows.
LWN 753.00
edition: 10.05.2010
6.4-4
Pressure
Set pressure
10 bar
2 bar
8 bar
When the superimposed back pressure is taken into account LESER will deliver the safety valve with
a spring which is designed for the differential pressure (From the example: 8 bar instead of 10 bar).
Variable Superimposed Back Pressure:
To compensate for variable superimposed back pressure a balanced bellows has to be installed. This
compensation reaches up to 50 % for safety valves of the API product group and up to 35% for all
other LESER safety valves with balanced bellows.
18)
LWN 753.00
edition: 10.05.2010
6.4-5