CH - 6.2 Final CCTXXX
CH - 6.2 Final CCTXXX
2 Final Cct
FINAL CCT
Definition : cct that come out from the
distribution cct @ user unit @ fuse switch to
feed one or more equipment point @ outlet
socket w/out intermediate with other
distribution box OR
Cct that is able to supply power to the
machineries, equipment @ outlet socket that
need current directly (motor) @ via outlet
socket (oven)
User cct that is assembled by the contractor in
final stage.
It’s started from distribution box until the
point of equipment.
Point is a fix wiring base for lighting, outlet
socket @ equipment that need current.
Lighting point / power point.
From distribution box, variety of fuse
range & cable size is use to match the
final cct & installation point.
Purpose of divide the main cct with final cct.
3 Litar akhir lampu Sama dgn arus beban dgn kadar min.
100W bg setiap pemegang lampu
4 Litar akhir jam, pencukur, Diabaikan (dianggap tiada kerana
soket alur keluar pencukur, terlalu rendah)
pengubah loceng &
kelengkapan yg
menggunakan kuasa <5W
Cth pengiraan :
Berapakah litar akhir yg diperlukan & berapakah arus yg
perlu dibekalkan setelah faktor kepelbagaian?
1. Lampu biasa 20W dan 120W [12 buah setiap satu]
2. Alat pemasak 5kW
Sollution :
3. 20W lamp 100W/240V=0.41A. Satu litar akhir 5A boleh
menampung 5/0.41A=13lamp
120 W lamp 120W/240V=0.5A. Satu litar akhir 5A boleh
menampung = 5/0.5A=10 lampu. So, kena pakai 2 litar
akhir la….
4. Arus yg diperlukan = (5x1000)/240V=20.8A
Arus slps faktor kepelbagaian = 10+(20.8-10)x30%
= 10+(3.24) = 13.24A
So, satu litar akhir 13A diperlukan.
Cable size determination