Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

LMS TECHNOLOGIES, INC.

6423 Cecilia Circle


Bloomington, MN 55439
(952) 918-9060, Fax: (952) 918-9061
Test Report-ASHRAE Test Standard 52.2
Test Requested By:

CLARCOR

Manufacturer:

CLARCOR

Product Name:

NF20000

Report # : 1409
Test Date : 09/27/2007

Model Number:
Dimensions:

13.8" x 26.0" Cylindrical ( Nominal )

Number of Pleats:

Minipleat, 9 PPI

Filter Description:

White, Synthetic Cylindrical Minipleat Filter

How Filter Obtained:

Provided by Clark Filter

Test Results
Test Air Flow Rate(CFM)/Velocity (FPM)
Initial Resistance (in. WG)
Final Resistance (in. WG)
Minimum Efficiency Rating Value (MERV)
Minimum Average Efficiency 0.3 to 1.0 Microns (E1)
Minimum Average Efficiency 1.0 to 3.0 Microns (E2)
Minimum Average Efficiency 3.0 to 10 Microns (E3)
Dust Fed to Final Resistance(grams)

903 cfm / 118 fpm


0.929"
4.000"
MERV 15 @ 903 cfm
89.0
98.3
99.8
789.3 grams

Test Description
Temp & Humidity:
Particle Analysis:

72 @ 40%
Hiac/Royco FE-80

Test Dust:
Test Aerosol:

ASHRAE 52.1 Dust


KCL Neutralized

Test Engineer :

Mick Flom/Emile Tadros/Kian Imani/Todd Krueger/Pat Best

Approved By:

K. C. Kwok, Ph.D.

LMS Technologies, Inc.


6423 Cecilia Circle
Bloomington, MN 55439
(612) 918-9060, Fax: (612) 918-9061

September 27, 2007


NF20000
52.2
REP# : 1409
KCL, Neutralized

Date :
Filter ID :
Test Type :
Test Aerosol :
P (" H2O)

Requested by :
CLARCOR
Manufacturer :
CLARCOR

0.929in. 0.969in. 1.697in. 2.465in. 3.232in. 4.000in. *CME


Fractional Efficiency (%)

Size Range (m)


0.3-0.4
0.4-0.55
0.55-0.7
0.7-1.0
1.0-1.3
1.3-1.6
1.6-2.2
2.2-3.0
3.0-4.0
4.0-5.5
5.5-7.0
7.0-10.0

79.7
86.9
93.1
96.3
97.2
98.0
98.7
99.2
99.6
99.8
99.9
99.9

94.3
96.8
98.5
99.1
99.5
99.8
99.9
99.9
99.9
100.0
100.0
100.0

99.9
99.9
99.9
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0

99.9
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0

99.9
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0

99.9
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0

79.7
86.9
93.1
96.3
97.2
98.0
98.7
99.2
99.6
99.8
99.9
99.9

Fractional Efficiency versus Particle Diameter

100

Fractional Efficiency (%)

80

60
0.929in.

40

0.969in.
100.0

1.697in.

80.0
60.0

2.465in.

20

3.232in.

40.0

*CME

20.0
0.0
0.1

10

4.000in.

0
0.1

TEST SUPERVISOR
MICK FLOM_____

1
Particle Diameter (m)
ENGINEERING APPROVAL
K.C. KWOK, PH.D._______

10