Section 4 Protection Functions: 4.4.3.8 Monitored Data

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Section 4

Protection functions

Table 357:
Parameter
Operation

4.4.3.8

1MRS757644 B

PREVPTOC Non group settings


Values (Range)

Unit

Step

1=on
5=off

Description

1=on

Operation Off / On

Monitored data
Table 358:

PREVPTOC Monitored data

Name

4.4.3.9

Default

Values (Range)

Unit

START_DUR

Type
FLOAT32

0.00...100.00

PREVPTOC

Enum

1=on
2=blocked
3=test
4=test/blocked
5=off

Description
Ratio of start time /
operate time
Status

Technical data
Table 359:

PREVTOC Technical data

Characteristic

Value

Operation accuracy

Depending on the frequency of the current


measured: fn 2 Hz
1.5% of the set value or 0.002 x In

Start time1)2)
IFault = 2.0 x set Start

value

Minimum

Typical

Maximum

22 ms

24 ms

25 ms

Reset time

< 40 ms

Reset ratio

Typical 0.96

Retardation time

< 35 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Suppression of harmonics

DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,

1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact

4.4.4

Negative-sequence overcurrent protection for motors


MNSPTOC

4.4.4.1

Identification
Function description
Negative-sequence overcurrent
protection for motors

436

IEC 61850
identification
MNSPTOC

IEC 60617
identification
I2>M

ANSI/IEEE C37.2
device number
46M

620 series
Technical Manual