Section 4 Protection Functions: 4.4.3.8 Monitored Data
Section 4 Protection Functions: 4.4.3.8 Monitored Data
Section 4 Protection Functions: 4.4.3.8 Monitored Data
Protection functions
Table 357:
Parameter
Operation
4.4.3.8
1MRS757644 B
Unit
Step
1=on
5=off
Description
1=on
Operation Off / On
Monitored data
Table 358:
Name
4.4.3.9
Default
Values (Range)
Unit
START_DUR
Type
FLOAT32
0.00...100.00
PREVPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Description
Ratio of start time /
operate time
Status
Technical data
Table 359:
Characteristic
Value
Operation accuracy
Start time1)2)
IFault = 2.0 x set Start
value
Minimum
Typical
Maximum
22 ms
24 ms
25 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
4.4.4
4.4.4.1
Identification
Function description
Negative-sequence overcurrent
protection for motors
436
IEC 61850
identification
MNSPTOC
IEC 60617
identification
I2>M
ANSI/IEEE C37.2
device number
46M
620 series
Technical Manual