COMPLIANCE SHEET

Project: Dambulla: 10P16


Client:
NWSDB.
Client letter No. : WSP/ Gr. Dambulla/Transmission /56/ (635) date. 28-11-2012
Date of reply :
06-03-2013

Comments s per WSP/Gr. Dambulla/ intake/ 60/1043 Dated 28/02/2012

Provide details of roof with welding etc.

Details will be provided by civil contractor during


execution

Change of roof truss to angle section

For building with span up to 8.0 m tubular sections


are recommended ..

Provide front view of cable trays to show


more details .

This will be shown in electrical drawing only.

VENTILATION of Diesel generator

Ventilation for DG internal are designed


by Powerica - DG supplier. The system has
got inlet fan and an exhaust fan which
suck fresh air from atmosphere for cooling
the DG internals, and hot air is carried
away thro exhaust pipe line. Capacity of
suction/exhaust fans, pipe sizes,
ventilation sizes - all are designed &
supplied by Powerica. W.r.t room
ventilation, we have considered exhaust
fans (actually not required, still provided
as good engg practise).

Contract does not call for, and hence not


considered. If required, area outside DG
room can be utilized.

Maintenance space

Suction capacity of exhaust fans.

Pl refer to reply to point #4

Complied by (Signature):
Name:
Radhika Gopakumar
Department: Civil

VA TECH WABAG LTD.