When the AIS is connected to EC-3000 (all software versions),
), necessary is the following setting. Otherwise, the ECDIS generates alerts ts which cannot be acknowledged with the ALARM ACK key. The ECDIS also receives alerts erts during the selftest on FA-150 AIS. Fig.1 is the alert list showing the he alerts receiving from FA-150. Alert numbers
Fig.1 Alert list showing the alerts from FA-150
(A) Connection of FA-150 of V04.01 On FA-150 (V04.01), change AMS mode fr from LEGACY to ALERT IF1. ([MENU] -> DIAGNOSTICS -> FOR SERVICE -> OTHER -> AMS MODE) See FQ4-2013-030. (B) Connection of FA-30/50/100 and FA-150 of V03.01 and earlier These AISs do not include interfacing for alarm acknowledge input from the ECDIS, so setup FMD-3200/3300 to disable the al alerts by using the following steps. 1. Open Common Installation Setting m menu and select Alert Definition List. 2. In the left pane, the list of sensors, select AIS Transponder. 3. In the right pane, select the alert number (Alert Num). 4. Click EDIT. 5. In Alert Detail Setting display, set Is Active to NO. See FQ4-2013-028. 6. Repeat steps 3 to 5 to disable all alerts related to AIS; 001, 002, 003, 004, 005, 008, 025, 026, 029, 030, 032, and 035. CONFIDENTIAL (internal use only) This confidential document is used only by FURUNO authorized persons. It is strictly prohibited to reproduce the document in whole or in part without prior written permission of FURUNO.