Profis Anchor 2.4.

www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

1
12/9/2014

Specifier's comments:

1 Input data
Anchor type and diameter:

AWS D1.1 GR. B 3/4

Effective embedment depth:

hef = 6.250 in.

Material:
Proof:

design method ACI 318-08 / CIP

Stand-off installation:

eb = 0.000 in. (no stand-off); t = 0.750 in.

Anchor plate:

lx x ly x t = 12.000 in. x 21.000 in. x 0.750 in.; (Recommended plate thickness: not calculated)

Profile:

S shape (AISC); (L x W x T x FT) = 3.000 in. x 2.330 in. x 0.170 in. x 0.260 in.

Base material:

cracked concrete, 2500, fc' = 2500 psi; h = 8.000 in.

Reinforcement:

tension: condition B, shear: condition B;

Seismic loads (cat. C, D, E, or F)

edge reinforcement: none or < No. 4 bar


yes (D.3.3.6)

Geometry [in.] & Loading [lb, in.lb]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.4.8

www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

12/9/2014

2 Load case/Resulting anchor forces


Load case: Design loads

3
y

Anchor reactions [lb]


Tension force: (+Tension, -Compression)
Tension force
Shear force
Shear force x
Anchor
1
0
2000
2000
2
0
2000
2000
3
0
2000
2000
4
1746
2000
2000
5
1746
2000
2000
6
1746
2000
2000
max. concrete compressive strain:
0.05 []
max. concrete compressive stress:
199 [psi]
resulting tension force in (x/y)=(-4.000/0.000):
5238 [lb]
resulting compression force in (x/y)=(5.163/0.000): 5238 [lb]

Shear force y
0
0
0
0
0
0

5
Tension

2
Compression

3 Tension load
Load Nua [lb]
1746

Capacity fNn [lb]


21547

Utilization bN = Nua/fNn
9

Status
OK

Pullout Strength*

1746

3297

53

OK

Concrete Breakout Strength**

5238

7297

72

OK

N/A

N/A

N/A

N/A

Steel Strength*

Concrete Side-Face Blowout, direction **


* anchor having the highest loading

**anchor group (anchors in tension)

3.1 Steel Strength


Nsa
= n Ase,N futa
f Nsteel Nua

ACI 318-08 Eq. (D-3)


ACI 318-08 Eq. (D-1)

Variables
n
1

Ase,N [in.2]
0.44

futa [psi]
65000

fsteel
0.750

f Nsa [lb]
21547

Calculations
Nsa [lb]
28730
Results
Nsa [lb]
28730

Nua [lb]
1746

3.2 Pullout Strength


NpN = yc,p Np
Np
= 8 Abrg f'c
f NpN Nua

ACI 318-08 Eq. (D-14)


ACI 318-08 Eq. (D-15)
ACI 318-08 Eq. (D-1)

Variables
yc,p
1.000

Abrg [in.2]
0.79

f'c [psi]
2500

fconcrete
0.700

fseismic
0.750

Calculations
Np [lb]
15700
Results
Npn [lb]
15700

fnonductile
0.400

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

f Npn [lb]
3297

Nua [lb]
1746

Profis Anchor 2.4.8

www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

3
12/9/2014

3.3 Concrete Breakout Strength


Ncbg

(AA ) y
Nc

Nc0

ec,N

yed,N yc,N ycp,N Nb

ACI 318-08 Eq. (D-5)

f Ncbg Nua
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef
1
2 e'N 1.0
yec,N =
1+
3 hef
ca,min
1.0
yed,N = 0.7 + 0.3 1.5h
ef
ca,min 1.5hef
1.0
ycp,N = MAX c , c
ac
ac
1.5
'
Nb
= kc l fc hef

)
)

ACI 318-08 Eq. (D-1)


ACI 318-08 Eq. (D-6)
ACI 318-08 Eq. (D-9)
ACI 318-08 Eq. (D-11)
ACI 318-08 Eq. (D-13)
ACI 318-08 Eq. (D-7)

Variables
hef [in.]
6.250

ec1,N [in.]
0.000

ec2,N [in.]
0.000

ca,min [in.]
33.000

cac [in.]
0.000

kc
24

l
1

f'c [psi]
2500

ANc0 [in.2]
351.56

yec1,N
1.000

yec2,N
1.000

yed,N
1.000

ycp,N
1.000

fconcrete
0.700

fseismic
0.750

fnonductile
0.400

f Ncbg [lb]
7297

Nua [lb]
5238

yc,N
1.000

Calculations
ANc [in.2]
651.56
Results
Ncbg [lb]
34750

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Nb [lb]
18750

Profis Anchor 2.4.8

www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

4
12/9/2014

4 Shear load
Load Vua [lb]
2000

Steel Strength*
Steel failure (with lever arm)*

Capacity fVn [lb]


18674

Utilization bV = Vua/fVn
11

Status
OK

N/A

N/A

N/A

N/A

Pryout Strength**

12000

20822

58

OK

Concrete edge failure in direction y-**

12000

26313

46

OK

* anchor having the highest loading

**anchor group (relevant anchors)

4.1 Steel Strength


Vsa
= n Ase,V futa
f Vsteel Vua

ACI 318-08 Eq. (D-19)


ACI 318-08 Eq. (D-2)

Variables
n
1

Ase,V [in.2]
0.44

futa [psi]
65000

fsteel
0.650

f Vsa [lb]
18674

Calculations
Vsa [lb]
28730
Results
Vsa [lb]
28730

Vua [lb]
2000

4.2 Pryout Strength


Vcpg

= kcp

[(AA ) y
Nc

ec,N

Nc0

yed,N yc,N ycp,N Nb

ACI 318-08 Eq. (D-31)

f Vcpg Vua
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef
1
2 e'N 1.0
yec,N =
1+
3 hef
ca,min
=
0.7
+
0.3
1.0
yed,N
1.5hef
ca,min 1.5hef
1.0
ycp,N = MAX c , c
ac
ac
1.5
'
Nb
= kc l fc hef

)
)

ACI 318-08 Eq. (D-2)


ACI 318-08 Eq. (D-6)
ACI 318-08 Eq. (D-9)
ACI 318-08 Eq. (D-11)
ACI 318-08 Eq. (D-13)
ACI 318-08 Eq. (D-7)

Variables
kcp
2

hef [in.]
6.250

ec1,N [in.]
0.000

ec2,N [in.]
0.000

ca,min [in.]
33.000

yc,N
1.000

cac [in.]
-

kc
24

l
1

f'c [psi]
2500

ANc0 [in.2]
351.56

yec1,N
1.000

yec2,N
1.000

yed,N
1.000

ycp,N
1.000

fconcrete
0.700

fseismic
0.750

fnonductile
0.400

f Vcpg [lb]
20822

Vua [lb]
12000

Calculations
ANc [in.2]
929.56
Results
Vcpg [lb]
99153

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Nb [lb]
18750

Profis Anchor 2.4.8

www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

5
12/9/2014

4.3 Concrete edge failure in direction yVcbg

(AA ) y
Vc

ec,V

Vc0

yed,V yc,V yh,V yparallel,V Vb

ACI 318-08 Eq. (D-22)

f Vcbg Vua
AVc see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
AVc0 = 4.5 c2a1
1
2e'v
1.0
yec,V =
1+
3ca1
ca2
1.0
yed,V = 0.7 + 0.3 1.5c
a1
1.5ca1
1.0
yh,V =
ha
0.2
l
1.5
Vb
= 8 e
da l f'c ca1
da

(( )

ACI 318-08 Eq. (D-2)


ACI 318-08 Eq. (D-23)
ACI 318-08 Eq. (D-26)
ACI 318-08 Eq. (D-28)
ACI 318-08 Eq. (D-29)
ACI 318-08 Eq. (D-25)

Variables
ca1 [in.]
49.000

ca2 [in.]
-

ecV [in.]
0.000

yc,V
1.000

ha [in.]
8.000

le [in.]
6.000

l
1.000

da [in.]
0.750

f'c [psi]
2500

yparallel,V
2.000

AVc0 [in.2]
10804.50

yec,V
1.000

yed,V
1.000

yh,V
3.031

Vb [lb]
180095

fconcrete
0.700

fseismic
0.750

fnonductile
0.400

f Vcbg [lb]
26313

Vua [lb]
12000

Calculations
AVc [in.2]
1240.00
Results
Vcbg [lb]
125299

5 Combined tension and shear loads


bN
0.718
z

bV
0.576

z
5/3

Utilization bN,V [%]


98

Status
OK

bNV = bN + bV <= 1

6 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!
Condition A applies when supplementary reinforcement is used. The factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-08 Appendix D, Part D.3.3.4
that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, Part
D.3.3.5 requires that the attachment that the anchor is connecting to the structure shall be designed so that the attachment will undergo
ductile yielding at a load level corresponding to anchor forces no greater than the controlling design strength. In lieu of D.3.3.4 and D.3.3.5,
the minimum design strength of the anchors shall be multiplied by a reduction factor per D.3.3.6.
An alternative anchor design approach to ACI 318-08, Part D.3.3 is given in IBC 2009, Section 1908.1.9. This approach contains
"Exceptions" that may be applied in lieu of D.3.3 for applications involving "non-structural components" as defined in ASCE 7, Section
13.4.2.
An alternative anchor design approach to ACI 318-08, Part D.3.3 is given in IBC 2009, Section 1908.1.9. This approach contains
"Exceptions" that may be applied in lieu of D.3.3 for applications involving "wall out-of-plane forces" as defined in ASCE 7, Equation 12.11-1
or Equation 12.14-10.
It is the responsibility of the user when inputting values for brittle reduction factors (fnonductile) different than those noted in ACI 318-08, Part
D.3.3.6 to determine if they are consistent with the design provisions of ACI 318-08, ASCE 7 and the governing building code.
Selection of fnonductile = 1.0 as a means of satisfying ACI 318-08, Part D.3.3.5 assumes the user has designed the attachment that the anchor
is connecting to undergo ductile yielding at a force level <= the design strengths calculated per ACI 318-08, Part D.3.3.3.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.4.8

www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
12/9/2014

Profis Anchor 2.4.8

www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

12/9/2014

7 Installation data
Anchor plate, steel: Profile: S shape (AISC); 3.000 x 2.330 x 0.170 x 0.260 in.
Hole diameter in the fixture: df = 0.813 in.
Plate thickness (input): 0.750 in.
Recommended plate thickness: not calculated
Cleaning: No cleaning of the drilled hole is required

Anchor type and diameter: AWS D1.1 GR. B 3/4


Installation torque: -0.009 in.lb
Hole diameter in the base material: - in.
Hole depth in the base material: 6.250 in.
Minimum thickness of the base material: 8.125 in.

6.000

2.500

6.000

8.000

10.500

2.500

10.500

8.000

2.000

8.000

2.000

Coordinates Anchor in.


Anchor
1
2
3

x
4.000
4.000
4.000

y
-8.000
0.000
8.000

c-x
-

c+x
-

c-y
33.000
41.000
49.000

c+y
-

Anchor
x
4
-4.000
5
-4.000
6
-4.000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

y
-8.000
0.000
8.000

c-x
-

c+x
-

c-y
33.000
41.000
49.000

c+y
-

Profis Anchor 2.4.8

www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

8
12/9/2014

8 Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan