Sump Design

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

ET

1 of 2

DESIGN OF SUMP (50 bedded Gov. Hospital Upgradation, Allur, Nellore)


1 SUMP( R.C.C)
Size of sump : 6x 3.4 x 1M depth + 0.3M Free Board
Data:
Length
5.975
m
Bredth
3.8
m
Depth
1
m
Free Board
0.3
m
Assumed thickness of Base Slab
0.25
m
0.125
m
Assumed thickness of cover Slab
Assumed Side Wall thickness
0.15
m
2
Concrete grade
30
N/mm
2
Grade of Steel
500
N/mm
3
Unit weight of water
9.81
Kn/m
Unit weight of soil
18
Kn/m3
Unit weight of Concrete
25
Kn/m3
Projection of base slab
Y
0.25
m
Pipes & other fixtures Load
100
Kn
SBC
85
KN/m2
Edge coefficient
0.1
Clear cover for Wall
0.025
m
Area of Bottom Slab
27.8425
Sqm
10
mm
Dia of Bars for Base Slab
Dia of Bars for Side walls
10
mm
a)

i)

Design of Bottom slab( Using uncracked theory)


Load transformed to Foundation
Load from water (L x B x H x Unit Weight of water )
Self weight of Side Wall ( L x H x Thick x Unit wt of
Concrete)
Weight of cover slab (L+Y)X(B+Y) X Depth x (Unit
Weight of Concrete)
Weight of base slab (L+Y)X(B+Y) X Depth x (Unit Weight
of Concrete)
Pipes & other fixtures
Total
Pressure on soil
When tank is Empty
Up ward pressure on base slab
As a two way slab

222.73605
114.3675
70.953125
170.2875
100
678.344175
24.36362

KN
KN/m2

10.248

KN/M2

ly/lx

1.51

69.185
SAFE

Two way

Bending Moment Coefficient from table 22 of IS 456

14.11596
Positive
(P)

*****

Enter the value from table 26 of IS 456


Mx ( + Ve)= P x W x (Lx)2
2

*****
*****

*****

Mx ( - Ve)= N x W x (Lx)
K=Effective depth( d') /Total depth(d)
As per uncracked theory

overall thickness
Provided thickness
Effective depth Provided
Area of Steel Required
Spacing required
Provided Spacing
Check for minimum reinforcement for base slab
Percentage of steel coefficients
Required minimum area of steel

Negative ( N)

0.1
0.1

14.12

0.056
3.95

22.02

KN-M

0.056

14.12

3.95

12.33

KN-M

270.95
mm

mm

0.90
2

M/bD

=
=
=
=
=
=

0.25
250
6.75
675.08
116.28
125

0.12
=
=

3.00
300.00

0.3
22.02 x 1000 x 1000
0.3 x 1000
=
m
or
250
mm
250
cm2
mm2
c/c

Unsafe

cm2
mm2

Safe

900

0.28832

ET

b)

Design of side wall


Ratio Breadth(b)/Depth ( a)

2 of 2

3.8
1

3.80

Asper Is 3370 part IV


Mx ( + Ve)= P x W x (Lx)2
Mx ( - Ve)= N x W x (Lx)

0.1
0.014

9.81

0.1
1

0.14

KN-M

0.126

9.81

1.24

KN-M

0.1
My ( + Ve)= P x W x (Lx)2
My ( - Ve)= N x W x (Lx)2
K=Effective depth( d') /Total depth(d)
As per uncracked theory

0.1

0.025

9.81

0.25

KN-M

0.092
=
M/bD2

9.81

0.90

KN-M

=
=
=

64.19
120.00
150

mm
mm
mm

0.98
=

0.3
1.24 x 1000 x 1000
0.3 x 1000
<

overall thickness
effective depth provided
Provide overal Thickness
Area of Steel Required

63.14
63.14
1243.17
200

mm2
mm
c/c

180.00

mm2

=
=

0.59
5.7879

w x a2
Kn

=
=
=

Spacing required
Provided Spacing
Check for minimum reinforcement
Percentage of steel coefficients
Required minimum steel

0.12

Provide 10mm @175c/c


Check for tension on wall
From Table 8 of 3370-Part IV
Wall coefficient
Tension on wall
Permissible tensile stress
Ast

=
=

150 N/mm2
38.586 mm2

0.0109
Safe

You might also like