Hirel UPS Operation
Hirel UPS Operation
(3) Then, inside the same menu goto the option Transfer Load to : Inverter. To
transfer the Load to
Alternate supply, select Transfer Load to : Alt.
(4) In control keypads PCB, put the bottom most DIP switch back to its original
position.
Nominal Voltage of each cell = 1.2 V DC
Total no. of cells in CDCP UPS = 275
Charging voltage of each cell should be = 1.4 V DC
So, charging voltage of total 275 cells of CDCP UPS = 275 x 1.4 = 385 V DC
Also, specific gravity of each cells electrolyte should be approx 1.20
And, level of electrolyte should be between Maximum and Minimum levels marked.
If the level falls below Minimum, then top up with Demineralised water to bring the
level between the Maximum and Minimum levels.
The power changes over from Inverter to Auxiliary automatically when the battery is
discharged up to 1.1 V DC per cell. The float charging current in CDCP is approx.
40A in stable condition when battery is discharged.