Crompton Greaves Limited

Switchgear Division : Power Systems


A-3 MIDC, Ambad, Nashik- 422 010, Maharashtra, India
T: +91 253 238 2271 F: + 91 253 238 1247
Customer :-GODREJ & BOYCE MFG CO.LTD.
Rated C.T. Ratio: 600-300/5+5
STC Rating :25KA/3SEC.
Rated output/class : 2.5/0.5, 15/5P10 ISF< 2.5
Secondary terminal on P1 side

CODE NO.:V6121ACT
HSV/Insulation Level : 12/28/75 kvp
Work Order no: V6121A-800
IS-2705/1992
Freq. 50 Hz.
Frame Size: HCTT3

1.Accuracy
. ccu acy Test:
est:

600/5+5A
Rated
Burden
CT
Sr. no.

151209

151210

151211

151212

151213

VA
PF

2.5VA
0.8

Primary Ratio
Current% Error %
20
120
100

0 03
-0.03
0.03
0.13

300/5+5A
0VA
1

Phase
Error
(min)
66.8
8
1.5
2.05

Ratio
Error %

2.5VA
0.8

Phase
Error
(min)

00.21
21

66.8
8

0.22

4.1

20
120
100

Composite Error (%): 0.31


0.06
4.3
0.23
0.11
3.1
0.24
0.18
1.75

20
120
100

Composite Error (%): 0.34


0.08
3.8
0.24
0.14
3.3
0.23
0.06
6.46

20
120
100

Composite Error (%): 0.40


-0.078
5.99
0.16
0.04
1.85
0.19
0.12
2.47

5.99
3.46

20
120
100

Composite Error (%): 0.82


-0.098
5.92
0.14
0.042
2.25
0.18
0.032
2.93

6.74
3.71

4.3
3

4.3
3.2

Ratio
Error %
0 36
-0.36
-0.09
0.14

0VA
1

Phase
Error
(min)

Ratio
Error %

88.9
9
1.44
3.01

Phase
Error
(min)

00.34
34
0.39

12
8.2

2.2

Composite Error (%): 0.78


-0.25
8.7
0.35
-0.06
0.7
0.42
0.21
3.3

10
9

Composite Error(%): 1.2


-0.33
8.7
-0.1
2.1
0.009
4.77

10
8

0.34
0.4

2.4

2.2

Composite Error(%): 0.98


-0.6
12.55
0.15
-0.19
1
0.27
0.064
3.8

18.52
9.16

Composite Error (%): 1.64


-0.67
13.72
0.15
-0.207
2.38
0.26
-0.16
4.73

16.7
9.84

3.2

Composite Error (%): 0.57


0 57
Composite Error(%): 1.14
1 14
20
-0.13
9.58
0.11
18.21
-0.64
17.53
0.24
24.42
120
0.02
2.82
0.13
12.48
-0.49
11.12
0.3
14.07
151214
100
0.16
2.64
0.13
3.18
Composite Error (%): 0.26
Composite Error (%): 1.5
2. Over voltage inter turn Test. :3. Polarity Test :
4. HV Power frequency Test 4.1 Primary to Secondary, frame & earth 28KV for one minute
4.2 Secondary to frame & earth 3 KV for one minute
Test Room Temperature : 230C
Date of test
09.01.2015

Tested By

PD
Value
@
7.62kV

Approved By

2.8

2.9
OK
OK
OK
OK