Section 4

Protection functions

1MRS757644 B

When the reset period is initiated, the time for which START has been active is
saved. If the fault reoccurs, that is, the negative-sequence current rises above the
set value during the reset period, the operate calculations are continued using the
saved values. If the reset period elapses without a fault being detected, the operate
timer is reset and the saved values of start time and integration are cleared.

Inv. curve B
The inverse time equation for curve type B is:
t [ s] =

k
2

I2 IS

Ir Ir

GUID-805DCB50-71D2-4721-830B-3343E1A5500B V1 EN

(Equation 68)

t[s] Operate time in seconds

620 series
Technical Manual

Machine time Mult

I2

Negative-sequence current

IS

Set Start value

Ir

Set Rated current

441