De = (5 5 8) 1/3 = 5.848m
r = 0.635 10-2m, so that
De/r = (5.848 2 102)/0.635 = 1841.9
and In(De/r) = 7.52.
Hence, we have, for each kilometer of length,
L = 2(1/4 + 7.52) 10-7 103= 1.554 mH/km
The inductive reactance per kilometer is then
XL = L = 377 1.554 10-3= 0.5858
where = yz,
is known as the propagation constant
y is the shunt. admittance per unit length of the
line, and
z is the series impedance per unit length,
Essential Formula
cos = power factor (p.f.)
Ohms law : V = I x Z
Percent Regulation = (Vno load Vload )/ Vno
load
x 100
Essential Formulas
per-phase voltage : Vs= V/ 3
Ohms law : V = I x R ; P = I x V
Percent Regulation = (Vno load Vload )/ Vno load
x 100
VR = 1805V
(b) we have
I = (3.75 105)/1905 = 207.75A
Essential Formulas:
impedance magnitude: Z 2= R2 + X2
per-phase voltage :
Vs= V/ 3
Ohms law : V = I x R ; P = I x V
VS = VR + I(R + jX)
I = IR + ICR
On a per-phase basis,
VR = 6351V
VS = (1 + 0.05)(6351) = 6668.6V
Z = [(0.3) 2 + (0.4) 2] = 0.5
Pmax = (6351/0.5) 2(0.5 6668.6 / 6351 0.3)
= 36.3MW/phase
and the maximum total power that can be
transmitted is 3 36.3 = 108.9MW
Essential Formulas:
per-phase voltage : Vs= V/ 3
Ohms law : V = I x R ; P = I x V
VS = VR + I(R + jX)
I = IR + ICR
I = I R + I CR = 298.37<-25.8 + 34.57<90
= 285 -29.5A
R + jXL = 2.07 + j377 0.3108 117.19
88.98 10-6
I(R + jXL) = 285<-19.5 117.19 88.98 =
33.4 69.48kV
VS = VR + I(R + jXL) = 124.13<0 +
33.4<69.48
= 139.39 12.97kV/phase
A = D = (1 + YZ)
= 1 + j[(4 10 -4)/2](10 + j20)
= 0.996<0.115
B = Z(1 + YZ)
= (10 + j20)[1 + (j4 10 -4)(10 + j20)]
= 22.25<63.45W
C = Y = j4 10 -4 = 4 10 -4<90S
Example: