Professional Documents
Culture Documents
Basic Cycle Analysis: Point Enthalpy, H (KJ/KG) Pressure, P (Kpa) Entropy, S (KJ/KG.K) Temperature, T (C) 1 2 3 4 5 6
Basic Cycle Analysis: Point Enthalpy, H (KJ/KG) Pressure, P (Kpa) Entropy, S (KJ/KG.K) Temperature, T (C) 1 2 3 4 5 6
Based on the general observations, the volumetric flow rate of water through the cooler is assumed to
be 150 L/ hour . The temperature of water available to the cooler is assumed to be 30O C whereas
the temperature of the water coming out of the cooler is assumed to be 10o C . The evaporator
temperature is taken to be 5o C with a degree of superheat of 3o C . The condenser temperature is
assumed to be 40 o C . Based on the above assumptions, the following T-s and P-h plots have been
drawn for an ideal vapor compression cycle.
The important properties evaluated at various points are:
Point
Enthalpy, h
(kJ/kg)
Pressure, P (kPa)
Entropy, s
(kJ/kg.K)
Temperature, T
(oC)
253.3
349.9
0.9288
256.1
349.9
0.9386
278.6
1017
0.9386
46.57
271.3
1017
0.9154
40
108.3
1017
0.3949
40
108.3
349.9
0.4072
T-s plot