Professional Documents
Culture Documents
02 SEP671 REL670 Exercise 1 Distance Protection Characteristics
02 SEP671 REL670 Exercise 1 Distance Protection Characteristics
Copyright
This document and parts thereof must not be reproduced or copied without
written permission from ABB, and the contents thereof must not be imparted to
a third party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a
license and may be used, copied, or disclosed only in accordance with the terms
of such license.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
ABB AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
Page 1
Page 2
B
Z1L = R1L + j X1L
Z0L = R0L + j X0L
3I
3U
Entity
Line length
Nominal Voltage Level
Line Positive Sequence Impedance, Z1L = R1L + j X1L
Line Zero Sequence Impedance Z0L = R0L + j X0L
CT A ratio
VT A ratio
Maximum Power Transfer over the line
Value
100 km
400 kV
(0,032 + j 0,36) km
(3,2 + j 36)
(0,13 + j 1,45) km (13 + j 145)
1200 A / 1 A
Start point earthed towards the line
400 kV / 100 V
S = 700 MVA
P = 628 MW
Q = 308 Mvar
Cosphi = 0.89
Page 3
Page 4
Page 5
Page 6
Page 7
Calculating the settings for five zones distance protection, polygonal characteristic
The settings for the distance protection will be calculated in order to meet the requirements indicated in Table 2.
Table 2: Setting requirements for distance protection zones
Zone
Zone 1
Zone 2
Zone 3
Requirement
85% of the protected line
Forward direction
Instantaneous operate time
Fault resistance to be covered at 80% of the line, radial feeder:
Phase-Earth faults: 25 primary ohms
Phase-Phase faults: 15 primary ohms
At least 120% of the protected line
Forward direction
Operate time 400 ms
Fault resistance settings: 50% more than settings for zone1
Remote back-up zone
400% of the protected line
Forward direction
Operate time 1 s
Zone 4
Zone 5
Load Encroachment
Page 8
Distance protection zones will not trip for exporting load equal or
smaller 700 MVA and for any cosphi between 1,00 than 0,89
(3,2 + j 36)
(13 + j 145)
RFPP
15
and RFPE
25
Page 9
1,5 15
22,5
23
1,5 25 37,5
38
and
Page 10
X1
400% ( X 1L)
4 36 144
It is meaningless to set the resistive value of zone3 to 400% of the protected line resistance, as this is a back-up
zone, protecting several objects after the line. It is chosen to have a characteristic angle of almost 90 degrees
hence the resistive value will be set to the small value of 1 ohm:
R1 1,00
X0
400% ( X 0 L)
4 145 580
As well as for the resistive value of the zero sequence impedance, it is chosen to set it to a small value in order
to get a characteristic angle of 90 degrees:
R0 1,00
RFPP
300
and RFPE
300
Page 11
RFPP
40
and RFPE
60
Page 12
1,3 23
29,9
30
1,3 38 49,4
49
and
Page 13
Figure 15: Impedance settings for phase selection to cover zone 2 and zone 5
Page 14
Figure 16: Partial Impedance settings for phase selection to cover zone 2 and zone 5
Page 15
Z load min
80%
2
U LL
min
S MAX
0,9 400 kV
700 MVA
0,8
148,11
Angleload max
tan
Q
P
tan
308 Mvar
628 MW
26,12
132,99
130
Figure 17: Final Impedance settings for phase selection including load encroachment
Page 16
Page 17
AIM2 CH7
AIM2 CH8
AIM2 CH9
AIM2 N
CURRENT OUTPUT A1
CURRENT OUPUT A2
CURRENT OUTPUT A3
CURRENT OUTPUT N
AIM2 CH1
AIM2 CH2
AIM2 CH3
AIM2 N
Connect also the trip contact from the REL670 to the binary input 1 of the test set:
IOM OUPUT 1
15. Open the Omicron test file for LE faults and run the tests for zones 1, 2,3 and 4
The test file is called
REL670 LE Zones1,2,3 and 4 Characteristic.adt
and it contains the characteristic shape of the
REL670 for phase-earth faults and for all the
zones, except for zone 5, according to the
calculated settings.
The file is available in the folder
Files for SEP-602A REL670 / OMICRON TESTS
on the desktop of your training PC.
Page 18
16. Open the Omicron test file for LL faults and run the tests for zones 1, 2,3 and 4
The test file is called
REL670 LL Zones1,2,3 and 4 Characteristic.adt
and it contains the characteristic shape of the
REL670 for phase-earth faults and for all the
zones, except for zone 5, according to the
calculated settings.
The file is available in the folder
Files for SEP-602A REL670 / OMICRON TESTS
on the desktop of your training PC.
17. Open the Omicron test file for LLL faults and run the tests for zones 1, 2,3 and 4
The test file is called
REL670 LLL Zones1,2,3 and 4 Characteristic.adt
and it contains the characteristic shape of the
REL670 for three-phase faults and for all the
zones, except for zone 5, according to the
calculated settings.
The file is available in the folder
Files for SEP-602A REL670 / OMICRON TESTS
on the desktop of your training PC.
Page 19
19. Open the Omicron test file for LE faults and run the tests for zone 5
The test file is called
REL670 LE Zone 5 Characteristic.adt
and it contains the characteristic shape of the
REL670 for phase-earth faults for zone 5,
according to the calculated settings.
The file is available in the folder
Files for SEP-602A REL670 / OMICRON
TESTS
on the desktop of your training PC.
Page 20
20. Open the Omicron test file for LL faults and run the tests for zone 5
The test file is called
REL670 LL Zone 5 Characteristic.adt
and it contains the characteristic shape of the
REL670 for phase-phase faults for zone 5,
according to the calculated settings.
The file is available in the folder
Files for SEP-602A REL670 / OMICRON TESTS
on the desktop of your training PC.
21. Open the Omicron test file for LLL faults and run the tests for zone 5
The test file is called
REL670 LLL Zone 5 Characteristic.adt
and it contains the characteristic shape of the
REL670 for 3-phase faults for zone 5, according
to the calculated settings.
The file is available in the folder
Files for SEP-602A REL670 / OMICRON TESTS
on the desktop of your training PC.
Page 21