Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 3

DC Motor trial operating checking list

MOTOR NO LOAD RUN TEST SHEET

Date:

Name of equipment

KKS Code

Kilo Watt

Armature Voltage

Field Voltage

Armature Current

Field Current

Duty

Type of connection

10

Degree of protection

11

Insulation class

12

Frame

14

Sr. No.

15

Make

CHECKING LIST:S.No.
1
2
3
4
5
6
7

8
9

Activity Description

Remarks

Result

Proper approach and house keeping


Ensure no PTW is pending on the
equipment
Ensure no person is working on the
equipment
Ensure Equipment is not running
Motor is coupled/ decoupled
Availability of Main power supply and
control supply
Type of mounting: Foot/Flange and
motor foundation bolts are tightened
properly and no damage to motor base
legs
Check no damage to the terminal box
and insulated terminal block
Ensure double Earthing of motor done
1

and LCS also double earthed


10

Measure the individual winding resistance


(Armature and Field Winding )
A1-A2:
F1-F2:

11

Measure the insulation resistance (with 500V


insulation tester) of each winding.
All the readings shall be > 5Mohms. If the IR
value is low switch on the space heater or by
external heating
A-E: F-E: A-F:

12

Ensure all logics and protections are in


service
Remove permit and DO NOT
OPERATE board from the feeder.

13

14

15

Put LOCAL/OFF/REMOTE selector


switch in LOCAL or REMOTE position.
As per operation requirement
Rack in the breaker/ Feeder

16

Switch ON control power MCB

17

Ensure OFF indication on feeder is


glowing
Give Clearance for Switch ON the
feeder from DCS/LCS and verify the
DOR.
Check the current of the equipment
Check the vibration, noise or any other
abnormality
Check the heating/temperature of the
motor and record in enclosed test sheet

18

19
20
21
22

Check / Confirm the spring tension and


condition of brushes.

LOAD RUN FOR _________Hrs


Stating Current :
Starting Time
S.No

Time

Voltage

Current (Amps)

P-N

P-N

Remarks

TEMPARATURE MEASUREMENT:S. No

Time

Motor body

Bearing Temp
DE

Winding
temperature

Remarks

NDE

VIBRATION MEASUREMENT:S. No

Time

Permissible Value
(mm/sec)

Vibration value
measured (mm/sec)
V

Remarks

REMARKS : Entry of unauthorized person should be prohibited and caution board should be
placed.

Witnessed By

KSK Engineer

KPS Engineer

You might also like