NETCONNECT SL Series Jacks and Category 6 Plugs: Product Specification
NETCONNECT SL Series Jacks and Category 6 Plugs: Product Specification
Specification
108-1990
11Mar11 Rev K
SCOPE
1.1.
Content
This specification covers perform ance, test and quality requirem ents for NETCONNECT* Category 3,
Category 5e and Category 6 SL Series unshielded 110 jacks, Category 5e and Category 6 SL Series
shielded 110 jacks and plugs. These assem blies are designed for installation into various outlet plates,
surface m ount boxes, panels, and other sim ilar type fittings. Jacks incorporate IDC term inals for
term inating both shielded or unshielded twisted pair com m unications cable. Jacks will accom m odate 22
- 24 AW G solid and 24 - 26 AW G stranded conductors. The m axim um conductor insulation diam eter is
1.45 m m [.057 in]. For large OD conductors 1.27 to 1.45 m m an external strain relief m ust be used. The
plugs accom m odate Category 6 cable and shielded or unshielded twisted pair cable with 23 - 24 AW G
solid, or 24 - 26 AW G stranded conductors. The m axim um conductor insulation diam eter is 1.00 m m
[.039 in] with a cable jacket diam eter between 4.7 and 7.0 m m [.185 and .276 in].
1.2.
Qualification
W hen tests are perform ed on the subject product line, procedures specified in Figure 1 shall be used.
All inspections shall be perform ed using the applicable inspection plan and product drawing.
1.3.
Successful qualification testing on the subject product line was com pleted on 01Nov02. The
Qualification Test Report num ber for this testing is 501-553. This docum entation is on file at and
available from Engineering Practices and Standards (EPS).
2.
2.1.
2.2.
Industrial Standards
!
!
!
!
!
1 of 8
LOC B
108-1990
2.3.
3.
REQUIREM ENTS
3.1.
3.2.
Materials
Materials used in the construction of this product shall be as specified on the applicable custom er
drawing.
3.3.
Ratings
!
!
3.4.
3.5.
Requirem ent
Meets requirem ents of product
drawing.
Procedure
Visual, dim ensional and functional
per applicable quality inspection
plan.
ELECTRICAL
Contact resistance.
R 20 m illiohm s m axim um .
IEC 60512-2-1.
Subject m ated plug and term inated
jack to 20 m illivolts m axim um open
circuit voltage at 100 m illiam peres
m axim um .
See Figure 3.
Insulation resistance.
IEC 60512-3-1.
Test voltage of 100 volts DC with 1
m inute hold. Test between adjacent
contacts of m ated plug and
term inated jack.
Figure 1 (continued)
Rev K
2 of 8
108-1990
Test Description
Voltage proof.
Requirem ent
Procedure
No discontinuities of 1 m icrosecond
m axim um .
Shall rem ain m ated and show no
evidence of physical dam age.
See Note.
IEC 60512-6-4.
Subject m ated plug and term inated
jack to frequency range of 10 to 55
Hz with displacem ent am plitude of
.014 inch. Sweep cycles per
direction shall be 5 in each direction
of 3 axis which are m utually
perpendicular planes.
No discontinuities of 5
m icroseconds m axim um .
See Note.
IEC 60512-6-3.
Subject m ated plug and term inated
jack to 30 G's half-sine shock wave
of 11 m illiseconds duration. Three
shocks in each direction (2 total)
applied along 3 m utually
perpendicular planes (3 axis), 18
total shocks.
IEC 60512-9-1.
Mate and unm ate plug and jack
interface with latch inoperative for
200 cycles with a 6 position plug at
a m axim um rate of 500 (autom atic)
or 300 (m anual) cycles per hour.
See Note.
IEC 60512-9-1.
Mate and unm ate plug and jack
interface with latch inoperative for
750 cycles at a m axim um rate of
500 (autom atic) or 300 (m anual)
cycles per hour.
IEC 60512-13-1.
Measure force required to m ate
plug and jack with latch depressed
at a m axim um rate of .5 inch per
m inute.
IEC 60512-13-1.
Measure force required to unm ate
plug and jack with latch depressed
at a m axim um rate of .5 inch per
m inute.
EIA 364-98.
Apply an axial load of 20 pounds to
plug housing at a rate of .5 inch per
m inute with plug m ated in jack and
latch engaged. Maintain load for 5
seconds.
Figure 1 (continued)
Rev K
3 of 8
108-1990
Test Description
Requirem ent
Procedure
W ire Size
AW G
22 Solid
23 Solid
24 Solid
24 Stranded
26 Stranded
Pounds
Minim um
14
12
9.5
7.5
4.6
EIA 364-8.
Determ ine slot tensile strength. Pull
parallel to term inated wire.
See Figure 4.
W ire Size
AW G
22 Solid
23 Solid
24 Solid
24 Stranded
26 Stranded
Pounds
Minim um
1.5
1
1
1.5
1.9
EIA 364-8.
Determ ine slot tensile strength. Pull
perpendicular to term inated wire.
See Figure 5.
See Note.
TIA/EIA 568-B.2.
Term inate and re-term inate IDCs
on jack for 200 cycles with 22 AW G
solid wire using im pact tool PN
569994-1 set on low im pact setting.
ENVIRONMENTAL
Therm al shock, IDC-wire interface.
See Note.
IEC 60068-2-14.
Subject m ated plug and term inated
jack to 100 cycles between -40 and
70C. Duration exposure shall be 30
m inutes with an average transition
rate of 3C per m inute.
See Note.
IEC 60512-11-9.
Subject m ated plug and term inated
jack to 25 cycles between 40 and
70C.
See Note.
IEC 60068-2-38.
Subject m ated plug and term inated
jack to 21 cycles (cycle tim e 24
hours) between 25 and 65C at
93% RH with a -10C sub-cycle
shock.
See Note.
IEC 60512-11-12.
Subject m ated plug and term inated
jack to 55C and 95% RH for 10
days.
See Note.
Figure 1 (continued)
Rev K
4 of 8
108-1990
Test Description
Mixed flowing gas, jack-plug
interface.
NOTE
3.6.
Requirem ent
Procedure
See Note.
Shall meet visual requirements, show no physical damage, and meet requirements of additional
tests as specified in the Product Qualification and Requalification Test Sequence shown in Figure
2.
Figure 1 (end)
Product Qualification and Requalification Test Sequence
Test Group (a)
Test or Examination
1,6
1,5
10
11
1,8
1,5
1,5
1,7
1,8
Contact resistance
2,4
2,6
2,7
Insulation resistance
1,4
1,5
1,5
2,4
2,4
1,5
2,5
2,7
3,6
Voltage proof
2,4
3(c)
NOTE
(a)
(b)
(c)
(d)
3
3(d)
Rev K
5 of 8
108-1990
4.
4.1.
Qualification Testing
A.
Specim en Selection
Plugs and jacks shall be prepared in accordance with applicable Instruction Sheet and shall be
selected at random from current production. Test groups 1, 2, 3, 4 and 5 shall each consist of 5
specim ens (plug and jack). If not specified, Category 6 plugs shall be used. Test groups 6, 7, 8, 9
and 10 shall each consist of 5 specim ens of each of the following subgroups: 1) SL Category 5e or
Category 6 jack and Category 6 plug; 2) SL Category 5e or Category 6 jack and high perform ance
plug; 3) SL Category 3 jack and 6 position plug. Test group 8, 6 position plug shall have no coring
where pins 1 and 8 are located in receiving jack, as shown in TIA-968-A Figure 6.3. Test group 11
shall consist of 5 specim ens of shielded jacks and plugs.
B.
Test Sequence
Qualification inspection shall be verified by testing specim ens as specified in Figure 2.
4.2.
Requalification Testing
If changes significantly affecting form , fit or function are m ade to the product or m anufacturing process
or controlling industry specification, product assurance shall coordinate requalification testing, consisting
of all or part of the original testing sequence as determ ined by developm ent/product, quality and
reliability engineering.
4.3.
Acceptance
Acceptance is based on verification that the product m eets the requirem ents of Figure 1. Failures
attributed to equipm ent, test setup or operator deficiencies shall not disqualify the product. If product
failure occurs, corrective action shall be taken and sam ples resubm itted for qualification. Testing to
confirm corrective action is required before resubm ittal.
4.4.
Rev K
6 of 8
108-1990
NOTE
(a)
(b)
Termination resistance of this assembly consists of plug to jack contact resistance plus
printed circuit board trace plus IDC terminal to discrete wire contact resistance. Printed circuit
board trace length varies with each jack position, therefore, significant variations in
termination resistance readings can be expected within each jack assembly.
Millivolt drop (resistance) due to wire lengths shall be subtracted from all readings.
Figure 3
Overall Term ination Resistance Measurem ent Points
Figure 4
Term ination Tensile Strength Horizontal Pull
Rev K
7 of 8
108-1990
Figure 5
Term ination Tensile Strength Vertical Pull
Rev K
8 of 8