Professional Documents
Culture Documents
Penn State University Fluids Lab Portfolio
Penn State University Fluids Lab Portfolio
Penn State University Fluids Lab Portfolio
Experiment
Turbine Speed and Horsepower
Operation of the Pelton wheel apparatus will involve adjusting the mass flow rate of the nozzle
jet stream for four open settings of the spear valve- 25, 50, 75 and 100 percent. At each setting
data will be recorded allowing for a computational analysis which will yield characteristic plots
for Braking Horsepower vs. Turbine Speed, Water Horsepower vs. Turbine Speed and Turbine
Efficiency vs. Turbine Speed.
10/24/2014
Joseph R. Felice
1
Introduction
The goal of this experiment is to operate the Pelton wheel in order to gather data related to its
function for calculations which will yield characteristic plots of braking/water horsepower, speed
and efficiency.
Graph 1 - Featured above is the characteristic plot of Braking Horsepower vs. Turbine Speed for the Pelton wheel apparatus.
Graph 2 - Featured above is the characteristic plot of Water Horsepower vs. Turbine Speed for the Pelton wheel apparatus.
Graph 3 - Featured above is the characteristic plot of Braking Horsepower vs. Turbine Speed for the Pelton wheel apparatus.
The braking and water horsepower were both at a maximum when the spear valve was adjusted
to a 100% setting. However, efficiency was at a maximum for each setting of the spear valve
for medium level turbine speeds.
Conclusion
Efficiency could be increased by maintaining a medium turbine speed. This is where the
maximum efficiency seemed to occur for spear setting during operation of the Pelton wheel.
Appendix
25%
Open
1
2
3
4
5
6
7
8
9
10
Turbine
Load
(lbf)
0.1063
0.4125
0.7313
0.9750
1.0750
1.2000
1.2823
1.3750
1.5063
1.8750
Turbine
Speed
(rpm)
Pressure
Head
(psig)
Flow
(ft3/min)
Volts
Amps
Motor
Speed
(rpm)
Motor
Load
(lbf)
1858
1608
1508
1316
1223
1140
1040
960
860
0
15
15
15
15
15
15
15
15
15
15
3.25
3.00
3.12
3.12
3.12
3.12
3.12
3.12
3.12
3.12
180
180
180
180
180
180
180
180
180
180
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
2127
2127
2127
2127
2127
2127
2127
2127
2127
2127
1.530
1.556
1.544
1.362
1.564
1.574
1.560
1.566
1.556
1.564
Table 2 - Above is the data collection for the Pelton wheel apparatus with the spear valve set at 25%.
50%
Open
1
2
3
4
5
6
7
8
9
10
Turbine
Load
(lbf)
0.0875
0.6500
1.1313
1.5188
1.8500
2.1188
2.5188
2.6875
2.8875
3.1000
Turbine
Speed
(rpm)
Pressure
Head
(psig)
Flow
(ft3/min)
Volts
Amps
Motor
Speed
(rpm)
Motor
Load
(lbf)
1909
1710
1530
1352
1170
1041
807
630
510
0
15
15
15
15
15
15
15
15
15
15
5.20
5.20
5.20
5.20
5.20
5.20
5.20
5.20
5.20
5.20
190
190
190
190
190
190
190
190
190
190
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
2290
2290
2290
2290
2290
2290
2290
2290
2290
2290
2.174
2.184
2.182
2.174
2.176
2.203
2.204
2.208
2.204
2.184
Table 2 - Above is the data collection for the Pelton wheel apparatus with the spear valve set at 50%.
75%
Open
1
2
3
4
5
6
7
8
9
10
Turbine
Load
(lbf)
0.0813
0.9125
1.5250
1.8688
2.5063
2.7500
3.1125
3.4188
3.5563
3.8438
Turbine
Speed
(rpm)
Pressure
Head
(psig)
Flow
(ft3/min)
Volts
Amps
Motor
Speed
(rpm)
Motor
Load
(lbf)
1942
1681
1502
1309
1142
1019
826
627
443
0
15
15
15
15
15
15
15
15
15
15
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
200
200
200
200
200
200
200
200
200
200
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
2460
2452
2445
2460
2457
2456
2459
2460
2457
2453
2.650
2.672
2.686
2.668
2.652
2.642
2.642
2.648
2.664
2.666
Table 3 - Above is the data collection for the Pelton wheel apparatus with the spear valve set at 75%.
100%
Open
1
2
3
4
5
6
7
8
9
10
Turbine
Load
(lbf)
0.1000
1.0875
1.6563
2.2438
2.7313
3.0875
3.4875
3.7375
3.9188
4.1063
Turbine
Speed
(rpm)
Pressure
Head
(psig)
Flow
(ft3/min)
Volts
Amps
Motor
Speed
(rpm)
Motor
Load
(lbf)
1935
1660
1499
1308
1121
996
803
629
490
0
15
15
15
15
15
15
15
15
15
15
7.20
7.20
7.20
7.20
7.20
7.20
7.20
7.20
7.20
7.20
210
210
210
210
210
210
210
210
210
210
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
2540
2541
2539
2539
2536
2539
2544
2543
2549
2551
2.924
2.926
2.928
2.906
2.918
2.922
2.924
2.934
2.952
2.946
Table 4 - Above is the data collection for the Pelton wheel apparatus with the spear valve set at 100%.
25% Open
Water
Horsepower
(WHP)
1
2
3
4
5
6
7
8
9
10
0.249532
0.249532
0.249532
0.249532
0.249532
0.249532
0.249532
0.249532
0.249532
0.249532
Turbine
Braking
Horsepower
(BHPT)
0.019733
0.066300
0.110220
0.128400
0.131400
0.136800
0.133180
0.131940
0.129400
0
Pump
Braking
Horsepower
(BHPP)
0.477401
0.477401
0.477401
0.477401
0.477401
0.477401
0.477401
0.477401
0.477401
0.477401
Pump
Efficiency
(P)
Turbine
Efficiency
(T)
0.522688
0.522688
0.522688
0.522688
0.522688
0.522688
0.522688
0.522688
0.522688
0.522688
0.079084
0.265698
0.441706
0.514564
0.526586
0.548226
0.533718
0.528750
0.518570
0
Table 5 - Above are computations based on the data collection from Table 1 used in generating the characteristic plots for
the Pelton wheel apparatus with the spear valve set at 25%.
50% Open
Water
Horsepower
(WHP)
1
2
3
4
5
6
7
8
9
10
0.430745
0.430745
0.430745
0.430745
0.430745
0.430745
0.430745
0.430745
0.430745
0.430745
Turbine
Braking
Horsepower
(BHPT)
0.01670
0.11110
0.17302
0.25200
0.21640
0.22047
0.20319
0.16924
0.14720
0
Pump
Braking
Horsepower
(BHPP)
0.73184
0.73184
0.73184
0.73184
0.73184
0.73184
0.73184
0.73184
0.73184
0.73184
Pump
Efficiency
(P)
Turbine
Efficiency
(T)
0.58858
0.58858
0.58858
0.58858
0.58858
0.58858
0.58858
0.58858
0.58858
0.58858
0.038770
0.257926
0.401676
0.476384
0.502386
0.511834
0.471718
0.392901
0.341734
0
Table 6 - Above are computations based on the data collection from Table 2 used in generating the characteristic plots for
the Pelton wheel apparatus with the spear valve set at 50%.
75% Open
Water
Horsepower
(WHP)
1
2
3
4
5
6
7
8
9
10
0.55476
0.55476
0.55476
0.55476
0.55476
0.55476
0.55476
0.55476
0.55476
0.55476
Turbine
Braking
Horsepower
(BHPT)
0.01578
0.15334
0.22900
0.24440
0.28600
0.28002
0.25700
0.21426
0.15748
0
Pump
Braking
Horsepower
(BHPP)
0.95324
0.95324
0.95324
0.95324
0.95324
0.95324
0.95324
0.95324
0.95324
0.95324
Pump
Efficiency
(P)
Turbine
Efficiency
(T)
0.58197
0.58197
0.58197
0.58197
0.58197
0.58197
0.58197
0.58197
0.58197
0.58197
0.02844
0.27640
0.41278
0.44056
0.51554
0.50476
0.46324
0.38622
0.28388
0
Table 7 - Above are computations based on the data collection from Table 3 used in generating the characteristic plots for
the Pelton wheel apparatus with the spear valve set at 75%.
100% Open
Water
Horsepower
(WHP)
1
2
3
4
5
6
7
8
9
10
0.62591
0.62591
0.62591
0.62591
0.62591
0.62591
0.62591
0.62591
0.62591
0.62591
Turbine
Braking
Horsepower
(BHPT)
0.01934
0.18046
0.24820
0.29340
0.30600
0.29920
0.27980
0.23500
0.19194
0
Pump
Braking
Horsepower
(BHPP)
1.08652
1.08652
1.08652
1.08652
1.08652
1.08652
1.08652
1.08652
1.08652
1.08652
Pump
Efficiency
(P)
Turbine
Efficiency
(T)
0.57607
0.57607
0.57607
0.57607
0.57607
0.57607
0.57607
0.57607
0.57607
0.57607
0.03090
0.28832
0.39654
0.46876
0.48888
0.47802
0.44702
0.37546
0.30666
0
Table 8 - Above are computations based on the data collection from Table 4 used in generating the characteristic plots for
the Pelton wheel apparatus with the spear valve set at 100%.
Table 9 - Above are measurements for the moment arms and pipe diameter for the Pelton wheel apparatus used in
computations for generating the characteristic plots.
Sample Calculations
Turbine Braking Horsepower @ 25%
[(6.3/12 feet)*(1858 rpm)*(1.7/16 lbs)*2*pi] /33000 = 0.01973 hp
Velocity @ 25%
Q = VA
[3.12 cubic feet/min]/60 = pi*[(9.2/12 feet)/2]2*V
V = 0.1126 ft/s
Water horsepower @ 25%
[[[15*144 lb/ft2]/[(1.94 slug/ft3)*(32.2 ft/square second)] + (0.1126 ft/s)2/[2*32.2
ft/s2]]*3.12/0.1337 gal/min*10]/33000 = 0.249532 hp
Turbine Efficiency @ 25%
0.019733 hp/0.249532 hp = 0.079084
References
[1] Summarized from ME 308 Lecture Notes, Fall 2014, Pelton Experiment Description, Slides
1-3. Pennsylvania State University, Angel Course Webpage.
2014
Joseph R. Felice
Pennsylvania State University
11/21/2014
1
Objective:
The purpose of this laboratory is for the student to be familiarized with the refrigeration cycle.
Following operation of the Hampden H6710 Refrigerator Demonstration Unit thermodynamic
analysis of the collected data will be conducted. Data analysis will include a temperature vs.
specific entropy plot (a.k.a. TS diagram) of the R134a refrigerant accompanied by a series of
calculations.
Introduction:
Essentially, the second law of thermodynamics states that heat exchange from a cold
temperature body to a high temperature body in the absence of work [2]. Heat transfer from
high temperature objects to low temperature objects occurs as a natural phenomenon, thus
requiring no work. Therefore, in order to generate the work needed for heat transfer to occur
in the opposite flow as aforementioned in the second law of thermodynamics a special
apparatus known as a refrigerator is required [3].
A refrigerator consists of four elements which are a compressor, condenser, expansion valve
and evaporator. Refrigerant is the term for the fluid used in this reverse flow process. The
efficiency of this process is measured by the coefficient of performance. Represented as COPR,
efficiency of the refrigeration cycle is established as a ratio of desired output to required input.
Unlike thermal efficiency, values for COPR can be higher than one [3]. The principles of the
refrigeration cycle that are demonstrated by the Hampden H6710 Refrigerator Demonstration
Unit are representative of the second law of thermodynamics.
Experimental Procedure:
1. Turn on the circulator pump to begin the refrigeration cycle process.
2. Turn on the circuit breaker for the compressor.
3. Open the valve at the condenser inlet.
4. Turn on the circuit breaker for the heater.
5. Adjust the heater setting around 20 F higher than the temperature of the tank water.
6. Before you start the experiment make note of the initial KW measurement for the
compressor unit.
7. Let the Hampden H6710 operate. During operation take down values for the
temperature and pressure at each of the thermocouple locations.
8. Operate the Hampden H6710 for 45 minutes before shutting the unit down.
Discussion/Results:
F
igure 2 - Above is a plot of Temperature vs. Specific Entropy for the Hampden Refrigeration Unit. Plotted are the curves for
the experimental data enveloped by minus and plus error readings.*
The above graph shown in Figure 2 was generated using the experimental data from the
operation of the Hampden Refrigeration Trainer Unit. Slight modifications were made to the
entropy values recorded before the evaporator at 41 psig when the temperature of the
refrigerant read 44 F. Initially, as shown in Table 8 in the Appendix, the entropy before
entering the evaporator was 0.0565 BTU/lb-R. Obviously, this cannot be the case since that
would be a loss of entropy through the expansion valve. Given these are not ideal conditions,
friction exists. Thus, the refrigerant would gain entropy traveling through the expansion valve.
In order to adjust these values, the absolute pressure which was 55.7 psia along with the
enthalpy value of 37.1 BTU/lb calculated at the entrance of the thermal expansion value (TEV)
yielded the correct value for entropy at 0.0782 BTU/lb-R. The plot of the experimental data
was complemented by an envelope of minus and plus error taken into account for the
temperature and pressure gauge readings recorded during the experiment. Plus and minus five
psi in pressure and three degrees in temperature were the ranges used in generating the error
plots. The values for the entropy at the 41 psig and 44 F refrigerant were also adjusted
accordingly for the plus and minus error data plots.
*See Note on bottom of page 8 in Appendix.
A possible source of error in the data acquired during the experiment could rest in a faulty
circulator pump shown below in Figure 4. Observing the data in the charts contained in the
Appendix one will notice that the temperatures of the water in the tank and of the refrigerant
leaving the evaporator were almost the same at 67 F. This should not be the case. The
circulator pump serves to distribute the water tank temperature. Since the evaporator coil is
located inside the water tank shown below in Figure 3, the highest the temperature of the
refrigerant leaving the evaporator should be around 60 F.
Figure 3 - Above is the water tank. Inside this tank is the evaporator coil surrounded by water maintained at 67 F. Since the
refrigerant temperature departing the evaporator coil is the same temperature as the tank water it is believed the circulator
pump malfunctioned, Image courtesy of Pennsylvania State University.
Figure 4 - Shown above is an image of the circulator pump, the component of the Hampden believed to be faulty during the
experiment, Image courtesy of Pennsylvania State University.
A negative value for the energy balance of the compressor component makes perfect sense. In
order for the compressor to function work must go in allowing for it to be able to increase the
pressure of the refrigerant. Thus, the negative sign represents the appropriate sense for the
direction of work going into the compressor.
The energy balance for the condenser was calculated at
condenser
The energy balance for the thermal expansion valve (TEV) was calculated at
TEV
The reason why the energy balance for the expansion valve is zero is because the pressure drop
of the refrigerant which occurs through the TEV takes place at constant enthalpy. Although
there is no way of knowing for certain that this is exactly the case with the Hampden trainer
unit theoretically it is known this is the situation. Thus, the recorded data value for enthalpy
before entering the evaporator of 26.2 BTU/lbm (Appendix, Table 8) was adjusted to the
enthalpy value recorded for entrance into the TEV of 37.1 BTU/lbm (Appendix Table 7). This
yielded the theoretically correct value of 0 BTU/min for energy balance of the TEV.
The energy in vs. the energy out ratio was calculated at
Ein/Eout = [(114 BTU/lbm 26.2 BTU/lbm) + 7 BTU/lbm]/(121 BTU/lbm 37.8 BTU/lbm) = 1.139
In a perfect situation the energy in to energy out ratio should be a 1:1 ratio. However, since
there are frictional losses to be taken into consideration the formula
out
in
in
- Frictionlosses
must be taken into consideration. From this we can calculate the value of friction loss to be
11.6 BTU/lbm. Therefore, when this value is added to out, the ratio becomes 1:1 for the
energy in versus energy out of the refrigeration cycle for the Hampden.
For the carnot cycle:
The coefficient of performance based on the calculated enthalpies for the experimental data
was determined to be
COPC = [117 BTU/lbm 37.1 BTU/lbm]/[124 BTU/lbm 117 BTU/lbm] = 11.4
This coefficient of performance for the carnot cycle (COPC) makes sense since when compared
to the refrigerant COPR it is a higher value. The COPR was 9.6 and the COPC as seen directly
above is 11.4. Since the carnot cycle is an ideal condition that does not involve and frictional
losses, it is expected that its COP will be a higher value.
For the minus error plot data the COPC was calculated at
COPC = [115 BTU/lbm 36.8 BTU/lbm]/[123 BTU/lbm 115 BTU/lbm] = 9.8
Again this value makes perfect sense since it is lower than the refrigerant COPR calculated for
the minus error plot was 5.5, which is less due to losses in the system compared to the above
value of 9.8 for the COPC for the carnot cycle.
Appendix [5]
Water In
Property
Value
43 psi @ 66 F
114
0.229
Table 1 - Above is a table of the values for specific enthalpy and specific entropy for the water in at 43 psi at 66 F.
Water Out
Property
Value
14.7 psi @ 82 F
120
0.266
Table 2 - Above is a table of the values for specific enthalpy and specific entropy for the water out at 14.7 psi at 82 F.
Entering Compressor
Property
Value
38 psi @ 68 F
115
0.232
Table 3 - Above is a table of the values for specific enthalpy and specific entropy for the refrigerant entering the compressor
at 38 psi at 68 F.
Leaving Compressor
Property
Value
122
0.231
Table 4 - Above is a table of the values for specific enthalpy and specific entropy for the refrigerant leaving the compressor at
109 psi at 119 F.
Entering Condenser
Property
Value
121
0.228
Table 5 - Above is a table of the values for specific enthalpy and specific entropy for the refrigerant entering the condenser at
110 psi at 113 F.
Leaving Condenser
Property
Value
115 psi @ 79 F
37.8
0.0786
Table 6 - Above is a table of the values for specific enthalpy and specific entropy for refrigerant leaving the condenser at 115
psi at 79 F.
Property
Value
37.1
0.0773
Table 7 - Above is a table of the values for specific enthalpy and specific entropy for the refrigerant going through the
thermal expansion valve (TEV) at 110 psi at 77 F.
Before Evaporator
Property
Value
41 psi @ 44 F
26.2
0.0565
Table 8 - Above is a table of the values for specific enthalpy and specific entropy of the refrigerant before the evaporator at
41 psi at 44 F.
After Evaporator
Property
Value
38 psi @ 67 F
114
0.232
Table 9 - Above is a table of the values for specific enthalpy and specific entropy for the refrigerant after the evaporator at 38
psi at 67 F.
Property
Value
14.7 psi @ 67 F
117
0.26
Table 10 - Above is a table of the values for specific enthalpy and specific entropy of the water in the tank at 14.7 psi at 67 F.
*Note: Please see attached Excel file for plot and data points for plot shown in Figure 2.
References
[1] Hampden Engineering Corporation, Model #H-6710 Refrigeration Demonstrator. 2011,
Web, 20 November 2014, from <http://www.hampden.com/productdetails.php?viewid=996>.
[2] HyperPhysics, Second Law of Thermodynamics. 2014, Web, 16 November 2014, from
<http://hyperphysics.phy-astr.gsu.edu/hbase/thermo/seclaw.html#c1>.
[3] Cengel, Yunus A., 2008, Introduction to Thermodynamics and Heat Transfer, 2nd ed.,
McGraw- Hill, New York, NY, Chap. 7.
[4] The Engineering ToolBox. Water Properties. Web. 12 November 2014.
<http://www.engineeringtoolbox.com/water-properties-d_1258.html>.*
*Reference [4] was used to acquire the specific heat of water at an average temperature of 74
F. This average was acquired based on the temperature in, 66 F and the temperature out, 82
F.
[5] Fluid Property Calculator. IRC Fluid Property Calculator. 2014. Penn State Angel Website.
12 November 2014. < https://cms.psu.edu/>.
Joseph R. Felice
Pennsylvania State University
12/1/14
Operation of the Pelton wheel apparatus will involve adjusting the mass flow rate of the
nozzle jet stream for four open settings of the spear valve- 25, 50, 75 and 100 percent.
At each setting data will be recorded allowing for a computational analysis which will
yield characteristic plots for Braking Horsepower vs. Turbine Speed, Water Horsepower
vs. Turbine Speed and Turbine Efficiency vs. Turbine Speed.
Objective:
The purpose of this laboratory experiment is to operate the Rankine Cycler System in
order to conduct technical calculations regarding turbine efficiency.
Introduction:
The rankine cycle is the process of converting heat to work [2]. This particular
experiment will utilize the Rankine Cycler System with a data acquisition computer to
collect values for temperature, pressure, speed, voltage and current. After these data
points are collected they will be downloaded into an Excel file where plots will be
generated. After these plots are made they will serve to aid in calculations for turbine
efficiency.
Specifically, the plots for turbine inlet/outlet temperatures and pressures will be
analyzed for times when steady-state conditions occurred. Due to the absence of a
pump in this Rankine Cycler System genuine steady-state conditions cannot be
achieved. Therefore, times when conditions were as close to steady-state as possible
will be used for turbine efficiency calculations. Two different times will be selected to
determine if there is any variation in the efficiency during operation of the Rankine
Cycler System.
These will be performed by entering the turbine inlet/outlet temperature and pressure
values into a steam properties calculator which will then yield the necessary enthalpies
for performing the computations. Values for entropy will also be collected. Shown
below in Figure 2 is an image of a turbine in a Rankine Cycler System [1].
Figure 3 Above is a plot of boiler pressure vs. time. Due to the absence of a pump a
transient state occurs during operation of the Rankine Cycler System.
Figure 5 Above is a plot of fuel flow vs. time. The sudden drop in flow is most likely an
anomaly in the acquisition of the data by the computer.
Figure 13 Above is a plot of propane energy release vs. time. The sudden drop in this
data relates to Figure 5 since flow rate was involved in the energy computation.
Calculations:
The isentropic efficiency for the turbine is determined using
nturb = hin hout,a/hin hout,s
At time 9:21:52 using the online calculator yielded
Turbine Inlet
Recorded @ 9:21:52
Recorded Data
Pressure (kPa)
Temperature (C)
Value
162.2
113.0
Table 1 Shown above is a table of values obtained by the data acquisition computer.
Turbine Inlet
Recorded @ 9:21:52
Recorded Data
Entropy (kJ/kg*K)
Enthalpy (kJ/kg)
Value
7.232
2696.62
Table 2 Shown above is a table of values for the thermodynamic properties based on
the values acquired by the data acquisition computer.
Turbine Outlet
Recorded @ 9:21:52
Recorded Data
Pressure (kPa)
Temperature (C)
Value
130.4
101.0
Table 3 Shown above is a table of values obtained by the data acquisition computer.
Turbine Outlet
Recorded @ 9:21:52
Recorded Data
Entropy (kJ/kg*K)
Enthalpy (kJ/kg)
Value
7.300
2691.245
Table 4 Shown above is a table of values for the thermodynamic properties based on
the values acquired by the data acquisition computer.
Recorded Data
Pressure (kPa)
Temperature (C)
Value
130.4
106.0
Table 5 Shown above is a table of values obtained by the data acquisition computer.
Turbine Outlet
Recorded @ 9:21:52
Recorded Data
Entropy (kJ/kg*K)
Enthalpy (kJ/kg)
Value
7.280
2684.959
Table 6 Shown above is a table of values for the thermodynamic properties based on
the values acquired by the data acquisition computer.
Recorded Data
Pressure (kPa)
Temperature (C)
Value
204.3
130.0
Table 7 Shown above is a table of values obtained by the data acquisition computer.
Turbine Inlet
Recorded @ 9:29:24
Recorded Data
Entropy (kJ/kg*K)
Enthalpy (kJ/kg)
Value
7.169
2726.83
Table 8 Shown above is a table of values for the thermodynamic properties based on
the values acquired by the data acquisition computer.
Turbine Outlet
Recorded @ 9:29:24
Recorded Data
Pressure (kPa)
Temperature (C)
Value
130.2
109.0
Table 9 Shown above is a table of values obtained by the data acquisition computer.
Turbine Outlet
Recorded @ 9:29:24
Recorded Data
Entropy (kJ/kg*K)
Enthalpy (kJ/kg)
Value
7.350
2704.267
Table 10 Shown above is a table of values for the thermodynamic properties based on
the values acquired by the data acquisition computer.
Recorded Data
Pressure (kPa)
Temperature (C)
Value
130.2
105.0
Table 11 Shown above is a table of values obtained by the data acquisition computer.
Turbine Outlet
Recorded @ 9:29:24
Recorded Data
Entropy (kJ/kg*K)
Enthalpy (kJ/kg)
Value
7.298
2683.511
Table 12 Shown above is a table of values for the thermodynamic properties based on
the values acquired by the data acquisition computer.
In regard to the turbine efficiency at 9:21:52 it was calculated at 46.1%. At this time the
turbine inlet pressure was recorded at 162.2 kPa. A short time later at 9:29:24 the
turbine efficiency was calculated at 52.1%. This time the turbine inlet pressure was
measured at 204.3 kPa. Thus, the turbine efficiency increased with a greater value for
inlet pressure. Essentially a higher value of inlet pressure means that a smaller
percentage of pressurized steam is lost to overcoming the rolling frictional factor of the
turbine wheel. Hence, with a higher percentage of the overall inlet steam pressure
being available for moving the turbine wheel the turbine efficiency increased.
The generator power output maximized at 9:42:28 at a value of 9.19 Watts. At this time
the turbine inlet temperature was 207 C at a pressure of 117 kPa. Also, the turbine
rpm was 3,580 rpm, which was the maximum rpm achieved during operation of the lab
apparatus. Therefore, steam at a high temperature and low pressure drives the turbine
wheel to its maximum rpm, thus causing the generator power output to yield its
maximum value. Since at a high temperature and low pressure the steam will have
more entropy it makes sense that the combination of values for pressure and
temperature at 9:42:28 drives the turbine to its maximum level of rpm.
Changes that could be made to the Rankine Cycler System if space permitted include
the addition of a collector for the condensed steam and a pump. The addition of these
elements to the apparatus would make for a genuine rankine cycle and more realistic
data collection such as achieving steady state boiler pressure instead of a transient
state during operation.
11
References
[1] Turbine Technologies, LTD, April 2012, RankineCycler Steam Turbine Power
System Sample Lab Experiment Procedure. From
<http://www.turbinetechnologies.com/portals/0/pdfs/rankinecycler_tech_sheets/rankincy
clersamplelab.pdf>.
[2] Ecourses, Thermodynamics Theory: Rankine Cycle. From
<http://www.ecourses.ou.edu/cgibin/ebook.cgi?topic=th&chap_sec=10.1&page=theory>.
Calculator:
CalcSteam, Calculation of thermodynamic properties of overheated steam. From
<http://www.peacesoftware.de/einigewerte/wasser_dampf_e.html>.