POSITION
DEVICE
Position Name:
APT-201
Work Order Number:
Location:
Plant Structure:
CrTD/
FUNCTION
Function:
Transfer Function:
Range (I/O):
Device ID:
APT-201
10126883
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:
CALIBRATION EVENT
PROCEDURE
Due Date:
06-May-17
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:
Calibration Date:
06-May-15 1:12:46 PM
Next Cal. Date:
06-May-17
Environment Temp.: 0.00
Interval:
2 years
Adjust To <: 0.00 % of span
1. As Found
FAILED
Actual
Input
[bar]
0.99
Humidity:
CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:
Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:
2. As Left
PASSED
Actual
Found
Output
Error
[mA]
[% of span]
4.812
0.125
Nominal
Input
[bar]
0.000
Actual
Input
[bar]
0.98
Nominal
Output
[mA]
4.00
Actual
Found
Output
Error
[mA]
[% of span]
4.7852
0.0075
5.000
5.01
8.000
8.046
0.238
5.000
5.02
8.000
8.0078
-0.0513
10.000
10.02
12.000
12.061
0.281
10.000
10.00
12.000
12.0084
0.0525
15.000
15.01
16.000
16.055
0.294
15.000
15.00
16.000
16.0000
0.0000
20.000
20.01
20.000
20.064
0.350
20.000
20.00
20.000
20.0004
0.0025
15.000
15.03
16.000
16.065
0.256
15.000
15.00
16.000
16.0004
0.0025
10.000
10.05
12.000
12.077
0.231
10.000
10.00
12.000
12.0053
0.0331
5.000
5.03
8.000
8.059
0.219
5.000
5.02
8.000
8.0199
0.0244
0.000
0.99
4.00
4.814
0.138
0.000
0.97
4.00
4.7840
0.0500
Calibration Note:
Calibrated by:
V M More
06-May-15 1:12:46 PM
Approved:
S Saha, SO/D
06-May-15 1:16:45 PM
Page: 1/ 1
CALIBRATION CERTIFICATE
POSITION
DEVICE
Position Name:
APT-202
Work Order Number:
Location:
Plant Structure:
CrTD/
FUNCTION
Function:
Transfer Function:
Range (I/O):
Device ID:
APT-202
1012686
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:
CALIBRATION EVENT
PROCEDURE
Due Date:
06-May-17
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:
Calibration Date:
12-May-15 3:59:34 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00
Interval:
2 years
Adjust To <: 0.00 % of span
1. As Found
Humidity:
FAILED
CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:
Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:
2. As Left
PASSED
Nominal
Input
[bar]
1.00
Actual
Input
[bar]
1.00
Nominal
Output
[mA]
6.67
Actual
Found
Output
Error
[mA]
[% of span]
6.648
-0.117
Nominal
Input
[bar]
1.00
Actual
Input
[bar]
0.99
Nominal
Output
[mA]
6.67
1.50
1.50
8.00
8.065
3.00
3.00
12.0
12.075
4.50
4.50
16.0
6.00
6.00
4.50
Actual
Found
Output
Error
[mA]
[% of span]
6.6413
0.0081
0.406
1.50
1.50
8.00
8.004
0.025
0.469
3.00
3.00
12.0
12.006
0.038
16.085
0.531
4.50
4.50
16.0
16.002
0.012
20.0
20.025
0.156
6.00
6.00
20.0
20.002
0.012
4.50
16.0
16.085
0.531
4.50
4.50
16.0
16.003
0.019
3.00
3.00
12.0
12.075
0.469
3.00
3.00
12.0
12.005
0.031
1.50
1.50
8.00
8.065
0.406
1.50
1.50
8.00
8.003
0.019
1.00
1.00
6.67
6.648
-0.117
1.00
0.99
6.67
6.640
0.000
Calibration Note:
Calibrated by:
V M More
12-May-15 3:59:34 PM
Approved:
S Saha, SO/D
12-May-15 4:02:27 PM
Page: 1/ 1
CALIBRATION CERTIFICATE
POSITION
DEVICE
Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/
FUNCTION
Function:
Transfer Function:
Range (I/O):
Device ID:
APT-203
101267
Serial Number:
Manufacturer Model: ABB 600T 624 FA
Operating Range:
Operating Temp.:
CALIBRATION EVENT
PROCEDURE
Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:
Calibration Date:
12-May-15 1:35:35 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00
Interval:
24 months
Adjust To <: 0.00 % of span
1. As Found
FAILED
Actual
Input
[bar]
0.99
Humidity:
CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:
Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:
2. As Left
PASSED
Actual
Found
Output
Error
[mA]
[% of span]
4.8135
0.1344
Nominal
Input
[bar]
0.000
Actual
Input
[bar]
0.98
Nominal
Output
[mA]
4.00
Actual
Found
Output
Error
[mA]
[% of span]
4.785
0.006
5.000
5.000
8.000
8.0338
0.2112
5.000
5.000
8.000
8.009
0.056
10.000
10.000
12.000
12.042
0.262
10.000
10.000
12.000
11.999
-0.006
15.000
15.000
16.000
16.052
0.325
15.000
15.000
16.000
16.003
0.019
20.000
20.000
20.000
20.008
0.050
20.000
20.000
20.000
20.001
0.006
15.000
15.000
16.000
16.055
0.344
15.000
15.000
16.000
16.003
0.019
10.000
10.000
12.000
12.044
0.275
10.000
10.000
12.000
11.998
-0.013
5.000
5.000
8.000
8.041
0.256
5.000
5.000
8.000
8.003
0.019
0.000
0.99
4.00
4.822
0.188
0.000
0.98
4.00
4.7850
0.0063
Calibration Note:
Calibrated by:
V M More
12-May-15 1:35:35 PM
Approved:
S Saha, SO/D
12-May-15 1:39:29 PM
Page: 1/ 1
CALIBRATION CERTIFICATE
POSITION
DEVICE
Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/
FUNCTION
Function:
Transfer Function:
Range (I/O):
Device ID:
APT-204
1012682
Serial Number:
Manufacturer Model: ABB 600T 624 FA
Operating Range:
Operating Temp.:
CALIBRATION EVENT
PROCEDURE
Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:
Calibration Date:
12-May-15 4:03:52 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00
Interval:
24 months
Adjust To <: 0.00 % of span
1. As Found
FAILED
Actual
Input
[bar]
0.98
Humidity:
CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:
Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:
2. As Left
PASSED
Actual
Found
Output
Error
[mA]
[% of span]
4.8136
0.1850
Nominal
Input
[bar]
0.000
Actual
Input
[bar]
0.98
Nominal
Output
[mA]
4.00
Actual
Found
Output
Error
[mA]
[% of span]
4.784
0.000
5.000
5.00
8.000
8.043
0.269
5.000
5.00
8.000
8.004
0.025
10.000
10.00
12.000
12.045
0.281
10.000
10.00
12.000
12.003
0.019
15.000
15.00
16.000
16.082
0.513
15.000
15.00
16.000
16.005
0.031
20.000
20.00
20.000
20.063
0.394
20.000
20.00
20.000
20.004
0.025
15.000
15.00
16.000
16.083
0.519
15.000
15.00
16.000
16.004
0.025
10.000
10.00
12.000
12.045
0.281
10.000
10.00
12.000
12.004
0.025
5.000
5.00
8.000
8.043
0.269
5.000
5.00
8.000
8.006
0.038
0.000
0.98
4.00
4.8136
0.1850
0.000
0.98
4.00
4.785
0.006
Calibration Note:
Calibrated by:
V M More
12-May-15 4:03:52 PM
Approved:
S Saha, SO/D
12-May-15 4:06:50 PM
Page: 1/ 1
CALIBRATION CERTIFICATE
POSITION
DEVICE
Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/
FUNCTION
Function:
Transfer Function:
Range (I/O):
Device ID:
APT-205
1012689
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:
CALIBRATION EVENT
PROCEDURE
Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:
Calibration Date:
12-May-15 2:03:49 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00
Interval:
24 months
Adjust To <: 0.00 % of span
1. As Found
Humidity:
FAILED
CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:
Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:
2. As Left
PASSED
Nominal
Input
[bar]
0.00
Actual
Input
[bar]
1.01
Nominal
Output
[mA]
Nominal
Input
[bar]
0.00
Actual
Input
[bar]
1.00
1.50
1.50
8.00
8.0177
0.1106
1.50
1.50
8.00
3.00
3.00
12.0
8.0002
0.0012
12.1038
0.6487
3.00
3.00
12.0
12.0001
4.50
4.50
0.0006
16.0
16.1008
0.6300
4.50
4.50
16.0
16.0002
6.00
0.0012
6.00
20.0
20.1184
0.7400
6.00
6.00
20.0
20.0002
0.0012
4.50
4.50
16.0
16.1005
0.6281
4.50
4.50
16.0
16.0002
0.0012
3.00
3.00
12.0
12.1025
0.6406
3.00
3.00
12.0
12.0001
0.0006
1.50
1.50
8.00
8.0156
0.0975
1.50
1.50
8.00
8.0001
0.0006
0.00
1.01
4.0
6.7528
0.3717
0.00
1.00
4.0
6.6667
0.0002
4.0
Actual
Found
Output
Error
[mA]
[% of span]
6.7528
0.3717
Nominal
Output
[mA]
4.0
Actual
Found
Output
Error
[mA]
[% of span]
6.6667
0.0002
Calibration Note:
Calibrated by:
V M More
12-May-15 2:03:49 PM
Approved:
S Saha, SO/D
12-May-15 2:06:43 PM
Page: 1/ 1
CALIBRATION CERTIFICATE
POSITION
DEVICE
Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/
FUNCTION
Function:
Transfer Function:
Range (I/O):
Device ID:
APT-206
1012679
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:
CALIBRATION EVENT
PROCEDURE
Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:
Calibration Date:
12-May-15 2:09:53 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00
Interval:
24 months
Adjust To <: 0.00 % of span
1. As Found
Humidity:
FAILED
CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:
Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:
2. As Left
PASSED
Nominal
Input
[bar]
0.00
Actual
Input
[bar]
1.00
Nominal
Output
[mA]
Nominal
Input
[bar]
0.00
Actual
Input
[bar]
1.00
1.50
1.50
8.00
8.007
0.044
1.50
1.50
8.00
3.00
3.00
12.0
8.0001
0.0006
12.013
0.081
3.00
3.00
12.0
12.0001
4.50
4.50
0.0006
16.0
16.022
0.137
4.50
4.50
16.0
16.0002
6.00
0.0012
6.00
20.0
20.028
0.175
6.00
6.00
20.0
20.0003
0.0019
4.50
4.50
16.0
16.023
0.144
4.50
4.50
16.0
16.0004
0.0025
3.00
3.00
12.0
12.014
0.087
3.00
3.00
12.0
12.0001
0.0006
1.50
1.50
8.00
8.005
0.031
1.50
1.50
8.00
8.0001
0.0006
0.00
1.00
4.0
6.6862
0.1221
0.00
1.00
4.0
6.6668
0.0008
4.0
Actual
Found
Output
Error
[mA]
[% of span]
6.6762
0.0596
Nominal
Output
[mA]
4.0
Actual
Found
Output
Error
[mA]
[% of span]
6.6669
0.0015
Calibration Note:
Calibrated by:
V M More
12-May-15 2:09:53 PM
Approved:
S Saha, SO/D
12-May-15 2:24:49 PM
Page: 1/ 1
CALIBRATION CERTIFICATE
POSITION
DEVICE
Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/
FUNCTION
Function:
Transfer Function:
Range (I/O):
Device ID:
APT-207
1012688
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:
CALIBRATION EVENT
PROCEDURE
Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:
Calibration Date:
12-May-15 2:17:08 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00
Interval:
24 months
Adjust To <: 0.00 % of span
1. As Found
Humidity:
FAILED
CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:
Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:
2. As Left
PASSED
Nominal
Input
[bar]
1.00
Actual
Input
[bar]
1.00
Nominal
Output
[mA]
6.67
Actual
Found
Output
Error
[mA]
[% of span]
6.6845
0.1115
Nominal
Input
[bar]
1.00
Actual
Input
[bar]
1.00
Nominal
Output
[mA]
6.67
1.50
1.50
8.00
7.9822
3.00
3.00
12.0
11.9828
4.50
4.50
16.0
6.00
6.00
4.50
Actual
Found
Output
Error
[mA]
[% of span]
6.6678
0.0071
-0.1113
1.50
1.50
8.00
7.9994
-0.0038
-0.1075
3.00
3.00
12.0
11.9993
-0.0044
15.9811
-0.1181
4.50
4.50
16.0
15.9998
-0.0012
20.0
19.9822
-0.1113
6.00
6.00
20.0
20.0003
0.0019
4.50
16.0
15.9854
-0.0912
4.50
4.50
16.0
15.9997
-0.0019
3.00
3.00
12.0
11.9825
-0.1094
3.00
3.00
12.0
11.9994
-0.0038
1.50
1.50
8.00
7.9823
-0.1106
1.50
1.50
8.00
7.9999
-0.0006
1.00
1.00
6.67
6.6844
0.1108
1.00
1.00
6.67
6.6679
0.0077
Calibration Note:
Calibrated by:
V M More
12-May-15 2:17:08 PM
Approved:
S Saha, SO/D
12-May-15 2:19:17 PM
Page: 1/ 1
CALIBRATION CERTIFICATE
POSITION
DEVICE
Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/
FUNCTION
Function:
Transfer Function:
Range (I/O):
Device ID:
APT-208
1012687
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:
CALIBRATION EVENT
PROCEDURE
Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:
Calibration Date:
12-May-15 3:56:06 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00
Interval:
24 months
Adjust To <: 0.00 % of span
1. As Found
Humidity:
FAILED
CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:
Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:
2. As Left
PASSED
Nominal
Input
[bar]
0.98
Actual
Input
[bar]
0.98
Nominal
Output
[mA]
Nominal
Input
[bar]
0.98
Actual
Input
[bar]
0.98
1.50
1.50
8.00
8.068
0.425
1.50
1.50
8.00
3.00
3.00
12.0
7.9999
-0.0006
12.135
0.844
3.00
3.00
12.0
12.0031
4.50
4.50
0.0194
16.0
16.132
0.825
4.50
4.50
16.0
16.0024
6.00
0.0150
6.00
20.0
20.083
0.519
6.00
6.00
20.0
20.0021
0.0131
4.50
4.50
16.0
16.132
0.825
4.50
4.50
16.0
16.0021
0.0131
3.00
3.00
12.0
12.135
0.844
3.00
3.00
12.0
12.0003
0.0019
1.50
1.50
8.00
8.068
0.425
1.50
1.50
8.00
8.0010
0.0062
0.98
0.98
6.6
6.665
0.323
0.98
0.98
6.6
6.6180
0.0292
6.6
Actual
Found
Output
Error
[mA]
[% of span]
6.663
0.310
Nominal
Output
[mA]
6.6
Actual
Found
Output
Error
[mA]
[% of span]
6.6176
0.0267
Calibration Note:
Calibrated by:
V M More
12-May-15 3:56:06 PM
Approved:
S Saha, SO/D
12-May-15 3:58:05 PM
Page: 1/ 1