CALIBRATION CERTIFICATE

Printed: 06.05.2015 13:17:03


Printed by: ADMIN
CMX version: 2.5.144.0

Certificate Number: CrTD-017


POSITION ID: APT-201

POSITION

DEVICE

Position Name:
APT-201
Work Order Number:
Location:
Plant Structure:
CrTD/

FUNCTION

Function:
Transfer Function:
Range (I/O):

Device ID:
APT-201
10126883
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:

CALIBRATION EVENT

Abs. Pressure Transmitter (APT)


Linear
0.00 to 20.00 bar (A)
4.00 to 20.00 mA

PROCEDURE

Due Date:
06-May-17
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:

Calibration Date:
06-May-15 1:12:46 PM
Next Cal. Date:
06-May-17
Environment Temp.: 0.00

Interval:
2 years
Adjust To <: 0.00 % of span

1. As Found

FAILED

Max Error: 0.35 % of span


Nominal
Input
[bar]
0.000

Actual
Input
[bar]
0.99

Humidity:

CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:

MC4 s/n: 40625

Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:

MC4 s/n: 40625

2. As Left

PASSED

Max Error: 0.05 % of span


Nominal
Output
[mA]
4.00

Actual
Found
Output
Error
[mA]
[% of span]
4.812
0.125

Nominal
Input
[bar]
0.000

Actual
Input
[bar]
0.98

Nominal
Output
[mA]
4.00

Actual
Found
Output
Error
[mA]
[% of span]
4.7852
0.0075

5.000

5.01

8.000

8.046

0.238

5.000

5.02

8.000

8.0078

-0.0513

10.000

10.02

12.000

12.061

0.281

10.000

10.00

12.000

12.0084

0.0525

15.000

15.01

16.000

16.055

0.294

15.000

15.00

16.000

16.0000

0.0000

20.000

20.01

20.000

20.064

0.350

20.000

20.00

20.000

20.0004

0.0025

15.000

15.03

16.000

16.065

0.256

15.000

15.00

16.000

16.0004

0.0025

10.000

10.05

12.000

12.077

0.231

10.000

10.00

12.000

12.0053

0.0331

5.000

5.03

8.000

8.059

0.219

5.000

5.02

8.000

8.0199

0.0244

0.000

0.99

4.00

4.814

0.138

0.000

0.97

4.00

4.7840

0.0500

Calibration Note:

Calibrated by:

V M More
06-May-15 1:12:46 PM

Approved:

S Saha, SO/D
06-May-15 1:16:45 PM

Page: 1/ 1

CALIBRATION CERTIFICATE

Printed: 12.05.2015 16:02:35


Printed by: ADMIN
CMX version: 2.5.144.0

Certificate Number: CrTD-018


POSITION ID: APT-202

POSITION

DEVICE

Position Name:
APT-202
Work Order Number:
Location:
Plant Structure:
CrTD/

FUNCTION

Function:
Transfer Function:
Range (I/O):

Device ID:
APT-202
1012686
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:

CALIBRATION EVENT

Abs. Pressure Transmitter (APT)


Linear
0.00 to 6.00 bar (A)
4.00 to 20.00 mA

PROCEDURE

Due Date:
06-May-17
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:

Calibration Date:
12-May-15 3:59:34 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00

Interval:
2 years
Adjust To <: 0.00 % of span

1. As Found

Humidity:

FAILED

Max Error: 0.53 % of span

CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:

MC4 s/n: 40625

Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:

MC4 s/n: 40625

2. As Left

PASSED

Max Error: 0.04 % of span

Nominal
Input
[bar]
1.00

Actual
Input
[bar]
1.00

Nominal
Output
[mA]
6.67

Actual
Found
Output
Error
[mA]
[% of span]
6.648
-0.117

Nominal
Input
[bar]
1.00

Actual
Input
[bar]
0.99

Nominal
Output
[mA]
6.67

1.50

1.50

8.00

8.065

3.00

3.00

12.0

12.075

4.50

4.50

16.0

6.00

6.00

4.50

Actual
Found
Output
Error
[mA]
[% of span]
6.6413
0.0081

0.406

1.50

1.50

8.00

8.004

0.025

0.469

3.00

3.00

12.0

12.006

0.038

16.085

0.531

4.50

4.50

16.0

16.002

0.012

20.0

20.025

0.156

6.00

6.00

20.0

20.002

0.012

4.50

16.0

16.085

0.531

4.50

4.50

16.0

16.003

0.019

3.00

3.00

12.0

12.075

0.469

3.00

3.00

12.0

12.005

0.031

1.50

1.50

8.00

8.065

0.406

1.50

1.50

8.00

8.003

0.019

1.00

1.00

6.67

6.648

-0.117

1.00

0.99

6.67

6.640

0.000

Calibration Note:

Calibrated by:

V M More
12-May-15 3:59:34 PM

Approved:

S Saha, SO/D
12-May-15 4:02:27 PM

Page: 1/ 1

CALIBRATION CERTIFICATE

Printed: 12.05.2015 13:39:42


Printed by: ADMIN
CMX version: 2.5.144.0

Certificate Number: CrTD-019


POSITION ID: APT-203

POSITION

DEVICE

Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/

FUNCTION

Function:
Transfer Function:
Range (I/O):

Device ID:
APT-203
101267
Serial Number:
Manufacturer Model: ABB 600T 624 FA
Operating Range:
Operating Temp.:

CALIBRATION EVENT

Abs. Pressure Transmitter (APT)


Linear
0.00 to 20.00 bar (A)
4.00 to 20.00 mA

PROCEDURE

Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:

Calibration Date:
12-May-15 1:35:35 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00

Interval:
24 months
Adjust To <: 0.00 % of span

1. As Found

FAILED

Max Error: 0.34 % of span


Nominal
Input
[bar]
0.000

Actual
Input
[bar]
0.99

Humidity:

CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:

MC4 s/n: 40625

Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:

MC4 s/n: 40625

2. As Left

PASSED

Max Error: 0.06 % of span


Nominal
Output
[mA]
4.00

Actual
Found
Output
Error
[mA]
[% of span]
4.8135
0.1344

Nominal
Input
[bar]
0.000

Actual
Input
[bar]
0.98

Nominal
Output
[mA]
4.00

Actual
Found
Output
Error
[mA]
[% of span]
4.785
0.006

5.000

5.000

8.000

8.0338

0.2112

5.000

5.000

8.000

8.009

0.056

10.000

10.000

12.000

12.042

0.262

10.000

10.000

12.000

11.999

-0.006

15.000

15.000

16.000

16.052

0.325

15.000

15.000

16.000

16.003

0.019

20.000

20.000

20.000

20.008

0.050

20.000

20.000

20.000

20.001

0.006

15.000

15.000

16.000

16.055

0.344

15.000

15.000

16.000

16.003

0.019

10.000

10.000

12.000

12.044

0.275

10.000

10.000

12.000

11.998

-0.013

5.000

5.000

8.000

8.041

0.256

5.000

5.000

8.000

8.003

0.019

0.000

0.99

4.00

4.822

0.188

0.000

0.98

4.00

4.7850

0.0063

Calibration Note:

Calibrated by:

V M More
12-May-15 1:35:35 PM

Approved:

S Saha, SO/D
12-May-15 1:39:29 PM

Page: 1/ 1

CALIBRATION CERTIFICATE

Printed: 12.05.2015 16:06:53


Printed by: ADMIN
CMX version: 2.5.144.0

Certificate Number: CrTD-020


POSITION ID: APT-204

POSITION

DEVICE

Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/

FUNCTION

Function:
Transfer Function:
Range (I/O):

Device ID:
APT-204
1012682
Serial Number:
Manufacturer Model: ABB 600T 624 FA
Operating Range:
Operating Temp.:

CALIBRATION EVENT

Abs. Pressure Transmitter (APT)


Linear
0.00 to 20.00 bar (A)
4.00 to 20.00 mA

PROCEDURE

Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:

Calibration Date:
12-May-15 4:03:52 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00

Interval:
24 months
Adjust To <: 0.00 % of span

1. As Found

FAILED

Max Error: 0.52 % of span


Nominal
Input
[bar]
0.000

Actual
Input
[bar]
0.98

Humidity:

CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:

MC4 s/n: 40625

Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:

MC4 s/n: 40625

2. As Left

PASSED

Max Error: 0.04 % of span


Nominal
Output
[mA]
4.00

Actual
Found
Output
Error
[mA]
[% of span]
4.8136
0.1850

Nominal
Input
[bar]
0.000

Actual
Input
[bar]
0.98

Nominal
Output
[mA]
4.00

Actual
Found
Output
Error
[mA]
[% of span]
4.784
0.000

5.000

5.00

8.000

8.043

0.269

5.000

5.00

8.000

8.004

0.025

10.000

10.00

12.000

12.045

0.281

10.000

10.00

12.000

12.003

0.019

15.000

15.00

16.000

16.082

0.513

15.000

15.00

16.000

16.005

0.031

20.000

20.00

20.000

20.063

0.394

20.000

20.00

20.000

20.004

0.025

15.000

15.00

16.000

16.083

0.519

15.000

15.00

16.000

16.004

0.025

10.000

10.00

12.000

12.045

0.281

10.000

10.00

12.000

12.004

0.025

5.000

5.00

8.000

8.043

0.269

5.000

5.00

8.000

8.006

0.038

0.000

0.98

4.00

4.8136

0.1850

0.000

0.98

4.00

4.785

0.006

Calibration Note:

Calibrated by:

V M More
12-May-15 4:03:52 PM

Approved:

S Saha, SO/D
12-May-15 4:06:50 PM

Page: 1/ 1

CALIBRATION CERTIFICATE

Printed: 12.05.2015 14:06:48


Printed by: ADMIN
CMX version: 2.5.144.0

Certificate Number: CrTD-021


POSITION ID: APT-205

POSITION

DEVICE

Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/

FUNCTION

Function:
Transfer Function:
Range (I/O):

Device ID:
APT-205
1012689
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:

CALIBRATION EVENT

Abs. Pressure Transmitter (APT)


Linear
0.00 to 6.00 bar (A)
4.00 to 20.00 mA

PROCEDURE

Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:

Calibration Date:
12-May-15 2:03:49 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00

Interval:
24 months
Adjust To <: 0.00 % of span

1. As Found

Humidity:

FAILED

Max Error: 0.74 % of span

CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:

MC4 s/n: 40625

Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:

MC4 s/n: 40625

2. As Left

PASSED

Max Error: 0.00 % of span

Nominal
Input
[bar]
0.00

Actual
Input
[bar]
1.01

Nominal
Output
[mA]

Nominal
Input
[bar]
0.00

Actual
Input
[bar]
1.00

1.50

1.50

8.00

8.0177

0.1106

1.50

1.50

8.00

3.00

3.00

12.0

8.0002

0.0012

12.1038

0.6487

3.00

3.00

12.0

12.0001

4.50

4.50

0.0006

16.0

16.1008

0.6300

4.50

4.50

16.0

16.0002

6.00

0.0012

6.00

20.0

20.1184

0.7400

6.00

6.00

20.0

20.0002

0.0012

4.50

4.50

16.0

16.1005

0.6281

4.50

4.50

16.0

16.0002

0.0012

3.00

3.00

12.0

12.1025

0.6406

3.00

3.00

12.0

12.0001

0.0006

1.50

1.50

8.00

8.0156

0.0975

1.50

1.50

8.00

8.0001

0.0006

0.00

1.01

4.0

6.7528

0.3717

0.00

1.00

4.0

6.6667

0.0002

4.0

Actual
Found
Output
Error
[mA]
[% of span]
6.7528
0.3717

Nominal
Output
[mA]
4.0

Actual
Found
Output
Error
[mA]
[% of span]
6.6667
0.0002

Calibration Note:

Calibrated by:

V M More
12-May-15 2:03:49 PM

Approved:

S Saha, SO/D
12-May-15 2:06:43 PM

Page: 1/ 1

CALIBRATION CERTIFICATE

Printed: 12.05.2015 14:25:08


Printed by: ADMIN
CMX version: 2.5.144.0

Certificate Number: CrTD-022


POSITION ID: APT-206

POSITION

DEVICE

Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/

FUNCTION

Function:
Transfer Function:
Range (I/O):

Device ID:
APT-206
1012679
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:

CALIBRATION EVENT

Abs. Pressure Transmitter (APT)


Linear
0.00 to 6.00 bar (A)
4.00 to 20.00 mA

PROCEDURE

Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:

Calibration Date:
12-May-15 2:09:53 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00

Interval:
24 months
Adjust To <: 0.00 % of span

1. As Found

Humidity:

FAILED

Max Error: 0.18 % of span

CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:

MC4 s/n: 40625

Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:

MC4 s/n: 40625

2. As Left

PASSED

Max Error: 0.00 % of span

Nominal
Input
[bar]
0.00

Actual
Input
[bar]
1.00

Nominal
Output
[mA]

Nominal
Input
[bar]
0.00

Actual
Input
[bar]
1.00

1.50

1.50

8.00

8.007

0.044

1.50

1.50

8.00

3.00

3.00

12.0

8.0001

0.0006

12.013

0.081

3.00

3.00

12.0

12.0001

4.50

4.50

0.0006

16.0

16.022

0.137

4.50

4.50

16.0

16.0002

6.00

0.0012

6.00

20.0

20.028

0.175

6.00

6.00

20.0

20.0003

0.0019

4.50

4.50

16.0

16.023

0.144

4.50

4.50

16.0

16.0004

0.0025

3.00

3.00

12.0

12.014

0.087

3.00

3.00

12.0

12.0001

0.0006

1.50

1.50

8.00

8.005

0.031

1.50

1.50

8.00

8.0001

0.0006

0.00

1.00

4.0

6.6862

0.1221

0.00

1.00

4.0

6.6668

0.0008

4.0

Actual
Found
Output
Error
[mA]
[% of span]
6.6762
0.0596

Nominal
Output
[mA]
4.0

Actual
Found
Output
Error
[mA]
[% of span]
6.6669
0.0015

Calibration Note:

Calibrated by:

V M More
12-May-15 2:09:53 PM

Approved:

S Saha, SO/D
12-May-15 2:24:49 PM

Page: 1/ 1

CALIBRATION CERTIFICATE

Printed: 12.05.2015 14:19:23


Printed by: ADMIN
CMX version: 2.5.144.0

Certificate Number: CrTD-023


POSITION ID: APT-207

POSITION

DEVICE

Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/

FUNCTION

Function:
Transfer Function:
Range (I/O):

Device ID:
APT-207
1012688
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:

CALIBRATION EVENT

Pressure Transmitter (APT)


Linear
0.00 to 6.00 bar (A)
4.00 to 20.00 mA

PROCEDURE

Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:

Calibration Date:
12-May-15 2:17:08 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00

Interval:
24 months
Adjust To <: 0.00 % of span

1. As Found

Humidity:

FAILED

Max Error: -0.12 % of span

CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:

MC4 s/n: 40625

Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:

MC4 s/n: 40625

2. As Left

PASSED

Max Error: 0.01 % of span

Nominal
Input
[bar]
1.00

Actual
Input
[bar]
1.00

Nominal
Output
[mA]
6.67

Actual
Found
Output
Error
[mA]
[% of span]
6.6845
0.1115

Nominal
Input
[bar]
1.00

Actual
Input
[bar]
1.00

Nominal
Output
[mA]
6.67

1.50

1.50

8.00

7.9822

3.00

3.00

12.0

11.9828

4.50

4.50

16.0

6.00

6.00

4.50

Actual
Found
Output
Error
[mA]
[% of span]
6.6678
0.0071

-0.1113

1.50

1.50

8.00

7.9994

-0.0038

-0.1075

3.00

3.00

12.0

11.9993

-0.0044

15.9811

-0.1181

4.50

4.50

16.0

15.9998

-0.0012

20.0

19.9822

-0.1113

6.00

6.00

20.0

20.0003

0.0019

4.50

16.0

15.9854

-0.0912

4.50

4.50

16.0

15.9997

-0.0019

3.00

3.00

12.0

11.9825

-0.1094

3.00

3.00

12.0

11.9994

-0.0038

1.50

1.50

8.00

7.9823

-0.1106

1.50

1.50

8.00

7.9999

-0.0006

1.00

1.00

6.67

6.6844

0.1108

1.00

1.00

6.67

6.6679

0.0077

Calibration Note:

Calibrated by:

V M More
12-May-15 2:17:08 PM

Approved:

S Saha, SO/D
12-May-15 2:19:17 PM

Page: 1/ 1

CALIBRATION CERTIFICATE

Printed: 12.05.2015 15:58:16


Printed by: ADMIN
CMX version: 2.5.144.0

Certificate Number: CrTD-024


POSITION ID: APT-208

POSITION

DEVICE

Position Name:
Work Order Number:
Location:
Plant Structure:
CrTD/

FUNCTION

Function:
Transfer Function:
Range (I/O):

Device ID:
APT-208
1012687
Serial Number:
Manufacturer Model: ABB 600T EN 624 EA
Operating Range:
Operating Temp.:

CALIBRATION EVENT

Abs. Pressure Transmitter (APT)


Linear
0.00 to 6.00 bar (A)
4.00 to 20.00 mA

PROCEDURE

Due Date:
Reject if Error >:
0.075 % of span
Classification:
Calibration Strategy:

Calibration Date:
12-May-15 3:56:06 PM
Next Cal. Date:
12-May-17
Environment Temp.: 0.00

Interval:
24 months
Adjust To <: 0.00 % of span

1. As Found

Humidity:

FAILED

Max Error: 0.84 % of span

CALIBRATORS
Input Calibrator:
Input Module:
Output Calibrator:
Output Module:

MC4 s/n: 40625

Humidity: 0.00 %
Due Date:
Due Date:
Due Date:
Due Date:

MC4 s/n: 40625

2. As Left

PASSED

Max Error: 0.03 % of span

Nominal
Input
[bar]
0.98

Actual
Input
[bar]
0.98

Nominal
Output
[mA]

Nominal
Input
[bar]
0.98

Actual
Input
[bar]
0.98

1.50

1.50

8.00

8.068

0.425

1.50

1.50

8.00

3.00

3.00

12.0

7.9999

-0.0006

12.135

0.844

3.00

3.00

12.0

12.0031

4.50

4.50

0.0194

16.0

16.132

0.825

4.50

4.50

16.0

16.0024

6.00

0.0150

6.00

20.0

20.083

0.519

6.00

6.00

20.0

20.0021

0.0131

4.50

4.50

16.0

16.132

0.825

4.50

4.50

16.0

16.0021

0.0131

3.00

3.00

12.0

12.135

0.844

3.00

3.00

12.0

12.0003

0.0019

1.50

1.50

8.00

8.068

0.425

1.50

1.50

8.00

8.0010

0.0062

0.98

0.98

6.6

6.665

0.323

0.98

0.98

6.6

6.6180

0.0292

6.6

Actual
Found
Output
Error
[mA]
[% of span]
6.663
0.310

Nominal
Output
[mA]
6.6

Actual
Found
Output
Error
[mA]
[% of span]
6.6176
0.0267

Calibration Note:

Calibrated by:

V M More
12-May-15 3:56:06 PM

Approved:

S Saha, SO/D
12-May-15 3:58:05 PM