2X250 MW Bhilai Power Plant- Unit 1

Attachment-2 to Doc.No. PE-DC-239-509-E001, Rev A

ERT-1

meter
Probe spacing, M reading
0.5
3.2
1
3.8
1.5
4.3
2
3.0
2.5
1.7
3
2.2
3.5
5.5
4
2.8
4.5
3.4
5
4.3
5.5
3.9
6
0.6
6.5
2
7
2.1
7.5
2.7
8
1.1
8.5
2.3
9
2
9.5
1
10
3.5
Average value of
resistance at
ERT-1

Resistivity at
Area-1 (Ohm m)
10.05
23.86
40.51
37.68
26.69
41.45
120.89
70.34
96.08
135.02
134.71
22.61
81.64
92.32
127.17
55.26
122.77
113.04
59.66
219.80

Probe spacing,
M
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9
9.5
10

81.6

Average value
of resistance at
ERT-2

ERT-2

ERT-4

Resistivity at
meter Area-1 (Ohm Probe spacing,
reading
m)
M
3.1
9.73
0.5
3.4
21.35
1
3.6
33.91
1.5
3.2
40.19
2
1.7
26.69
2.5
2.5
47.10
3
4.7
103.31
3.5
3
75.36
4
4
113.04
4.5
3.9
122.46
5
2.8
96.71
5.5
1.9
71.59
6
2.3
93.89
6.5
2.4
105.50
7
1.1
51.81
7.5
2.1
105.50
8
2
106.76
8.5
1.5
84.78
9
3.7
220.74
9.5
3.4
213.52
10

meter
reading
3.8
0.9
2.0
1.7
5.1
1.4
1.1
3.2
2.2
1.8
1.6
1.3
0.8
1.0
1.5
2.0
1.9
2.3
2.2
2.9

87.2

Average value
of resistance at
ERT-4

Resistivity at
Area-1 (Ohm
m)
11.93
5.65
18.84
21.35
80.07
26.38
24.18
80.38
62.17
56.52
55.26
48.98
32.66
43.96
70.65
100.48
101.42
130.00
131.25
182.12
64.2

2X250 MW Bhilai Power Plant- Unit 1

Average value of
resistance in
Ohm-m

Attachment-2 to Doc.No. PE-DC-239-509-E001, Rev A

77.7