Appendix A: Generator

Data Sheet
104,400 KVA, 3600 RPM, 13800 Volt, 0.85 PF, 30 PSIG, 46.0 C H2, 86740 KW,
4368 Amp, 0.58 SCR, 375 FLD Volts, Wye Conn
Reactance Data(Per Unit)

Direct Axis

Quadrature Axis

Synchronous
Transient
Subtransient
Negative Sequence
Zero Sequence
Leakage

Xd 1.48
Xd0 0.196
X00d 0.136
X2 0.129
X0 0.066
Xlm 0.14

Xq 1.42
Xq0 0.484
X00q 0.132

Field Time Constant Data(Seconds at 12588 C)


Open Circuit
Open Circuit Subtransient
3PH Short circuit Transient
3PH Short circuit Subtransient
L L Short circuit Transient
L N Short circuit Transient

T 0d0 3.59
T 00d0 0.033
T d0 0.476
T 00 0.023
T 0d2 0.727
T 0d1 0.84

0
T q0
0.312
00
T q0 0.084
T q0 0.102
T 00q 0.023

Armature DC Component Time Constant Data(Seconds at 10088 C)


Three phase short circuit
L L Short Circuit
L N Short Circuit
Rotor Short-Time Thermal Capacity, I 22t
Turbine-Generator Combined Inertia Constant, H
Three Phase Armature Winding Capacitance
Armature Winding DC Resistance (per phase)
Field winding DC Resistance
Field Current at Rated KVA, Arm Volts, PF
Field Current at Rated KVA, Arm Volts, PF 0

Ta3 0.239
Ta2 0.239
Ta1 0.200
30
3.09 Kw sec/Kva
0.947 Microfarads
0.00262 Ohms 1008C
0.308 Ohms 258C
848.8 Amp
1017 Amp

517
2006 by Taylor & Francis Group, LLC