HYDAC Oil Air Coolers
HYDAC Oil Air Coolers
COOLER SYSTEM
WITH AXIAL FAN FOR
INDUSTRIAL APPLICATIONS.
Application
These high performance coolers with
axial fans are suitable for hydraulic
cooling applications with both return line
and off line versions available.
Typical applications include: industrial
power units, lubrication systems
(i.e. gearboxes) and machine tools.
E 5.801.1/01.05
OIL/AIR COOLER
DESCRIPTION
GENERAL
In hydraulic systems energy is
transformed and transmitted. During this
transformation and transmission losses
occur, i.e. mechanical and hydraulic
energy is converted into heat. It is the
function of the cooler to dissipate this
heat.
ADVANTAGES OF THE OIL/AIR
COOLERS:
z Environmentally friendly:
exchange between air and oil not
possible
z For commissioning only electrical
energy is required
z Low operating costs, no additional
cooling circuit necessary for the
cooling medium, i.e. air
CONSTRUCTION FOR OK EL1-11
Oil/air cooler units consist of the (1)
metal housing, (2) motor, (3) axial fan
and (4) heat exchanger. The oil
connections are external.
OK-EL7,8
E 5.801.1/01.05
Example
OK-EL1
OK-EL1
OK-EL2-3
OK-EL2-3
OK-EL4,5,6,9,10,11
OK-EL4-11
CONSTRUCTION FOR
OKA & OKAF EL4-6
OKA-EL4,5,6
OKA-EL4,5,6
OKAF-EL4,5,6
OKAF-EL4,5,6
OKA-EL4,5,6
Oil/air cooler units consists of the metal
housing (1), motor (2), axial fan (3) and
heat exchanger (4), and low noise feed
pump (5) with excellent suction
performance. The oil connections are
external.
OKAF-EL4,5,6
Oil/air cooler units consist of the metal
housing (1), motor (2), axial fan (3), heat
exchanger (4), low noise feed pump (5)
with excellent suction performance and
filter (6). The oil connections are
external, together with access to the
filter element for cleaning and changing.
The filters are fitted with visual clogging
indicators, as standard.
E 5.801.1/01.05
Example
CONSTRUCTION FOR
OKA & OKAF EL7-11
OKA-EL7-11
OKA-EL7-11
OKAF-EL7-11
OKAF-EL7-11
OKA-EL7-11
Oil/air cooler units consist of the metal
housing (1), motor (2), axial fan (3), heat
exchanger (4), and low noise feed pump
(5) with excellent suction performance.
The oil connections are external.
OKAF-EL7-11
Oil/air cooler units consist of the metal
housing (1), motor (2), axial fan (3), heat
exchanger (4), and low noise feed pump
(5) with excellent suction performance
and filter (6). The oil connections are
external, together with access to the
filter element for cleaning and changing.
The filters are fitted with visual clogging
indicators, as standard.
E 5.801.1/01.05
Example
= 4.78 [kW]
t 60
Cooler selection:
Desired oil temperature: 60 C
Ambient temperature (air): 30 C
Pv
P01 =
[kW/C]
T1 - T3
4.78
P01 =
= 0.159
[kW/C]
60 - 30
A 10% safety margin is
recommended to allow for
element contamination, and
therefore the specific power is:
P01 1.1 = 0.175 kW/C
The power loss 0.175 kW/C must
be dissipated by an oil cooler.
Suggestion:
Cooler OK-EL2H,
P01 = 0.18 kW/C at 80 l/min.
Example 2:
The power loss can also be
estimated: With unrestricted flow
approx. 15 to 20% of the drive
power. With restricted flow up to
30% of the drive power.
Weight [kg]
1.1.
OK-EL1H
*120
**
0.04
60
16
130
2000
OK-EL2S
*180
4/63
0.18
64
16
130
2000
13
OK-EL2H
*180
2/63
0.25
80
16
130
2000
13
OK-EL3S
*180
4/63
0.18
66
16
130
2000
17
OK-EL3H
*180
2/71
0.55
85
16
130
2000
17
OK-EL4L
*200
6/71
0.25
63
16
130
2000
31
OK-EL4S
*200
4/71
0.37
72
16
130
2000
31
OKA-EL4L
28-40
24/34
6/90
1.1
68
80
350
34
OKA-EL4S
28-40
36/52
4/90
1.8
75
80
350
34
OKAF-EL4L 28-40
24/34
6/90
1.1
68
80
350
LPF 160 41
OKAF-EL4S 28-40
36/52
4/90
1.8
75
80
350
LPF 160 41
OK-EL5L
*250
6/80
0.37
65
16
130
2000
38
OK-EL5S
*250
4/90
1.1
75
16
130
2000
38
OKA-EL5L
28-40
24/34
6/90
1.1
70
80
350
41
OKA-EL5S
28-40
36/52
4/90
1.8
80
80
350
41
OKAF-EL5L 28-40
24/34
6/90
1.1
70
80
350
LPF 160 48
OKAF-EL5S 28-40
36/52
4/90
1.8
80
80
350
LPF 160 48
OK-EL6L
*250
6/80
0.37
67
16
130
2000
43
OK-EL6S
*250
4/90
1.1
77
16
130
2000
47
OKA-EL6L
28-40
24/34
6/90
1.1
70
80
350
50
OKA-EL6S
28-40
36/52
4/90
1.8
81
80
350
50
OKAF-EL6L 28-40
24/34
6/90
1.1
70
80
350
LPF 160 57
OKAF-EL6S 28-40
36/52
4/90
1.8
81
80
350
LPF 160 57
Pv =
TECHNICAL DETAILS
Displacement [cm/U]
Designation:
PV = Power loss [kW]
P01 = Specific cooling capacity [kW/C]
V = Tank contents [l]
oil = Density of the oil [kg/l]
for mineral oil: 0.915 kg/l
Coil = Specific heat capacity [kJ/kgC]
for mineral oil 1.88 kJ/kgC
T = Temperature increase in the
system [C]
t
= Operating time [min]
T1 = Desired oil temperature [C]
T3 = Ambient temperature [C]
Example 1:
Measurement of the power loss
on existing units and machinery.
For this method the temperature
increase of the oil is measured
over a certain period. The power
loss can be calculated from the
temperature increase.
Parameters:
The oil temperature increases
from 20 C to 45 C over
15 minutes.
The tank contains 100 l.
Heat to be dissipated:
T coil oil V
[kW]
Pv =
t 60
1.
Type of cooler
COOLER
SELECTION
COOLER
SELECTION
T coil oil V
[kW]
t 60
40 1.88 0.915 400
PV =
= 28.7 [kW]
16 60
PV =
Cooler selection:
Desired oil temperature: 60 C
Ambient temperature (air): 30 C
P01 =
P01 =
Pv
T1 - T3
28.7
60 - 30
[kW/C]
= 0.96
[kW/C]
2/90
2/112
2/90
4/100 2/112
2/90
6/90 2/112
2/90
4/100 2/112
6/90
4/100
2/90
6/90 2/112
2/90
4/100 2/112
2/90
6/90 2/112
2/90
4/100 2/112
8/90
6/90
2/90
8/90 2/112
2/90
6/90 2/112
2/90
8/90 2/112
2/90
6/90 2/112
8/100
6/112
2/90
8/100 2/112
2/90
6/112 2/112
2/90
8/100 2/112
2/90
6/112 2/112
8/132
6/132
2/90
8/132 2/112
2/90
6/132 2/112
2/90
8/132 2/112
2/90
6/132 2/112
6/90
E 5.801.1/01.05
1.1
3.0
1.1
3.0
1.1
3.0
1.1
3.0
1.1
3.0
0.55
1.1
3.0
5.5
3.0
5.5
3.0
5.5
3.0
5.5
3.0
5.5
3.0
5.5
3.0
5.5
3.0
5.5
3.0
0.55 5.5
3.0
1.1 5.5
3.0
0.55 5.5
3.0
1.1 5.5
1.1
2.2
3.0
1.1 5.5
3.0
2.2 5.5
3.0
1.1 5.5
3.0
2.2 5.5
2.2
3.0
3.0
2.2 5.5
3.0
3.0 5.5
3.0
2.2 5.5
3.0
3.0 5.5
76
84
76
84
77
84
77
84
77
84
70
77
70
77
70
77
72
80
72
80
72
80
77
85
77
85
77
85
16 130 2000
16 130 2000
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
16 130 2000
16 130 2000
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
16 130 2000
16 130 2000
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
16 130 2000
16 130 2000
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
16 130 2000
16 130 2000
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
320/130
6 80 240
Weight [kg]
76
84
1.1
3.0
6/90
4/100
*300
*300
100/150
180
100/150
180
100/150
180
100/150
180
*300
*300
100/150
180
100/150
180
100/150
180
100/150
180
*330
*330
100/150
180
100/150
180
100/150
180
100/150
180
*330
*330
100/150
180
100/150
180
100/150
180
100/150
180
*330
*330
100/150
180
100/150
180
100/150
180
100/150
180
40/58
69
OKA-EL7S
40/58
69
OKAF-EL7L
40/58
69
OKAF-EL7S
40/58
69
OK-EL8L
OK-EL8S
OKA-EL8L
40/58
69
OKA-EL8S
40/58
69
OKAF-EL8L
40/58
69
OKAF-EL8S
40/58
69
OK-EL9LL
OK-EL9L
OKA-EL9LL
40/58
69
OKA-EL9L
40/58
69
OKAF-EL9LL 40/58
69
OKAF-EL9L
40/58
69
OK-EL10LL
OK-EL10L
OKA-EL10LL 40/58
69
OKA-EL10L
40/58
69
OKAF-EL10LL 40/58
69
OKAF-EL10L 40/58
69
OK-EL11LL
OK-EL11L
OKA-EL11LL 40/58
69
OKA-EL11L
40/58
69
OKAF-EL11LL 40/58
69
OKAF-EL11L 40/58
69
* max oil flow
Type of cooler
OK-EL7L
OK-EL7S
OKA-EL7L
Designation:
= Power loss [kW]
= Specific cooling capacity [kW/C]
= Tank contents [l]
= Density of the oil [kg/l]
for mineral oil: 0.915 kg/l
Coil = Specific heat capacity [kJ/kgC]
for mineral oil 1.88 kJ/kgC
T = Temperature increase in the
system [C]
t
= Operating time [min]
T1 = Desired oil temperature [C]
T3 = Ambient temperature [C]
Example 1:
Measurement of the power loss
on existing units and machinery.
For this method the temperature
increase of the oil is measured
over a certain period. The power
loss can be calculated from the
temperature increase.
Parameters:
The oil temperature increases
from 20 C to 60 C over
16 minutes.
The tank contains 400 l.
Heat to be dissipated:
PV
P01
V
oil
Displacement [cm3/U]
54
59
74
79
LPF 280
82
LPF 280
-
87
58
63
78
83
LPF 280
86
LPF 280
-
91
109
109
133
133
LPF 280
141
LPF 280
-
141
142
142
167
167
LPF 280
175
LPF 280
-
175
190
190
216
216
LPF 280
224
LPF 280
224
30
0.75
28
EL6S
26
0.65
0.6
EL5S
22
20
EL6L
18
EL5L
16
EL4S
14
0.2
0.15
EL2S
0.1
EL1H
0.05
0
0
20
40
60
80
100
120
0.4
0.25
EL3S
EL2H
0.45
0.3
EL4L
10
0.5
0.35
EL3H
12
0.55
24
0.7
140
160
180
200
220
240
0
260
OK EL7-11
Tolerance: 5%
120
110
2.75
EL11L
2.5
2.25
EL11LL
80
EL10L
70
1.75
EL10LL
60
EL8S
EL7S
50
40
EL8L
EL7L
30
1.5
EL9L
1.25
EL9LL
1
0.75
20
0.5
10
0.25
0
0
30
60
90
120
150
180
210
240
270
300
330
360
390
0
420
E 5.801.1/01.05
90
100
3.5
EL3
EL1
3.0
Pressure drop at 30 mm/s [bar]
EL2
2.5
2.0
EL5
EL4
1.5
EL6
1.0
0.5
0.0
0
30
60
90
120
150
180
210
240
270
300
2
EL7
1.8
EL8
EL11
1.6
EL10
1.4
EL9
1.2
1
0.8
0.6
0.4
0.2
0
0
30
60
90
120
150
180
210
240
270
300
330
360
390
420
E 5.801.1/01.05
10
0.35
15
0.5
22
0.75
30
1
46
1.4
68
1.9
100
2.5
150
3.5
2.
MODEL TYPE
(also order example)
Type of cooler
OK-EL
= Oil/air cooler
OKA-EL = Oil/air cooler with built-in feed pump
OKAF-EL = Oil/air cooler with built-in feed pump and filter
Size / motor speed
1-11
= See hydraulic details 1.3.
LL
= 8 pl (750 min-1)
L
= 6 pl (1000 min-1)
S
= 4 pl (1500 min-1)
H
= 2 pl (3000 min-1)
Displacement cm/rev
28, 40
= (OKA/OKAF-EL4 -> EL6, see technical details 1.1.)
40, 58, 69 = (OKA/OKAF-EL8 -> EL11, see technical details 1.2.)
Type code and modification number
For the latest version of each cooler, please see the table in our internet site.
Clogging indicators (only OKAF)
A
= Without clogging indicator
B
= With visual indicator (*)
C
= With electrical indicator
D
= With electrical and optical indicator
Fluids
M
Motor voltage
A
= Standard voltages and frequencies for threephase motor
50 Hz: 380 - 420 V (Y) / 220-240 V ()
60 Hz: 440 - 480 V (Y) / 254-277 V ()
Except for EL1, for which the standard voltage is 220-240 V, 50/60Hz, single phase
Other special voltages and frequencies on request and clearly written
Size of filter (only OKAF)
OKAF-EL4-6
= LPF160
OKAF-EL7-11
= LPF280
Filtration rating in micron, Viscosity up to 80 mm/s (only OKAF)
(5 BN3HC)
8
= 5 m Betamicron-3-N
4
= 10 m Betamicron-3-N (10 BN3HC) *
5
= 20 m Betamicron-3-N (20 BN3HC)
Paint
1
E 5.801.1/01.05
Accessories
AITF
= Thermostat (fixed)
IBP
= Heat exchanger with integrated bypass valve
IBT
= Heat exchanger with integrated thermo-bypass valve
GP
= Vibration absorber
3.
DIMENSIONS
3.1.
OK-EL1
3.2.
OK-EL2-6
Plug
Plug
3.3.
OK-EL7-8
(4x) slot F
Plug
3.4.
OK-EL9-11
E 5.801.1/01.05
Plug
10
OKEL1 H
OKEL2 S,H
OKEL3 S,H
OKEL4 L,S
OKEL5 L,S
OKEL6 L,S
OKEL7 L,S
OKEL8 L,S
OKEL9 L
OKEL10 L
OKEL11 L
A1
10
355
355
455
520
562
640
726
726
880
1030
1180
B
25
400
420
527
580
600
612
612
709
758
804
C1
10
200
330
380
485
542
584
706
706
790
930
1050
D1
2
255
255
255
410
410
410
410
410
750
750
750
D2
2
150
160
290
425
482
482
560
560
700
700
700
D3
2
295
295
295
450
450
450
450
450
790
790
790
E1
5
289
289
389
439
439
500
600
630
760
910
1060
E2
5
41
41
41
51
72
80
73
58
75
75
75
E3
5
88
58
58
104
94
74
74
74
116
116
116
F
/slot
9
9
9
9
9
9
9x20
9x20
12
12
12
W1
Min.*
150
500
800
1200
1500
1800
1200
1200
2500
2800
3000
W2
Min.*
100
200
300
400
500
600
600
600
900
900
1000
Z1
Z3
G"
G"
G"
G1"
G1"
G1 "
G1 "
G1 "
G1 "
G1 "
G1 "
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
3.5.
OKA/OKAF-EL4-6
3.6.
Plug
3.7.
OKAF-EL7-8
(4x)
slot F
Plug
OKA/OKAF-EL9-11
(4x)
slot F
4.
E1
5
439
439
500
439
439
500
600
630
760
910
1060
600
630
760
910
1060
5.
E2
5
51
72
80
51
72
80
83
68
75
75
75
83
68
75
75
75
E3
5
104
94
74
104
94
74
74
74
116
116
116
74
74
116
116
116
F
/slot
9
9
9
9
9
9
9x20
9x20
12
12
12
9x20
9x20
12
12
12
W1
Min.*
1200
1500
1800
1200
1500
1800
1200
1200
2500
2800
3000
1200
1200
2500
2800
3000
W2
Z1
Min.* (IN)
400 G1 "
500 G1 "
600 G1 "
400 G1 "
500 G1 "
600 G1 "
600 G 2"
600 G 2"
900 G 2"
900 G 2"
1000 G 2"
600 G 2"
600 G 2"
900 G 2"
900 G 2"
1000 G 2"
Z2(3x)
Z3
G 1"
G 1"
G1 "
G 1"
G 1"
G1 "
G1 "
G1 "
G1 "
G1 "
G1 "
G1 "
G1 "
G1 "
G1 "
G1 "
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
M22x1.5
NOTE
The information in this brochure relates to the operating
conditions and applications described.
For applications or operating conditions not described,
please contact the relevant technical department.
Subject to technical modifications.
E 5.801.1/01.05
A1
B
C1
C2
D1 D2 D3
10 25 10 25
2
2
2
OKAEL4 L,S
520 690
485 578 410 425 450
OKAEL5 L,S
562 700
542 653 410 482 450
OKAEL6 L,S
640 720
584 709 410 482 450
OKAFEL4 L,S 520 690
485 631 410 425 450
OKAFEL5 L,S 562 700
542 688 410 482 450
OKAFEL6 L,S 640 720
584 725 410 482 450
OKAEL7 L,S
736 612
706 775 560 560 600
OKAEL8 L,S
736 612
706 815 560 560 600
OKAEL9 L
880 709
790 910 830 700 870
OKAEL10 L
1030 758
930 1050 830 700 870
OKAEL11 L
1180 804 1050 1150 830 700 870
OKAFEL7 L,S 736 612
706 825 560 560 600
OKAFEL8 L,S 736 612
706 846 560 560 600
OKAFEL9 L
880 709
790 936 830 700 870
OKAFEL10 L 1030 758
930 1071 830 700 870
OKAFEL11 L 1180 804 1050 1191 830 700 870
* for smaller distances please contact our technical office
11