OPERATION MODES
3BF15
PARALLEL OPERATION
Share load ?
WNSFI-S / HLX / 3BF15 / 25.03.1996
Page 2 / 9 / DROOP_KW.PPT
Frequency / Hz
SYSTEM SPEED
IS CONTROLLED
BY UTILITY
52
50
48
46
0
25
50
75
100
a) with kW feedback
DROOP
kW / %
Speed
control
speed
reference
ENGINE
speed feedback
TRUE kW CONTROL
Load
reference
100
kW feedback
75
50
kW
reference
25
ENGINE
0
0
25
50
75
100
kW / %
Speed ref.
kW ref.
Speed
control
54
GENERATOR 1
Frequency / Hz
Frequency / Hz
54
GENERATOR 2
52
50
48
46
46
0
25
50
75
100
25
kW / %
50
75
kW / %
Speed
control
Speed
ref.
speed feedback
+
Speed
control
speed
reference
ENGINE
Paralleling lines
-
+
WNSFI-S / HLX / 3BF15 / 25.03.1996
Page 6 / 9 / DROOP_KW.PPT
100
ENGINE
kW feedback
Disadvantages
Better performance
new control methods
Easy to adjust, when person is
familiar with the controller
Possibility to create standard
settings as adjustments are given
as numbers
No drafting in setting values
More expensive
Requires more understanding
of speed control basics when
adjusting, because there are more
parameters
Utility system
Disadvantages
Good performance
Limiters for generator protection
Easy to adjust, when person is
familiar with the controller
Possibility to create standard
settings as adjustments are given
as numbers
Interchangeability through
standardsettings
No drifting in setting values