AEG
Power Solutions
Declaration of Conformity to Greek Standards
We, AEG Power Solutions GmbH, declare under our sole responsibility that the product
Model: PROTECT PV10
Ratings: 10KVA
to which this declaration relates is in conformity with the following limits, standards or other normative
documents
1. The inverter complies with safety rules according to Greek’s standard (PPC) defining connection of
solar inverters to the LV grid
2. As per Greek's standards (PPC), the inverter will disconnect automatically from LV line if the public
grid is disconnected.
3. 2redundant relays are used to handle the disconnection and reconnection process through the
intemal software of 2 redundant Digital Signal Processors (DSPs). Details abut the process are:
+ The islanding function implemented internally is in compliance with German standard VDE0126-1-1.
+ The inverter monitors the grid and disconnects if the grid voltage is out of the following range
0.8 Vnom-1.15 Vnom and 49.5 Hz — 50.5 Hz.
+ The disconnection time form the grid is <0.5 s.
+ The software is protected by password and is not accessible by the final customer by end user.
* Connection and reconnection after clearance of grid failure is not less than 180s.
4, The total harmonic distortion (THD) of the output current is < 5 %.
5, The inverter has been through all factory routine tests where all specified limits and isolation system
are tested.
6. The maximum DC current level of the output current into the grid is < 0.5% of the nominal current.
tssue in Zwanenburg, The Netherlands, on 29 November 2010
Freddy Canizales Daniel Fuselier
OK
AS .
Product Manager Director of Quality
AtPorSoltosBY AEG Powe Sdutons Grol
aoe Pov Gril Sere En Sepremnsie
“B14 Zenenbiry- The Neen S358 WarsienBeecks- Garman
Tel 431 2077600 @ Fac tS 204077 a Tel 492900 7630 +Fac 49 2902763680